PART 1 - GENERAL
1.1.1.1 SUMMARY
A. Section includes the insulated sandwich panel system and accessories as shown and specified.
Work includes providing and installing:
1. Wall assemblies
2. Roof assemblies
3. Skylight assemblies
4. Canopy assemblies
B. Related Sections:
1.1.1.2 SUBMITTALS
A. Submit manufacturer’s product data. Include construction details, material descriptions, profiles
and finishes of components.
B. LEED Submittals:
1. Laboratory Test Reports for Credit SS 7.2: For roofing materials with a Solar
Reflectance Index (SRI) for a minimum of 75% of the roof’s surface of 29 or higher for
a steep sloped roof (>2:12) per ASTM E 1980. Emittance to be greater than .90 per
ASTM E 408 or ASTM C 1371.
2. Product Data for Credit MR 4: Provide documentation demonstrating use of materials
with a minimum [10%] [20%] <Insert Number> % recycled content (post-consumer
+ ½ pre-consumer).
3. Product Data for Credit IEQ 8.1: Provide Daylight Autonomy Report showing that the
proposed translucent daylighting system will provide <Insert Number> lux in the
daylit areas for an average of <Insert Number> % of the daylight hours for the entire
year.
4. Provide computer simulation (RADIANCE) that demonstrates that 75% or more of all
regularly occupied spaces achieve daylight illuminance levels of a minimum of
25 footcandles (fc) and a maximum of 500 footcandles (fc) in a clear sky condition on
Sept. 21 at 9 a.m. and 3 p.m.
D. Submit manufacturer’s color charts showing the full range of colors available for factory
finished aluminum.
1. When requested, submit samples for each exposed finish required, in same thickness
and material indicated for the work and in size indicated below. If finishes involve
E. Submit Installer Certificate, signed by installer, certifying compliance with project qualification
requirements.
F. Submit product reports from a qualified independent testing agency indicating each type and
class of panel system complies with the project performance requirements, based on
comprehensive testing of current products. Previously completed reports will be acceptable if
for current manufacturer and indicative of products used on this project.
A. Manufacturer’s Qualifications:
B. Installer’s Qualifications: Installation shall be by an experienced installer, which has been in the
business of installing specified panel systems for at least two consecutive years and can show
evidence of satisfactory completion of projects of similar size, scope and type.
A. The manufacturer shall be responsible for the configuration and fabrication of the complete
panel system.
1. When requested, include structural analysis data signed and sealed by the qualified
professional engineer responsible for their preparation.
2. Standard panel system shall have less than 0.01 cfm/ft² air leakage by ASTM E 283 at
6.24 PSF (50 mph) and no water penetration by ASTM E 331 at 15 PSF; and structural
testing by ASTM E 330.
3. Structural Loads (Wall Assemblies). Provide system capable of handling the following
loads:
C. Deflection Limits:
1. Wall Panel Assemblies: Limited to [L/60] or <Insert Deflection> of clear span for
each assembly component.
B. Store panels on the long edge; several inches above the ground, blocked and under cover in
accordance with manufacturer’s storage and handling instructions.
1.1.1.7 WARRANTY
A. Provide manufacturer's and installer's written warranty agreeing to repair or replace panel
system work, which fails in materials or workmanship within one year from the date of
delivery. Failure of materials or workmanship shall include excessive deflection, deterioration
of finish on metal in excess of normal weathering, defects in accessories, insulated translucent
sandwich panels and other components of the work.
B. Extended Panel Warranty: <Insert Extended Warranty if required> years from date of
delivery.
PART 2 - PRODUCTS
2.1.1.1 MANUFACTURER
A. The basis for this specification is for products manufactured by Kalwall Corporation. Other
manufacturers may bid this project subject to compliance with the performance requirements of
this specification and submission of evidence thereof. Listing other manufacturers’ names in
this specification does not constitute approval of their products or relieve them of compliance
with all the performance requirements contained herein.
