In all cases, (T) – Tensile force; (C) – Compressive force
Structural Design of Roof Trusses to Eurocode 3
All structural steel employed in the design has the following properties; fy (Yield strength) 275N/mm2 fu (ultimate tensile strength 430N/mm2
3.4 Design of diagonal Members (considering maximum effects)
LOAD CASE 1: DEAD LOAD + IMPOSED LOAD only
Fu = γGjGk + γQkQk Ultimate design force (NEd) = 1.35Gk + 1.5Qk #REF! compressive LOAD CASE 2: DEAD LOAD + IMPOSED LOAD + WIND LOAD acting simultaneously Partial factor for permanent actions (DK) Partial factor for leading variable actions (Wk) Therefore ultimate design force in the member = Fu = γGjGk + #REF! compressive γWkWk = Gk + 1.5Wk. LOAD CASE 3: DEAD LOAD + WIND LOAD acting simultaneously Partial factor for permanent actions (DK) Partial factor for leading variable actions (Wk) Therefore ultimate design force in the member = Fu = γGjGk + #REF! tensile γWkWk = Gk + 1.5Wk. With a maximum length of 2163mm, a little consideration will show that UA 50 X 50 X 6 will satisfy all the necessary limit state requirements. CHECK FOR DEFLECTION Employing UA 50 X 50 X 6 in all members of the roof truss; the deflection due to unfactored imposed load calculated using STAADPRO V8i software is 1.028mm Allowable deflection for roofs (Table 4.1 ENV 1993-1-1:1992) = L/250 = 72 1.028mm < 28.8mm. Therefore deflection is ok 4 Conclusion The analysis and design for the section members have been successfully carried as shown in the calculations above. Whenever the wind load effect is greater than the live load effect, one should always watch out for possible reversal of stresses during load combinations. The design has shown that the provision of UA 50 X 50 X 6 for the entire roof truss will be adequate.