Professional Documents
Culture Documents
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Special Process Procedure Elements (Typical for "REVIEW PROCEDURE" type Special Process SAICs, See Notes)
A
Sch Q,
Procedure is project specific, identifiable by Budget Item (BI) or Job
A1
Number, Contract Number & Project title & traceable to Quality Plan.
Para 3.1, 3.2
Sch Q,
An attachment section exists listing applicable QC forms & records.
A3
(ISO 9001:2008, Para. 4.2.4a)
Para 3.1, 3.2
Sch Q,
Other sections for special process control procedures (per Sch Q) detail
A4
references, responsibilities, definitions & procedure reqmts.
Para 3.1, 3.2
Page 1 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
General Requirements
B Note 1: Use SAIC-A-2003 for specific Test package responsibilities & instructions
Note 2: Use SAIC-A-2009 for specific Testing Equipment requirements including Safety Inspections
Page 2 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Page 3 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
On-Plot Piping Pressure Testing (Includes all Utilities, Firewater & Plbg References, SAIC-S-Checklists & SATRs)
D
SAES-L-150,
Lube and seal oil piping is strength tested in its own fluid at the greater
D5 Section 7
of 1.5 times design pressure or 100 psig (for 30 minutes).
Para 7.5.1
Page 4 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
B) Between root isolation valve & instrument isolation using treated water
(or approved fluid) at 1.25 times system design pressure.
SAES-L-150,
D9 C) The test
Para 5.12
duration is not less than 30 minutes.
D) Instrumentation subject to damage from testing is disconnected.
E) When liquid is used in lieu of air, lines are
blown dry after test. See Attachment 2
for related Flushing/Cleaning Methods
Page 5 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Page 6 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
E Service Test, Leak Test, Minor Repair & Other Applications (Include & detail Service Test limitations per scope)
In New Plants, Low pressure steel piping in water, instrument air, plant air,
inert gas (Nitrogen, etc.) & steam systems operating at 150 psig or SAES-L-150,
E1
lower are Service Tested (except FW systems). Section 9.3
Vessel Trim & Sampling lines also receive a Service test.
Service Test socket welded piping on Tie-in work & repairs (in
Existing Facilities) if Operations Engineering Unit determines hydrostatic
test is impractical & the following requirements are met:
SAES-L-150,
E3 A) A request of NDT in lieu of pressure testing is processed.
Section 9.2
B) Qualified welders and welding procedures are used.
C) Weld gap is verified & welding is witnessed by Operations Insp.
D) Welds are MT or PT tested (Operations Inspection choice).
Procedure* & Design Package* for Hot Taps & Stoppling Connection
Use
F1 Install. Note: *
SAIC-L-2090
Use latest Edition SAEP-311 (Safety).
Page 7 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Use SAIC-
F2 Hot Tap/Stopple & Reinforcement Calculation Request-Form 7627
L-2091
G Cleaning, Flushing, Water Treatment & Lay-up (Include applicable requirements into the procedure)
The general flushing medium is plant/ process water or raw water. Fire
water may be used where process water is not available. Sea water is not
acceptable. Water for hydrostatic test with pH less than 6 and/or SRB SAES-A-007
G2
counts greater than 10² per ml is unacceptable. Treat test fluid to control Section 4
corrosion and bacteria when applicable.
Employ regular water analysis, maintain certs and records.
Test Procedure details Lay-up & treatment of Hydrostatic Test Water for
Carbon & Low Alloy Steel systems as follows:
A) Follow 14-day rule with oxygen scavenger & 90-day rule with biocide
use in pipelines, use batching scrapers & nitrogen slug to separate air
from contacting treated water SAES-A-007 Para
G3
B) Lay-up per 60-day rule (14 days on exchangers) 5.2
• Wet, Dry, Inert Gas & Ambient Methods are detailed in procedure
• Boiler Layup is per SAEP-1026, Other methods are CSD approved
Test Procedure details Lay-up & treatment of Hydrostatic Test Water for
Stainless (300, 400 series) systems as follows:
A) Chloride content of test water is tested/certified below 50 mg/L.
