You are on page 1of 1

X

65
+8
00
X

X
X
X

THIS SITE
X

65+900
X

PT: 65+8
99.72 KEY PLAN
FOR CONTINUATION SEE DWG # NAS-2-XX16-WW030-0001-SD-01-15

NOTES:
X

1. MINIMUM COVER OVER PIPE SHOULD BE NOT LESS THAN 1.00 M. PIPES HAVING COVER
LESS THAN 1.0 SHALL BE ENCASED IN PLAN CONCRETE.
1.03
779 2. A HORIZONTAL SEPARATION OF 2.00 METERS AND A VERTICAL SEPARATION OF 0.50 METER
E 52 608.62
X

80 SHALL BE MAINTAINED BETWEEN POTABLE WATER AND SEWER LINES WITH THE SEWER
N 28 LINE BELOW THE WATER LINE. A HORIZONTAL SEPARATION OF 3.00 METERS SHALL BE
X MAINTAINED WHERE A MINIMUM OF 0.50 METER VERTICAL SEPARATION CANNOT BE
X
ACHIEVED. AT CROSS OVERS, WHERE THE VERTICAL SEPARATION CANNOT BE
X

MAINTAINED, THE SEWER LINE SHALL BE ENCASED IN CONCRETE FOR A MINIMUM LENGTH

FOR CONTINUATION SEE BELOW LEFT


OF 3.00 METERS ON EACH SIDE OF THE WATER LINE.
0+100 0+120
A-01 0+140 0+160 0+180 0+200 3. FOR GRAVITY PIPE LESS THAN OR EQUAL TO 600MM DIAMETER, VITRIFIED CLAY PIPE (VC)
2+350 0+220 0+240 0+260 0+280 0+300 SHALL BE USED CONFORMING TO SASO 236/235-1995. FOR PIPES GREATER THAN 600MM
2+375 0+320 0+340 0+360 0+380 0+400 0+420
0+0802+395 0+440 0+460 DIAMETER GLASS REINFORCED PLASTIC (GRP) PIPES SHALL BE USED CONFORMING TO
mm

0+480 0+500 0+520


2+350 0+540 0+560 0+580 0+600 SN-10,0. FOR FORCEMAIN DUCTILE IRON (DI) PIPES SHALL BE USED CONFORMING TO ISO
2+375 0+025 0+050 0+620 0+640 0+660
AIN Ø150

0+075 0+680
65+996

0+100 0+125 0+700 0+720 0+740 2531.


0+150 0+175 0+200 0+760 0+780 0+800 0+820
0+225 0+250 0+275 0+300 FORCEMAIN Ø150mm 0+840 0+860 0+880 0+900 0+920
EP: 65+9
2+575 0+325 0+350 0+375 0+940 0+960 0+980 1+000 4. THE LOCATION OF THE SEWER LINES AND MANHOLE CHAMBERS SHALL GENERALLY BE AS
96.08 0+400 0+425 0+450
2+5 0+475 0+500 0+525 INDICATED ON THE DRAWINGS, HOWEVER, THE EXACT LOCATION ON SITE SHALL BE
0+060 0+550 0+575 FORCEMAIN Ø150mm
FORCEM

5 2 0+600 0+625 0+650 0+675 MODIFIED AS NECESSARY TO SUIT THE EXISTING CONDITION AS APPROVED BY THE
2+600 0+700 0+725 0+750 ENGINEER.
2+350
2+5 2+550 WO-01
E 527693.60 0+775 0+800 0+825 0+850 0+875
2+375
00
N 2881225.62 0+900
2+400 2+475
LEGEND:
0+000

0+040 ARV-012+425 2+450


A-01B A-01
INTERFACE POINT WITH OTHER CONTRACTS
8.40
783
E 52 610.77 PROPOSED SEWER LINE
9.34 N 28
80
A-01
787
E 52 612.62
80 0+020 MH PROPOSED SANITARY SEWER MANHOLE
N 28 E 52
7700
DIRECTION OF FLOW IN PIPE
X
X STUBOUT FOR FUTURE CONNECTION
0+000

.342 PROPOSED FORCEMAIN LINE


7879
E 52 612.625
80
N 28 AIR RELEASE VALVE
X

BOX / PIPE CULVERT


ION
ECT ACT
ONN
X

R
CE C E CONT
RFA WASHOUT
INTE R PHAS
O T HE
WITH
X

ABBREVIATIONS:
X

Refer to the attached MH MANHOLE


L-MG1-04

Ø PIPE DIAMETER IN mm
X

LS LIFT STATION

Comment's Sheet IL
IC
INVERT LEVEL
INSPECTION CHAMBER
X

WO WASHOUT
ARV AIR RELEASE VALVE
X

REFERENCE DRAWINGS:
Supervision and Management Services for King Faisal Air Academy
Facilities Relocation and Construction Project, Majmaah DRAWING NO. DRAWING TITLE
X

1422-04-WW-000 SEWAGE COLLECTION SYSTEM OVERALL LAYOUT PLAN


DOCUMENT / DESIGN REVIEW 1422-04-WW-001 TO 047 SEWAGE COLLECTION SYSTEM LAYOUT PLAN (SHEET 1 TO 25)
☐ A - Approved - Construction / Fabrication / installation may be undertaken.
☐ B - Approved as noted - Approval does not authorize changes in contract sum or contract time.

