You are on page 1of 1

Determination of Reflux Ratio and Boil-Up Rate for Distillation

Column with Intermittent Take-Off-Type Reflux Control

Yi-Chung Chang,' U. S. Bureau of Mines, Morgantown, W. Va., and Liang-tseng Fan,2


West Virginia University, Morgantown, W. Va.

N BATCH distillation work, accurate variables can be expressed by not given, they can be determined ex-
I control of reflux ratio is important. BT - 3600_
= ~
C _
perimentally.
To determine the leakage, the column
Reflux ratio isa major factor affecting
sharpness of separation and time of
Bt +
3600 C (1)
may be operated under total reflux and
distillation. Inaccuracy in its control where the volume of the condensate collected
often leads to w o n g interpretation of in the receiver over a certain interval
R = reflux ratio = reflux/product
of time measured. Boil-up rate usually
data. B = boil-up rate a t top of column
One of the many reflux regulating de- excluding internal reflux, ml. has no appreciable effect on leakage;
vices is an intermittent take-off type per hour the column can be operated a t any
[Brandt, P. L., Perkins, R. B., ,Jr., T = reflux time, seconds per cycle convenient rate.
Halverson, L. K., Oil GUS J . 45, KO. t = discharge time, seconds per Boil-up rate may be determined by
31, 86,102 (1946)], as shown in Figure 1. cycle a rate device placed between the pot
C = volume of cup, nil. and the column [Nples et al.,
The condensate from the reflux con- Znd. Eng. Chem. 43, 1452 (1951)l or
denser falls into a small glass cup, to In deriving this equation, it is as-
sumed that the spherical plug fits the by the following formula, if the product,
which a distillate take-off tube is con- P , collected during 1 hour is known.
nected a t the bottom. The interior of seat perfectly, so that during reflux
the cup is ground t o form a valve seat. no condensate can leak out. B =
+
P ( T t ) - 3600(C TL) +(3)
A spherical plug, which fits into this If leakage exists, Equation 1 may be t
seat, seals the distillate tube when modified to include a leakage term. In using Equation 3, C must be known
reflux is to be returned to the column, first. When both B and Care unknown,
the reflux overflowing the cup. BT - 3600 ( C T L ) + (*I the product rate may be measured a t
In operation, reflux from the con- R = Bt +3600 (C + TL) t v o different timer settings using equal
denser falls into the cup, overflows, and boil-up rates, and these two sets of
is returned to the column when the where L = rate of leakage, ml. per
valve is seated, closing the distillate second. values substituted in Equation 3.
line; but the entire reflux is taken over-
head when the valve is lifted. The
T17ith values for B , C, and L given.
the reflux ratio can be calculated by
+ +
B = Pi(T1 t i ) - 360WC T I L ) (4)
tl
reflux ratio can thus be controlled by
suitable timer switch actuation, open-
Equation 2 for each combination of
timer settings. Khen B, C, and L are B = +
Pz(Tz +
t z ) - 3600(C TzL)
(5)
tz
ing and closing the valve. Note. tl must be different from t ~ .
TOSO.E%OID
Depending on the size of the column, By simultaneously solving Equations
the cup has a holdup of from 0.1 to 0.5
ml. and at each lift of the plug, one of
1 4 and 5, B and C can be obtained.
REFLJX
-CON3EVSE3
In one test on a 1-inch column, the
these quantities of distillate is taken leakage through the valve determined
over, in addition to the proportion of under total reflux was 0.71 ml. per
reflux indicated by the timer setting. hour or 0.0002 ml. per second. The dis-
Vnder conditions of low vapor through- tillates collected were 166.5 ml. per hour
put, this holdup becomes an appreci- a t a timer setting of TI = 20 seconds
able part of the total distillate, and the and tl = 2 seconds, and 120.4 ml. per
reflux ratio actually realized is consider- hour a t Tz= 40 seconds, t z = 3 seconds.
ably different from that determined On substituting these values in Equa-
tions 4 and 5 and solving simultane-
by the timer setting as shown in Figure ously, the value for C was 0.18 nil., and
2. If the boil-up rate were calculated PACK€:.
the boil-up rate was 1500 ml. per hour.
COLLKk
from the apparent reflux ratio deter- The boil-up rate determined from the
mined by the setting of the timer and Figure 1. Intermittent take-off reflux- heat removed by the cooling water flow-
the distillate collected in a certain time control device for distillation column ing through the reflux condenser was
interval, considerable error might result. 1430 ml. per hour. Considering the
Using the conditions stipulated for loss of some heat due to imperfect
Figure 2 for a boil-up rate of 1000 ml. insulation, these results agree well.
per hour, the distillate collected in five Without this correction, the boil-up
minutes is 10.3 ml. (assuming no leak- rates calculated by employing the ap-
REFLUX . T I M E - 2 0 SEC.
age). This, when multiplied by 1 plus O l S C H 4 R G E T I M E - 2 SEC.
parent reflux ratio determined by the
the apparent reflux ratio, or 11, will c 5 CUP C A P 4 C I T Y - 0 2 ML timer settings are 1832 ml. per hour for
give a calculated boil-up rate of 1360 the first setting and 1726 for the second
nil. per hour, n hich is 36% off the actual setting.
value. K i t h the type of control described,
Hom-ever, the relationship between the the reflux ratio determined by the
reflux ratio and the other operating ratio of the reflux time and discharge
time can deviate considerably from the
1 Present address, Research Center, BOIL-UP R 4 T E . M U H R actual value. By the procedures de-
IT. S. Steel Corp., Jlonroeville, Pa. scribed, accurate reflux ratios can be
Present address, Kansas State College, Figure 2. Effect of boil-up rate on
Rlanhattan, Kaxi. corrected reflux ratio easily determined and controlled.

VOL. 31, NO. 6, JUNE 1959 1121

You might also like