B) Treat test water with oxygen scavenger (4-day contact rule) SAES-A-007
G4
C Treat test water with biocide (14-day contact rule) and lay- Section 6
up
• Wet, Dry, Inert Gas & Ambient (40% humidity limit) Methods
Procedure can utilize SAES-A-007, Section 6 in entirety
Page 8 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Test manifolds are certified & tested to 1.2 times maximum test pressure
but not less than discharge pressure of test pump.
SAES-A-004 Para
H2 Manifold Test Report (Sketch & Certificate) is required. The sketch
5.5.4
lists detailed information/ratings of all components. Manifolds
receive unique numbers and records are kept.
Procedure details isolation of test sections (checklist items):
A) Paddle blinds or spectacle
blinds isolate test sections.
B) Blind flanges, pipe plugs and caps isolate test sections SAES-A-004,
H3
C) Block valve Para 8.3
isolation is severely restricted & supported by calcs.
Fabricated test implements are rated, marked & inspected
During the application of the test pressure, all in-line valves if not used as
test isolation valves are verified to be in an open position. SAES-A-004,
H4
Inspectors check valve lineup & position prior Para. 9.1.3
to testing.
Block valve use for isolation during hydrotest (testing against the seat of a
closed gate, ball or plug valve) is limited & supported with Engineering
calculations (limiting factor considerations) as follows:
A) Test pressures never exceed seat closure test
pressures per API 598 (Example: 150# gate valve seat closure test is at
SAES-A-004,
314 psi)
Para 8.3 &
B) Valves do not leakby (Successfully passed a seat
H5
closure test) C) Both sides
Attachment 2
of isolation valve have relief valves during test.
D) Test pressure is never
reduced below 1.5 x system design pressure per SAES-L-150, Section 7
(ASME B31.3, Para. 345.4.2)
Ensure testing against valve seats causes no damage.
Page 9 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
All joints (threaded, welded & flanged) are exposed for visual leak
SAES-L-150,
H11 detection during the strength test. External coating/priming of such joints
Section 7.3
is not allowed unless approved by ID Manager & Proponent
Test duration and hold times consider full inspection access via
scaffolding & manlifts as necessary to allow visual inspection of 100% of
all joints including weep holes, 6mm drain holes in dummy legs (required). SAES-L-150,
H12
Inspection time may exceed test times listed in SIS sheets & Hydrotest Para. 7.2
reports (30 minute is a minimum).
Inspectors shall complete inspection before tests are ended.
Page 10 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Temporary supports & other support considerations for above ground
piping installations during hydrotest are as follows:
A) Where required to
prevent damage to system
SAES-L-150,
H13 B) As highlighted in the approved hydrotesting
Section 6
procedure. C) Expansion joints and
spring hangers or spring supports are to be provided with temporary
restraints where needed to prevent excessive travel or deformation under
test loads.
Disposal sites for the test fluid shall be reviewed and approved prior to the
hydrostatic test in accordance with SAEP-327 "Disposal of Wastewater
SAES-L-150,
H15 from Cleaning, Flushing, and Hydrostatic Tests".
Section 11
Test
water reuse is restricted to ensure cleanliness & quality
Page 11 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
REMARKS:
Pressure Test Procedure (SAES-A-004 Definition): Information assembled to ensure all requirements listed in GI-0002.102 , all referenced
SA & Industrial standards are met. Per SAES-A-004 Definition, test packages are part of the Pressure Test Procedure. This checklist provides
Note a complete detailing of all Pressure Testing Applications/Requirements for SA Projects. See Attachment 1.
Hydrotest, Pneumatic and Soap Bubble Leak Test*, Service Test, & Valve Testing, can be
1 one (1) procedure (Pressure Testing). Small projects (less than 500 welds) do not require a Database for tracking welds & test packages per
SAEP-1160 requirements. *Note: Soap Bubble Leak Test procedure (See SAIC-A-2005) shall meet ASME SEC V Article 10
& Appendix requirements.
Pressure Test Plan is submitted for Company review & contains the following 4 elements necessary to control the work:
1. Pressure Test Procedure (Including Test Package Controls)
Note 2. Sample Hydrotest Package Per SAIC-
2003 3. Hydrotest Data Mgmt & Tracking Database per
2 SAEP-1160 Small projects (less than 500 welds)
do not require a Database for tracking welds & test packages per SAEP-1160 requirements.