B. Kalwall Corporation, Tel: (800) 258-9777 – Fax: (603) 627-7905 – Email: info@kalwall.com
A. Face Sheets:
a. Color stability: Full thickness of the exterior face sheet shall not change color more
than 3 CIE Units DELTA E by ASTM D 2244 after [3] [5] years outdoor South
Florida weathering at 5° facing south, determined by the average of at least three
white samples with and without a protective film or coating to ensure long-term
color stability. Color stability shall be unaffected by abrasion or scratching.
b. Strength: Exterior face sheet shall be uniform in strength, impenetrable by hand
held pencil and repel an impact minimum of [70 ft. lbs.)] [230 ft. lbs.)] without
fracture or tear when impacted by a 3-1/4” diameter, 5 lb. free-falling ball per UL
972.
c. Strength: Exterior face sheet shall be uniform in strength, with panel meeting
ASTM E1996 and ASTM E1886 or TAS 201, 202 and 203.
d. Erosion Protection: Integral, embedded-glass erosion barrier.
4. Appearance:
a. Exterior face sheet: Smooth, <Insert Thickness> thick and <Insert Color> in
color.
b. Interior face sheet: Smooth, <Insert Thickness> thick and <Insert Color> in
color.
c. Face sheets shall not vary more than ± 10% in thickness and be uniform in color.
B. Grid Core:
C. Laminate Adhesive:
1. Heat and pressure resin type adhesive engineered for structural sandwich panel use,
with minimum 25-years field use. Adhesive shall pass testing requirements specified by
the International Code Council “Acceptance Criteria for Sandwich Panel Adhesives".
2. Minimum tensile strength of 750 PSI when the panel assembly is tested by ASTM C
297 after two exposures to six cycles each of the aging conditions prescribed by
ASTM D 1037.
3. Minimum shear strength of the panel adhesive by ASTM D 1002 after exposure to four
separate conditions:
A. Provide sandwich panels of flat fiberglass reinforced translucent face sheets laminated to a grid
core of mechanically interlocking I-beams. The adhesive bonding line shall be straight, cover
the entire width of the I-beam and have a neat, sharp edge.
B. Standard panels shall deflect no more than 1.9” at 30 PSF in 10’-0” span without a supporting
frame by ASTM E 72.
C. Standard panels shall withstand 1200° F fire for minimum one hour without collapse or exterior
flaming.
E. Roof/Skylight System:
1. Roof/Skylight system shall pass Class A Roof Burning Brand Test by ASTM E 108.
2. (Optional) Roof/Skylight system shall be UL listed as a Class A Roof by UL 790,
which requires periodic unannounced factory inspections and retesting by Underwriters
Laboratories.
F. Roof/Skylight System shall meet the fall through requirements of OSHA 1910.23 as
demonstrated by testing in accordance with ASTM E 661, thereby not requiring supplemental
screens or railings.
1. Extruded aluminum 6063-T6 and 6063-T5 alloy and temper clamp-tite screw type
closure system.
2. Curved closure system may be roll formed.
3. Skylight perimeter closures at curbs shall be factory sealed to panels.
1. [Standard] [Thermally Broken] extruded aluminum 6063-T6 and 6063-T5 alloy and
temper clamp-tite screw type closure system.
D. Fasteners: 300 series stainless steel screws for aluminum closures, excluding final fasteners to
the building.
E. Finish:
1. Manufacturer's factory applied finish, which meets the performance requirements of
AAMA 2604. Color to be <Insert Color and Number> [selected from
manufacturer's standards].
2. Mill (optional)
3. Anodized
A. Windows shall be designed specifically for inclusion in the translucent panel unit wall system
and factory unitized to panels.
a. Project-out bottom
b. Project-in top
c. Fixed lite
C. Construction: All window frame members shall be of heavy gauge 6063-T5 extruded
aluminum with a thermal break. Frame sections shall be coped and joined by stainless steel
screws at each corner. All joints exposed to the weather shall be sealed with an elastic
compound. All openings shall be double weather stripped using T-slot bulb gaskets to insure
minimum air infiltration.
