Professional Documents
Culture Documents
TABLE OF CONTENTS
SCOPE ....................................................................................................................................................3
DEFINITIONS..........................................................................................................................................3
SELECTION ............................................................................................................................................3
DESIGN ...................................................................................................................................................5
TABLE 1..................................................................................................................................................7
LIST OF TABLES
TABLE 1..................................................................................................................................................8
Revision 2 Memo
OCT/2000 This specification has been revised to reflect the current design basis
1. Incorporate latest IEC Standards
2. Updated for current ECS Standards
3. Revised motor voltages
4. Incorporated CHAD Project Addendum
ESSO EXPLORATION &
PRODUCTION CHAD INC.
ECS 16-7-1
MOTOR APPLICATION
Page 3 of 8
SCOPE
1.1 This specification covers mandatory requirements governing the application of motors.
R2 1.3 A pound sign (#) indicates that Purchaser/ESSO review/approval is required before
design is finalized.
DEFINITIONS
R2 2.1 Acceptable and Preferred Practices - where this specification lists more than one type of
equipment or method as acceptable or preferred, the contractor shall make the selection
based on optimum cost benefits. Optimum cost benefits may be achieved by reducing
maintenance and operative expense through initial added investment. Economic basis
for calculating optimum cost benefits will be agreed to by Purchaser/ESSO.
2.2 The definitions in ECS 16-9-1 shall also apply to this specification.
R2 3.1 Applicable standards of manufacture and testing for motors are given in ECS 16-9-1.
3.2 The equipment and materials used shall be all new and conform to the latest revision of
ECS 16-9-1.
SELECTION
R2 # 4.1 Squirrel-cage induction motors are preferred for all applications. Synchronous or other
type induction motors are acceptable when their characteristics are more appropriate for
an application, but their use must be approved by Purchaser. All motors shall be
approved and labelled in accordance with applicable IEC Standards. Motors for use in
IEC Zone 1 and 2 shall be labelled and approved for the zone and shall be suitable for
all atmospheres in the particular group.
4.2 If synchronous motors are used, motors shall have brushless excitation systems with
rotating exciters.
R2 * 4.3 Table 1 lists the Enclosure Selection Requirements. Special project requirements will be
specified by Purchaser/ESSO.
a. All motors used in IEC Zone 1 shall be the IEC equivalent of the API explosion
proof.
ESSO EXPLORATION &
PRODUCTION CHAD INC.
ECS 16-7-1
MOTOR APPLICATION
Page 4 of 8
b. All motors used in IEC Zone 2 shall be the IEC equivalent of the API totally
enclosed fan-cooled (TEFC).
c. All motors used in non-hazardous areas of a process facility shall be the IEC
equivalent of the API TEFC or better.
d. All motors used in non-process related facilities will have suitable enclosures as
per IEC.
e. All motors requiring filters in a process facility shall have re-usable filters,
suitable for adequate protection of the motor in the dusty environment.
R2 # 4.5 Modifications to Table 1 shall be made, with Purchaser's approval, where special
conditions make this necessary. For example:
4.6 Transient rotor temperature shall be checked for non-zone 1 motors driving fans and
other high-inertia loads in Zone 2 locations. Calculated rotor temperature during a
normal start from design operating temperature must not exceed 80% of the
"autoignition" temperature in ºC of the gas or vapour involved.
4.8 If the need for filters is questionable, motors shall have provisions for future installation
of filters. Provisions shall permit filters to be installed readily in ventilating openings or
to substitute new ventilating opening covers having filter frames attached. The motor
ventilating system shall be designed for operation with filters.
4.9 3-phase motors shall be used in all critical services, such as process units or boiler
plants, 0.37 kW and larger.
ESSO EXPLORATION &
PRODUCTION CHAD INC.
ECS 16-7-1
MOTOR APPLICATION
Page 5 of 8
4.10 Horizontal motors shall not normally be used in a vertical application. If used in a
vertical application they shall be of a design which ensures proper lubrication of top and
bottom bearings. For outdoor locations such as air coolers, motors will have drip covers
installed above them and drain holes in the lower end bell.
R2 # 4.11 Vertical motors shall be of the solid-shaft type. Hollow-shaft vertical motors may be
proposed for Purchaser's approval when their characteristics are more appropriate for
an application. If hollow-shaft motors are used they shall be equipped with bolted
couplings; screwed joints are not acceptable.
* 4.12 Grease fittings shall be specified on motors for use in a plant where re-greasing in
service is practiced.
* 4.13 To ensure that motors 1100 kW and smaller have suitable performance characteristics
2 2
for starting and reaccelerating high inertia Wk (kgm ) loads, such as fans and
centrifugal or axial compressors, the following information shall be supplied to the motor
vendor:
R2 * 4.14 Operating voltages for 60 Hz motors shall be as follows, unless specified on the motor
data sheet:
DESIGN
5.1 When resistance temperature detectors are provided in the stator winding, one of the
detectors shall be connected to a temperature indicator-controller with high alarm
contacts as follows:
b. Indicator shall be capable of reading at least 20ºC above controller set point.
R2 # 5.9 Single tube coolers may be used for totally-enclosed, water-air cooled motors and the
IEC equivalents if the coolers are mounted below the motor in a design, approved by
Purchaser/ESSO, which provides the following:
a. Baffling against leaks impinging directly on windings.
b. Vertical sections in paths from cooler to fan inlets with design air velocity under
200 meters/minute.
c. Indication of water leaks.
d. Access to cooler for maintenance and its removal without moving the motor.
5.10 High and low flow devices shall be provided in the cooling water circuit of totally-
enclosed, water-air-cooled or IEC equivalent motors. The high flow device shall operate
an alarm and the low flow device shall operate an alarm immediately and then trip the
motor after a time delay through a hand reset lockout relay.
ESSO EXPLORATION &
PRODUCTION CHAD INC.
ECS 16-7-1
MOTOR APPLICATION
Page 7 of 8
TABLE 1
Zone 2 Class 1 Division Oil immersed, o SQUIRREL CAGE INDUCTION AND BRUSHLESS
non-hazardous 2 and non- Powder-filled/sand filled, q SYNCHRONOUS MOTORS (3-phase, and 1-phase induction
locations, hazardous TypeN without starting winding cutout)
outdoor or locations, IP44 or higher
protected (2). outdoor or IPW24 a. Totally-enclosed (non-ventilated or fan
protected (2). Alternatively as specified in cooled)
Zone 1 b. Weather-protected Type ll
Zone 2 Class 1 Division Oil immersed, o SQUIRREL CAGE INDUCTION AND BRUSHLESS
non-hazardous 2 and non- Powder-filled/sand filled, q SYNCHRONOUS MOTORS
locations, hazardous TypeN (3-phase, and 1-phase induction without starting winding
indoor not locations, indoor IP12,IP22 cutout)
subject to not subject to IP44 or higher
hosing down. hosing down. Alternatively as specified in a Drip-proof (1)
Zone 1 b b. Totally-enclosed (non-ventilated or fan-cooled)
Zone 2 Class 1 Division Oil immersed, o 1 PHASE MOTORS WITH ARCING DEVICE
locations: 2 locations: Powder-filled/sand filled, q
indoor, outdoor indoor, outdoor TypeN Explosion proof
or protected (2). or protected (2) IP44 or higher
Alternatively as specified in 3-PHASE OR DC MOTORS WITH SLIP RINGS OR
Zone 1 COMMUTATORS
a Explosion proof
b Totally-enclosed forced-ventilated (1)
c Totally-enclosed pressurized (1)
R2 Table 1 Notes:
R2