4. Pressure Testing Specification (Plant Piping System Line Class List modified for Pressure test design)
Note Pressure Testing Specification shows all systems, design factors and proposed system testing details including lay-up and includes all Plant
Piping Line classes including those for Utilities, Firewater System and Plumbing, to guide pressure test design and test package development.
3 Submit early on major projects as Pressure Testing is almost always Critical Path on Projects.
Note Section A relates to Procedure "Structure" & Sch Q specific Quality Goals such as: 1) Continuing Process Improvement (CPI) & adoption of
Best Practices 2) Meeting SA Standards 3) Ultimate Customer Satisfaction 4) Cost Savings through Quality. This section is not
4 repeated in other "Review Procedure" type special process checklists, yet is intended for all.
Page 12 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
ATTACHMENTS: Attachment 1 - Pressure Testing Matrix for SA Projects
Attachment 2 - Pressure Testing Inspection Guide
Page 13 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
REFERENCE DOCUMENTS:
1. Contract Schedule Q - Quality Assurance and Control, Inspection and Testing (Project Specific)
2. SA General Instruction Manual GI-002.102 (28 October 2008) Pressure Testing Safely
3. SAEP-1160 (10 July 2011) Tracking & Reporting of Welding, NDT & Pressure Testing for Capital Projects
4. SAES-A-004 (30 Jan 2011) General Requirements for Pressure Testing
5. SAES-A-007 (24 July 2011) Hydrostatic Testing Fluids and Lay-Up Procedures
6. SAES-L-108 (11 Oct 2010) Selection of Valves
7. SAES-L-150 (25 April 2010) Pressure Testing of Plant Piping and Pipelines
8. SAES-L-310 (29 April 2007) Design of Plant Piping
9. SAES-L-350 (22 April 2009) Construction of Plant Piping
10. SAES-S-010 (21 November 2009) Sanitary Sewers
11. SAES-S-020 (13 March 2011) Industrial Drainage and Sewers
12. SAES-S-030 (16 March 2011) Storm Water Drainage Systems
13. SAES-S-040 (10 March 2012) Saudi Aramco Water Systems
14. SAES-S-050 (5 Feb 2006) Sprinkler and Standpipe Systems in Buildings
15. SAES-S-060 (28 January 2004) Saudi Aramco Plumbing Code
16. SAES-S-070 (13 Novemebr 2007) Installation of Utility Piping Systems
17. SAEP-311 (13 September 2009) Installation of Hot Tapped and Stopple Connections (Use Latest Edition for Safety)
Page 14 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05(Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
Attachment 1 - Pressure Testing Matrix for On-Plot Piping (Incl. UG Utilities, FW & Plumbing)
ON-PLOT NEW B31.1 & B31.3 CODE PRESSURE PIPING (SATIP-A-004 Series)
SYSTEM TEST PRESS TEST CONSIDERATIONS & NOTES
&
Process DURATION
As Calculated* Piping Line Class List (Hydrotest Spec) lists all new process piping line classes (strength test
30 mins (min) required per code) with exceptions for Service Test and other tests as noted below. NDE in lieu of
Piping pressure test may be performed if requested & approved by SA Insp. Dept. Mgr. Process requests
per Sect 5 of SAES-A-004, and at a minimum, 30 days ahead of testing.
*Note: Unless limited by flanges, valves or other component (exceptions below), hydrostatic strength test pressures for every section of new
constructed line shall produce a hoop stress in pipe of 90% SMYS at test temperature. See Exceptions Below.
Lube & Seal Oil See Notes *Lube & seal oil piping is pressure tested with its own fluid at 1.5 times design pressure or 100 psig,
30 mins (min) whichever is greater. Chemical cleaning precedes pressure testing. Joints shall be completely cleaned*
Systems (oil free) before testing. *Baby Powder works best to clean/dry joints
Note: Leaks are common, difficult to identify as "active" or "non-active". Perform preliminary tests to identify all leaks, especially at flanged and
threaded joints. When evaluating leakage, utilize clean dry cloths to identify "active" leaks for repair. Oil residue found after wiping the joints (check low
points carefully) is cause for clean and retest. Always wait a minimum of 30 mins after wiping joints before reevaluation.