☐ C - Revise and Resubmit - Construction / Fabrication / installation may not be undertaken.


☐ D - Rejected - In resubmitting, limit corrections to the items marked.
- Dar Al Riyadh approval of submitted item is not required or the submittal is
☐ E - Not reviewed not complying with contact requirements
☐ Architecture ☐ Interior Design ☐ Civil ☐ Electrical ☐ Survey
Squad Checking:
N

☐ Mechanical ☐ Structural ☐ Telecom ☐ Landscape


28

Reviewed By : NM/OK Date: 22 November 2020


81
50

Disclaimer:
0

1. Review and approval are for conformance with the information given and the design concept of the Project as
expressed in the Contract Documents.
2. Dar Al Riyadh review and approval of the Contractor’s submittals shall not relieve the Contractor from any
obligation contained in the Contract Documents.
3. No responsibility is assumed for accuracy or completeness of submittal dimensions, quantities or details.
4. The Contractor is responsible to field verify all dimensions prior to fabrication, Construction or installation.
5. Coordinate with all adjacent and/or related contractors, disciplines, other equipment and materials.
0 05.11.2020 SUBMITTAL FOR APPROVAL
ROAD A-03 START
6. Respond to and address all previous comments from Dar Al Riyadh.
STA. 2+390.115 7. Comply with the requirements of all required approving authorities and obtain timely approval/consent as
REV DATE DESCRIPTION
FOR CONTINUATION SEE ABOVE RIGHT

N 2881563.708 necessary.
N

E 527578.882 CLIENT:
28
81
60

MINISTRY OF DEFENCE
0

0+8
80
0+9
ROYAL SAUDI AIR FORCES
00
0+9
0+8 20
00 SUPERVISION:
2+400

FOR CONTINUATION SEE DWG # NAS-2-XX16-WW030-0001-SD-03-15


0+9 E 527647.35
40
0+8
25 0+9 N 2881518.50 1+080 ENGINEERING AND WORKS
60 1+100
0+8
50 0+9
1+060 DEPARTMENT
80 1+120
0+8
ENGINEERING AFFAIRS
75 1+0 1+040
2+425

00 m
1+020 50m PROJECT:
0+9 Ø1 1+140
00 M AIN E 527595.41
CE KING FAISAL AIR ACADEMY
0+9 F OR N 2881665.27
25 IN MAJMA'A
RA # 04 1+160
2+450

0+9 1+180
50 1+200 1+220 1+240 1+260 1+280 1+300 1+320 1+340 1+360 1+380 1+400 1+420 1+440 1+460 1+480 1+500 1+520 1+540 1+560 1+580 1+600 1+620 1+640 1+660 1+680 1+700 1+720 1+740 1+760 1+780 1+800 1+820 1+840 1+860
E PMC:
52
77 0+9
75 Dar Al-Riyadh Consultants
N

00
FORCEMAIN Ø150mm ARV02 FORCEMAIN Ø150mm P.O. Box 250170, Riyadh 11391-Saudi Arabia
28

1+025 1+050 1+100 1+125 1+150 1+175 1+200 1+225 1+250 1+275 1+300 1+325 1+350 1+375 1+400 1+425 1+450 1+475 1+500 1+525 1+550 1+575 1+600 1+625 1+650 1+675 1+700 1+725 1+750 1+775 Tel.: (+966-11) 206 00 88
81

1+075 E 527326.43
80

www.daralriyadh.com
1+0
0

00 N 2882131.16
CONTRACTOR(S):
JV NAS
P.O. Box 4339, Riyadh 11491-Saudi Arabia
0+

Tel.: (+966-11) 408 51 00


02

A-01 A-01 Fax: (+966-11) 405 78 28


5

CONTRACTOR'S CONSULTANT:
ENTRANCE GATE
STEEL FENCE (TYP.)

GRAVEL AREA

FLOW METER

WATER INLET
0+

PIPE CHAMBER
STEEL FENCE (TYP.)

PAVED AREA
50 0

STEEL FENCE (TYP.)

WATER TANK

M.C.C.

PAVED AREA

CONTROL

GRAVEL AREA

STEEL FENCE (TYP.)


Facility Name:
0+

PHASE - II
07
5

TANK & PUMPING STATION-01 (UT34)


PROPOSED IRRIGATION WATER

E
52
76
PRIMARY INFRASTRUCTURE
00

ROAD A-06 END


STA. 0+083.395‬ Drawing Title:
N 2881602.891
E 527735.895 SEWAGE COLLECTION SYSTEM
LAYOUT PLAN
(SHEET 2 OF 15)
Scale: Date:
1 : 1000 05.11.2020
Prepared: Checked: Checked: Approved:
E S.V A.T S.N.S M.H
52
7 70
0

Sheet No. Rev.

NAS-2-XX16-WW030-0001-SD-02-15 00