Professional Documents
Culture Documents
17
PVsyst TRIAL
PVsyst - Simulation report
Grid-Connected System
PVsyst TRIAL
Thumthumke Dada, Kushadevi - Nepal
PVsyst TRIAL
PVsyst TRIAL
Author
PVsyst TRIAL
Project: New Project
Variant: New simulation variant
PVsyst V7.2.17
VC1, Simulation date:
11/08/22 09:52
PVsyst TRIAL
with v7.2.17
Project summary
Geographical Site Situation Project settings
Thumthumke Dada, Kushadevi Latitude 27.58 °N Albedo 0.20
Nepal Longitude 85.47 °E
Altitude 1786 m
Time zone UTC+5.8
Meteo data
Lapsetar, Kushadevi
Meteonorm 8.0 (1981-2010), Sat=100% - Synthetic
System summary
PVsyst TRIAL
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 27500 units Nb. of units 11 units
Pnom total 11.00 MWp Pnom total 11.00 MWac
Pnom ratio 1.000
Results summary
Produced Energy 18 GWh/year Specific production 1658 kWh/kWp/year Perf. Ratio PR 87.14 %
PVsyst TRIAL
Project and results summary
Main results
Loss diagram
Special graphs
Table of contents
PVsyst TRIAL
PVsyst TRIAL
11/08/22 PVsyst Evaluation mode Page 2/6
Project: New Project
Variant: New simulation variant
PVsyst V7.2.17
VC1, Simulation date:
11/08/22 09:52
PVsyst TRIAL
with v7.2.17
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 32 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PVsyst TRIAL
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model IBEX-144MHC-Duo-400Wp-144 cells Model APS1000-PV-1-550-5
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 400 Wp Unit Nom. Power 1000 kWac
Number of PV modules 27500 units Number of inverters 11 units
Nominal (STC) 11.00 MWp Total power 11000 kWac
Modules 1100 Strings x 25 In series Operating voltage 804-1425 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.00
Pmpp 10.02 MWp
U mpp 929 V
I mpp 10785 A
PVsyst TRIAL
Total PV power Total inverter power
Nominal (STC) 11000 kWp Total power 11000 kWac
Total 27500 modules Number of inverters 11 units
Module area 55883 m² Pnom ratio 1.00
Cell area 49899 m²
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 1.4 mΩ Loss Fraction -1.3 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst TRIAL
IAM loss factor
Incidence effect (IAM): Fresnel, AR coating, n(glass)=1.526, n(AR)=1.290
PVsyst TRIAL
11/08/22 PVsyst Evaluation mode Page 3/6
Project: New Project
Variant: New simulation variant
PVsyst V7.2.17
VC1, Simulation date:
11/08/22 09:52
PVsyst TRIAL
with v7.2.17
Main results
System Production
Produced Energy 18 GWh/year Specific production 1658 kWh/kWp/year
Performance Ratio PR 87.14 %
PVsyst TRIAL
Balances and main results
PVsyst TRIAL
February 116.0 41.39 11.60 149.9 147.8 1.480 1.459 0.885
March 163.4 61.41 17.33 183.5 180.0 1.764 1.739 0.861
April 151.0 73.45 22.12 148.3 144.6 1.413 1.393 0.854
May 173.2 87.61 23.66 156.9 152.5 1.491 1.471 0.852
June 149.3 81.02 23.44 130.7 126.8 1.252 1.234 0.858
July 141.1 84.86 22.08 125.0 121.0 1.208 1.191 0.866
August 154.6 74.70 21.99 146.6 142.8 1.404 1.384 0.859
September 131.7 62.36 21.08 138.2 134.8 1.318 1.299 0.855
October 144.6 59.39 18.81 175.0 172.2 1.688 1.664 0.865
November 125.8 37.78 13.69 180.9 178.4 1.780 1.755 0.882
December 121.7 28.58 8.55 192.8 190.2 1.934 1.907 0.899
Year 1690.7 727.51 17.61 1902.7 1863.4 18.497 18.237 0.871
PVsyst TRIAL
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst TRIAL
11/08/22 PVsyst Evaluation mode Page 4/6
Project: New Project
Variant: New simulation variant
PVsyst V7.2.17
VC1, Simulation date:
11/08/22 09:52
PVsyst TRIAL
with v7.2.17
Loss diagram
1691 kWh/m² Global horizontal irradiation
+12.5% Global incident in coll. plane
+1.25%
-2.10%
-1.09%
PV loss due to temperature
PVsyst TRIAL
0.00% Inverter Loss due to voltage threshold
-0.02% Night consumption
18.24 GWh Available Energy at Inverter Output
18.24 GWh Energy injected into grid
PVsyst TRIAL
PVsyst TRIAL
11/08/22 PVsyst Evaluation mode Page 5/6
Project: New Project
Variant: New simulation variant
PVsyst V7.2.17
VC1, Simulation date:
11/08/22 09:52
PVsyst TRIAL
with v7.2.17
Special graphs
Daily Input/Output diagram
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
11/08/22 PVsyst Evaluation mode Page 6/6