Underground As Calculated A) Test prior to backfilling (all joints exposed) & maintain test pressure for a minimum 2 hrs. B) Per
A) Process See Notes SAES-S-070, Section 18, Underground Utilities are tested for a minimum of 4 hours. If
Piping justifiable (safety, back-filled line) a 24 hr recorded test (Chart Recorder) is reqd.
B) Utility Piping
Flare Lines See Notes Flare lines 24-inch NPS & larger with a design pressure of 75 psig or lower may be strength tested
30 mins pneumatically (75 psig is tested at 1.1 factor or 82 psig) per Para. 345.5 of ASME B31.3
(24" & (min)
above)
Note: Test limits shall be downstream of isolation valves (beyond PZVs & locked valves for equipment). Portions of the test may be less than 24 inches
from these valves to the flare header branch connection. Flare system Isolation Valves receive a pneumatic seat test at 5 psig in lieu of a high pressure
seat hydrotest. Conduct this test on a weekend to minimize personnel exposure. Perform a stored energy calc when requested by Company. Test limits
utilize blind flanges at removed isolation valve locations. Follow Pneumatic Testing SATIP.
Vacuum Piping See Notes Tested to 1.5 times the differential external pressure, but not less than 15 psig.
30 mins
(min)
Air & Inert Gas SERVICE TEST & Perform a preliminary soap bubble test at 5-10 psig after construction is complete & threaded joints are
(150 psig Soap Bubble Test checked for engagement (two full visible thread rule). Coordinate with Compressor and Receiver
max) 30 mins Service tests and final gasket installation.
(min)
LP Steam SERVICE TEST Coordinate with system Service tests and construction completion.
(60 psig max) 30 mins (min)
Weld-Plus-Ends Soap Bubble Leak Weld-Plus-Ends shall be subjected to a pneumatic pressure test of 5 to 10 psig in the annulus between
(SAIC-A- Test at 5-10 psig the gasket and the seal weld. It shall be examined for leaks using a soap solution.
2016)
Existing Plant As Calculated* For revalidation purposes of existing plant piping, the test pressure shall be minimum required by the
Piping 30 mins (min) Code ASME B31.3. The actual wall thickness of the piping and flange rating shall be determined and
Incl. Tie-Ins taken into consideration when calculating the test pressure. In case of flanged tie-in connections, a
flange tester is utilized to conduct hydrostatic testing of flange butt weld.
RETESTING See Notes Systems that already passed a successful pressure test require RETEST IF subjected to new welding
REQMTS activities (Modifications, repair to pressure boundary) OR IF PWHT is reqd*.
Note: Seal welds of threaded connections & Attachment welds of non-pressure containing parts, such as wear pads DO NOT REQUIRE RETEST
UNLESS THE LINE REQUIRES PWHT (Including attachment welds & seal welds to the pressure boundary).
REPAIR EXISTING See Notes Every existing plant piping & pipeline, after repairs or alterations have been made that affect the
integrity of the pressure containing parts, shall successfully pass a hydrostatic test. The test pressure
PIPING shall be in accordance with the requirements of the applicable code.
Note: SAEP-310 requirements apply as well for pressure testing after Repairs, Upgrades, Refurbishment, etc
Open-Ended EXEMPT, Drains, vents & piping downstream of pressure relieving devices that discharge directly to the
Piping VISUAL EXAM atmosphere (max internal pressure 10 psig) are EXEMPT from testing. Drain holes installed, etc
Note: Test Package SIS Sheet shows design data & "EXEMPT" under required test pressure. Line(s) shall be visually examined.
Instrument Impulse As Calculated* Whether piping or tubing, between the root isolation valve and the instrument isolation shall be
Lines 30 mins (min) pneumatically pressure tested (air or nitrogen) at 1.25 X design pressure of the piping system or
process equipment to which it is connected. Test duration shall not be less than 30 minutes.
Note: Instrumentation that could be damaged due to the test shall be disconnected. When pneumatic test is not practical (pressure greater than 1000
psig, physical configuration, etc.) test with liquid or water. (Flush, test & dry clean using a quality of water not harmful to lines).
