Configurable parameters:
bb Automatic transfer system ON/OFF
Paralleling upon Auto return
bb Operating mode: Semi-Auto, Auto SW1, Auto SW2, A software-configurable option allows the automatic transfer system to disable
SW1 –> SW2, SW2 –> SW1 or enable paralleling of the channels upon automatic return to the main channel
bb T1: 0 ms to 2 min. in increments of 100 ms (in "Auto" mode).
bb T2: 0 s to 30 min. in increments of 5 s
bb Disabling/enabling transfer upon fault detection: Enabling of paralleling must be confirmed by the activation of a dedicated digital input.
bb Choice of voltage presence detection: DI4 or VD23 Paralleling disabled: Auto return to the priority channel involves opening the backup
bb Channel connected to generator: SW1 or SW2 channel and, when it is open, closing the priority channel.
bb Type of automatic transfer system: Network ATS
or Generator ATS Paralleling enabled: Auto return to the priority channel involves first closing
bb Manual control enabled/disabled if ATS in operation the priority channel and, when it is closed, opening the backup channel.
bb Paralleling enabled/disabled in auto and/or manual mode
bb Choice of type of changeover to Generator: immediately
or after detection of Generator power on
Changeover conditions
Changeover takes place if the following conditions are met:
•• Automatic transfer system in operation
•• SW1 open and SW2 closed or SW1 closed and SW2 open
DE59175
DI 1 1
2 •• Absence of fault current on the two channels (only if locking by fault detection
DI 2 3 option activated)
4 •• "Transfer locking" absent
Priority channel DI 3 5 •• "Earthing switch" absent on the two channels
6
•• MV voltage absent on the active channel
Genset voltage presence DI 4 7
•• MV voltage present on the other channel.
8
Parallel connection input DI 5 9 Return to the main channel for the "Auto" modes occurs if:
10 •• The priority channel is open
Genset forcing DI 6 11 •• The MV voltage on the priority channel is present during time delay T2.
12
The DIs can be assigned Digital Input connection Generating set connections
for ATS automation ("J2" or "J10" terminal block) Relays are installed in factory in the T200 enclosure to provide interfacing with
(configurable options)
the generating set (Generator ATS version only). Connection should be performed
as follows (see diagram opposite):
•• Voltage: contact closed if Generator started, to be wired on the two available
DE56806