You are on page 1of 5

Add:No.

8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

REFERENCE NUMBER:HT20022132UG-BV4

REPLACE:HT20022132UG-BV3

Technical Specification
for High Voltage Power Cable

Cu/XLPE/CAS/PE
36/66(72.5)kV 1C630mm2

Revision Date Description Designed by Approved by

Technical
BV4 21st/7/2020
Specification

For customer/client signature

Page 1 of 5
Add:No.8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

1 Scope

This specification provided by Hengtong Submarine Power Cable Co., Ltd covers the
application, construction, dimensions, performance and transportation drum of HV power
cable. The design, quotation, manufacture of cables is based on this specification as the
technical part of contract. Matters not mentioned in this specification shall be negotiated by
customer and supplier.

2 Application

Max. continuous operation temperature 90℃


Max. temperature at short circuit(≤5s) 250℃
Lowest recommended temperature during installation 0℃

3 Referent Standards

Document Document title

ISO 9001 Quality Management Systems-Requirements

OHSAS 18001 Occupational health and safety management system

ISO 14001 Environment Management System

IEC 60228-2004 Conductors of insulated cables

Power cables with extruded insulation and their accessories for rated
IEC 60840 voltages above 30kV (Um =36kV) up to 150kV (Um = 170kV)–Test
methods and requirements
Electric cables-Calculation of the current rating-
IEC 60287-1-1-2014 Part 1-1: Current rating equations (100% load factor) and calculation
of losses-General
Electric cables-Calculation of the current rating-
IEC 60287-2-1-2015
Part 2-1: Thermal resistance-Calculation of thermal resistance

Calculations of thermally permissible short circuit currents, taking


IEC 60949-2008
into account non-adiabatic heating effects.

Page 2 of 5
Add:No.8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

4 Diagram of Cable Construction

Nominal Diameter
No. Cable structure Description
thickness (Approx.)
Stranded circular compacted plain annealed
1 Conductor / 29.9
copper conductor(class 2)
Semi-conducting tape and extruded semi-
2 Conductor screen 2×0.12+1.1 32.6
conducting thermosetting compound

3 Insulation XLPE 12.0 56.6

Extruded semi-conducting thermosetting


4 Insulation screen 1.0 58.6
compound

5 Water blocking Semi-conducting water blocking tape 1.5 64.1

6 Metallic sheath Corrugated aluminium sheath 2.0 77.0

7 Anti-corrosive layer Bitumen / 77.0

8 Outer layer PE(Black) coated with graphite 4.0 85.0

9 Outer conductive layer Graphite / 85.0

Unit:mm

Page 3 of 5
Add:No.8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

5 Technical Particulars

No. Description unit Parameters

Mechanical Performance:

1 Min. bending radius during installation mm 1700

2 Min. bending radius installed mm 1275

3 Max. allowable pulling tension of conductor kN 44.1

4 Total weight of completed cable (Approx) kg/m 10.3

Electrical Performance:

1 Rated voltage of cable kV 66

2 Impulse lightning voltage of cable kV 325

3 Maximum DC resistance of conductor at 20℃ Ohm/km 0.0283

4 Maximum AC resistance of conductor at 90℃ Ohm/km 0.0385

5 Conductor to screen capacitance μF/km 0.252

6 Nominal electrical stress at conductor screen kV/mm 4.0

7 Nominal electrical stress at insulation screen kV/mm 2.3

8 Charge current A/km 2.8

9 Inductance per unit length mH/km 0.398

10 Screen short circuit capacity for 1s kA 39.5

11 Conductor short circuit capacity for 1s kA 90.1


Continuous current rating of flat formation,buried at depth of 1500mm with thermal
12
resistivity of 1.5degC.m/w and soil temperature of 25℃,axial distance 400mm

12.1 In air (30℃) A 1515

12.2 In soil A 805

12.3 In duct(Polyethylene duct buried) A 768

Page 4 of 5
Add:No.8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

6 Packing

The cable is wound on the non-returnable steel drum. Both ends of cable are securely
fastened to drum and reliable sealed. The required marking is printed with a weather-proof
material on the outsides of drum according to customer’s requirement. Packing with
fumigated wood battens and using steel strip to fix. For different length of cable, we provide
different packing methods. The transportation drum drawing is described as below.

a.Draft drum drawing b. Packing drawing