Page 15 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05(Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
Internally FBE As Calculated* For internally Fusion Bonded Epoxy (FBE) coated piping system, the test pressure shall not exceed
Coated Lines 30 mins (min) 5,000 psi for APCS 100, 101, 103 systems & 3,000 psi for APCS 102 System
Note: ALL Welding shall be completed (Design Issue), all internal coating and Holiday Testing PRIOR TO pressure testing.
Sampling Lines See Note Test as an integral part with the piping or equipment to which it is connected.
Vessel & Tank See Note Test separately (separate package) as required. Exemptions include sight glasses &
Trim (Piping) other instruments. Strength or Service test associated piping based on service
Note: ALL Code Piping construction (in-situ) that is not VENDOR supplied shall be tested. Utility = Service Test, Process = Strength Test
Skid-Mounted EXEMPT IF TESTED BY VENDOR 1. When testing with adjacent Lube oil system piping (no leaks = acceptance).
Piping (Vendor) per 01-SAMSS-010 2. When code repairs are made to skid-mounted piping to correct misalignment,
(exceptions noted) physical damage or any modifications in-situ, pressure test the affected spools.
FIELD HYDROTESTING OF NEW VALVES (SAES-L-108, Section 4.7 & SATIP-L-108 & SAIC-L-2042)
Test Location See Note Location shall be specified by proponent & PID approved. SAIC-A-2031 Sect. J
Field Testing of See Note All new valves designated for isolation service (as specified by the Proponent) shall be
subjected to high pressure hydrostatic seat test prior to installation in line.
New Valves
Exception See Note Low pressure pneumatic seat test at 5 psig shall be substituted for high pressure
hydrostatic seat test for flare system valves. Identify & Segregate Early!!!
Exemption See Note Buttweld & socketweld end valves in NPS 2 inches and smaller are exempt
Procedure See Note Test procedures, pressures, durations, & leakage acceptance criteria shall be equal to
those that the valves were originally purchased to. All resilient (soft) seated isolation
(Checklist
Item D4)
valves shall have zero leakage. See SAIC-L-2042
Note: Proponent specifies those Line Classes and valves subject to field hydrotesting. Valves received shall be carefully identified & given a unique ID
number for installation into the correct Line Class based on visual verification of construction stamp. Valves shall be given a unique ID & corresponding
test report document upon receipt, Valve ID shall be controlled, documents transferred into appropriate Test Pkg & Database (Piping System, Line
Class, Line Number, Location) per SAEP-1160. Procedure identifies all critical aspects of Valve Testing incl Receipt Inspection (internal visual exam by
qualified Inspector), pressure test, ambient lay-up (corrosion protection per mfg instructions & follow-up preservation reqmts) & segregation control to
prevent "mixing valves". Controlled System for Valve Placement exists.
6.9 Utility Piping Systems - Utility systems, including irrigation piping & water distribution mains, shall be tested per SAES-S-070, Sect 18
6.10 Industrial Drainage and Sewers - Industrial drainage and sewers shall be tested per SAES-S-020 (SAES-070, Section 18).
6.11 Sanitary Sewers - Sanitary sewer systems within buildings shall be tested per reqmts of the Uniform Plumbing Code (UPC). Exceptions to
UPC requirements are listed in SAES-S-060. THERE ARE 3 MAJOR EXCEPTIONS FOR INSPECTION AWARENESS
Sanitary sewer lines outside of buildings shall be tested in accordance with SAES-S-070 Section 18.
6.12 Storm Water Drainage Systems - Test per SAES-S-030 (SAES-S-070, Section 18) Note: Only OWS portions are tested.
Page 16 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05(Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
6.13 Miscellaneous Building Services Piping - Steam & condensate piping outside the jurisdiction of ASME B31.3, heating & cooling water piping,
vacuum & compressed air system piping for building services shall be tested per ASME B31.9, Building Services Piping.
