You are on page 1of 2

2.

Manual Set Constant (Signal Generator) Applications

2. Manual Set Constant


(Signal Generator)
The output of the manual set constant is an analog signal developed within the function that is equal to <S1>. This function
provides a tunable output value in engineering units.

Outputs

(2 )
A N
Blk Type Description

N R User selected constant

Specifications

Spec Tune Default Type Range Description

S1 Y 0.000 R Full Output value in engineering units

2.1 Applications
Scaler

Figure 2-1 illustrates how to use the manual set constant as a scaler. In the example, the transmitter has a range of 200 to
700 pounds per square inch. The range is scaled up 200 pounds per square inch by setting the manual set constant to 200.
The summer adds <S1> and <S2> to provide an output range of 400 to 900 pounds per square inch.

PT
2 0 0 -7 0 0
p si

S1 O U T PU T = S 1 + S 2
A
(2 ) S2  (K ) (1 5 )
N
OR
N 4 0 0 -9 0 0 p si

S 3 = 1 (G AIN O F S 1 )
S 1 = 200 S 4 = 1 (G AIN O F S 2 )
T 01 5 82 A

Figure 2-1 Scaler Configuration

Set Point

Figure 2-1 illustrates how to use the manual set constant for a set point configuration. The transmitter range is ten to 20
inches of water. The desired set point (output of the summer block) is 15 inches of water. By setting the manual set constant
to 15, the summer subtracts <S2> from <S1>. Thus, when <S1> equals 15 inches of water, output N of the summer block
equals zero inches of water which shows the level has reached set point.

FT
1 0 -2 0
in.H O2

S1 OUTPUT = S1 - S2

A
(2 ) S2  (K) (1 5 )
N
OR
0 WHEN SET POINT
N IS REACHED
S 3 = 1 (G AIN O F S 1 )
S 1 = 15 S 4 = 1 (G AIN O F S 2 )
T 01 5 83 A

Figure 2-1 Set Point Configuration

2VAA000844R0001 Vol. 1 Rev. D 2-1


Applications 2. Manual Set Constant (Signal Generator)

2-2 2VAA000844R0001 Vol. 1 Rev. D

You might also like