1. Operating sash shall be hollow extruded design, mitered and joined with heavy
reinforcing corners.
D. Hardware:
1. Hinges on operating windows shall be four bar stainless steel with adjustable friction
blocks.
3. HC-2000 Projected windows: Locking hardware shall be of cam lever design and
shall be made of cast white bronze.
4. E-Series Projected windows: Locking hardware shall consist of a single centered cast
aluminum handle with concealed multi-point locking elements (locking handles
optional). Handles are available in [white] [black] or [silver].
E. Glazing:
a. (Optional) 1” translucent panels with <Insert Value> U-factor and faces to match
2-3/4” translucent panels.
A. Windows shall be designed specifically for inclusion in the translucent panel unit wall system
and factory unitized to panels.
a. Project-out bottom
b. Fixed lite
1. E-Series Project out Large Missile windows: Design Pressure 80 PSF. Tested and
certified to TAS 201, TAS 202, TAS 203, ASTM E1886 and ASTM E1996. Poured
and debridged thermal breaks are not acceptable.
2. E-Series Fixed Large Missile windows: Design Pressure 80 PSF. Tested and certified
to TAS 201, TAS 202, TAS 203, ASTM E1886 and ASTM E1996. Poured and
debridged thermal breaks are not acceptable.
D. Hardware:
1. Hinges on project out windows shall be four bar stainless steel with adjustable friction
blocks.
2. Locking hardware shall consist of a single centered cast aluminum handle with
concealed multi-point locking elements (locking handles optional). Handles are
available in [white] [black] or [silver].
E. Glazing:
1. E-Series Large Missile windows shall be factory glazed with 1” nominal laminated
insulated large missile resistant glass.
A. Drainable Fixed Louver, 45°, 2-3/4” deep, shall be designed specifically for inclusion in the
translucent panel unit wall system and factory unitized to panels.
B. Performance:
1. Bird Screens: ¾" flat expanded alum. 0.051" thick set in an extruded tubular aluminum
screen frame.
2. Insect Screens: 18-16 aluminum mesh set in an extruded tubular aluminum screen
frame.
3. Blank-off plates: 0.063" thick.
1. Exterior face sheets: Smooth, .070 thick and <Insert Color> in color.
2. Interior face sheets: Smooth, [.045 S-171] [.045 Type 25] thick and <Insert Color> in
color.
3. Light Transmission 1%.
1. Materials: Panel face shall be two ply construction consisting of .063” aluminum and .
125” thick hardboard.
2. “U” factor: [.17 “U” Alum I-beam] OR [.11 “U” Thermally broken I-beam]
3. Construction: Components shall be laminated as one monolithic unit by a laminator
with minimum 15 years of experience. Adhesive shall be permanent elastic type
neoprene rubber based applied to 100% of the surface.
4. Finish:
PART 3 - EXECUTION
3.1.1.1 EXAMINATION
B. Do not proceed with panel installation until unsatisfactory conditions have been corrected.
3.1.1.2 PREPARATION
A. Metal Protection:
1. Where aluminum will contact dissimilar metals, protect against galvanic action by
painting contact surfaces with primer or by applying sealant or tape recommended by
manufacturer for this purpose.
3.1.1.3 INSTALLATION
A. Install the panel system in accordance with the manufacturer's suggested installation
recommendations and approved shop drawings.
1. Anchor component parts securely in place by permanent mechanical attachment system.
2. Accommodate thermal and mechanical movements.
3. Set perimeter framing in a full bed of sealant compound, or with joint fillers or gaskets
to provide weather-tight construction.
B. Install joint sealants at perimeter joints and within the panel system in accordance with
manufacturers suggested installation instructions.
B. Repair or replace work that does not pass testing or that is damaged by testing and retest work.
3.1.1.5 CLEANING
A. Clean the panel system interior and exterior, immediately after installation.