6.14 Gas Cylinders - Gas cylinders shall be tested per Saudi Aramco Bottled Gas Manual. (Application - New Labs, etc)
6.15 Valves - Valves shall be tested in accordance with SAES-L-108, Section 4.7
6.16 Non Metallic Piping - Such as RTR, Thermoplastic, PVC/UPVC & CPVC shall be tested per SAES-S-070, Section 18.
Page 17 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05(Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
Attachment 2 - Saudi Aramco Pressure Testing Inspection Guide For Procedures
SAES-L-150 Pressure Testing Definitions
Hydrostatic Test: A pressure test conducted using water or other approved liquid as the test medium.
Leak Test: A pressure test to ensure tightness of flanged and threaded joints at the test pressure. It
is normally conducted before initial start-up & after T&Is. A leak test is different from tightness test below.
Pneumatic Test: A pressure test conducted using air or other approved gas as the test medium or in conjunction with
liquid.
Revalidation Test: A pressure test performed to prove the integrity of existing pipelines or plant piping.
Service Test: A pressure test performed to prove the integrity of pipelines or plant piping using the service fluid at the
maximum attainable operating pressure.
Strength Test: A pressure test at an internal pressure determined in accordance with this standard and the applicable
Code* to verify the integrity of the piping systems for service at the design pressure.
Tightness Test: Pressure test to ensure piping system tightness (i.e., no system leaks) at test pressure.
*Strength test (ASME B31.8 code term) is same as a hydrostatic leak test (B31.3) or proof test (B31.4)
Water Flushing: Equipment sensitive to damage during water flushing shall be removed, blocked off or isolated. A list
shall be prepared and be part of the flushing procedure. Ball valves shall be flushed in fully open position. All piping
systems shall be flushed using high pressure [60.8 mPa (8.8 ksi) minimum] jet such as rotating hose or rotating nozzle.
Below 4", use High Velocity Water Flushing (HVWF). On systems where high pressure jet flushing cannot be used due
to complicated shapes and/or long runs use HVWF or slug flushing. Water velocity shall be a minimum of 3 m/s.
General flushing medium shall be plant/process/raw water. Fire water is used where process water is not available. Sea
water is not acceptable. When flushing stainless steel lines, chloride ion content shall be less than 50 mg/L. After
flushing, piping systems shall be completely drained, dried to a dew point below -1°C and protected against corrosion.
Valve Cavities (low points) without drains shall be addressed in the procedure.
Mechanical Scrapers: Can be used under the condition that damage to the pipe interior surface shall not occur.
Page 18 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05(Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
Valve Considerations: Valve Cavities (low points) without drains shall be addressed in the test procedure.
Whenever any valve without a low point drain is tested in-line, steps shall be taken to assure:
1) Complete draining of low points including the valve cavity after testing.
2) Complete removal of debris deposited during flushing and filling. Demonstrate effectiveness of
flushing to prevent debris accumulation in low points. Reinspection after cleaning and examination of seating surfaces &
performance of manufacturer recommended preservation or corrosion control measures is one acceptable method.
Contact CSD. 3) Corrosion Protection measures
shall be per SAES-A-007. Ambient lay-up of 400* Series (13Cr) trim valves, (Trim 1, 4, 6, 7, 8 & 8A) is prohibited
without CSD approved corrosion prevention measures.
TEST WITH ISOLATION AGAINST VALVE SEATS (CALCS) PER SAES-A-004, SECTION 7.3
Example 1: A typical Carbon Steel Class 150 # system (Proposed for hydrotest at 450 psi, limiting factor = flange)
1. A test proposes isolatation against a closed valve (gate, ball or plug type). Valve has passed a body & seat test.
2. Calculations are made to determine if a test against the valve seat is allowable per SAES-A-004, Section 7.3
• A 150 # steel gate valve (Refer to ASME B16.34, Group 1.1 Materials tables & Section 7 Pressure Testing & API 598
Table 3 & Table 4) has working pressure design rating of 285 psi.
• Determine Valve body hydrotest value. Design x 1.5, round up to next 25 value (285 x 1.5 = 427.5 = 450 psi)
• Determine Valve Seat/Closure Test pressure. Design = 110% or 1.1 per API 598 Table 3 (285 x 1.1 = 313.5 psi).
• Determine hold time for seat test. Refer to API 598 Table 4. Closure test = 1 minute (valves to 12” NPS)
Do not allow a 30 minute hydrotest at 450 psi against the valve seat (because overpressurization results).
Resolution: Remove valve from line for test, install a 150# blind flange & proceed with test at 450 psi Or, reduce test
pressure to 313 psi & list valve seat closure as ""limiting factor"" if valve cannot* be removed for test (*justification &
Company
Example #2 approval
(Spec is required)
break between systems): CS Class 150 # system (hydrotest at 450 psi, limiting factor = flange).
1. Test limit is at a 24” Class 300 # Ball Valve (spec break). Proposed test against valve in closed position. Valve
passed body/seat test.
2. Calculations are made to determine if a test against the valve seat is allowable per SAES-A-004, Section 7.3
• A 300 # steel ball valve (ASME B16.34, Group 1.1 Matls table & API 598 Tables 3 & 4) has working pressure design
rating of 740 psi
• Determine Valve body hydrotest value. Design x 1.5, round up to next 25 value (740 x 1.5 = 1,110 = 1125 psi)
• Determine Valve Seat/Closure Test value. Design x 110% or 1.1 per API 598 Table 3 (740 x 1.1 = 814 psi)
• Determine hold time for seat test. Refer to API 598 Table 4. Closure test = 2 minutes (valves 14” NPS & over)
Result: Allow 30 minute hydro at 450 psi. Isolation valve is a Higher Class (No seat overpressurization).
Ensure limiting factors are listed (SIS Sheets/test reports) and are correct per SAES-L-150, Section 7.1
Example #1: A CS 150 # Raw Water System 12LEOU (hydrotest at 450 psi per SIS, limiting factor = flange)
System has Fusion-bonded epoxy (FBE) internally coated piping & valves (check & gate) for corrosive water service.
System (ISOs & SIS information match) Design Pressure = 190 psi at Design temperature of 100F. Piping is shown on
drawings to be API 5L, Gr B seamless pipe 24” Standard or .375” nominal wall, also 12” Standard or .375” Pipe flanges
are ASTM A 105, forged CS, per ASME 16.5. A 150 # gate valve in this service is Ductile iron ASTM A395 epoxy lined
body, Bolted Bonnet, ASTM B61/B62 bronze trim. A 150 # check valve in this service is Ductile iron ASTM A395 epoxy
lined body, Bolted Cover, ASTM B61/B62 bronze trim. Note: The system test will cover three open gate valves, one
check valve (internals removed for test), and one closed gate valve.
Page 19 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05(Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
Quick Calc Steps: 1. Do not accept a test in 150# system against a closed 150# valve (typical for all classes)
Do not accept the proposed test against a closed gate valve. Perform thorough review even after finding an error.
2. Determine Flange Pressure ratings as follows:
• Pipe flg limiting factor per ASME B16.5 (Table 1-A, Mat'l Group 1.1 = ASTM A 105) Press Temp Rating Table 2-1.1
• Working pressure rating for Class 150 systems @ temp of 100 F = 285 psig (multiply value by 1.5 per Section 8.3)
• 285 x 1.5 = 427.5, round up to next increment of 25 = 450 psig (acceptable, as our listed limiting factor is 450 psi)
3. Determine Valve Pressure ratings by checking ASME B16.34 OR API 598 Table 2 & 3
Note: Class 150 Ductile Iron = 400 psig per Table 2 (shell test) & 250 psig (high pressure seat
closure test)
ACTIONS: Do not accept 450 psig test pressure. Class 150 valves (ductile iron) are tested to 400 psig (250 at seat).
B) Request a test pressure reduction to 400 psig and test limit revision & proceed with review, even after
2 errors.
4. Determine piping Pressure ratings as follows in the following code formula based on 90% SMYS (per SA):
Use ASME B31.3 code formula t = PD / 2SE & SA requirement of 90% SMYS values for strength test calcs.
Formula for pressure is P = t x 2S(0.9)(E) / D
S = Stress Values from ASME B31.3 Table A-1 (API 5L Gr. B has a SMYS of 35,000) therefore S = 35,000
t = pipe thickness (nominal less 12.5 % mill tolerance for seamless pipe, less 0.10” for welded plate)
Therefore .375” x 87.5%, t = .328” for both 12” & 24” seamless pipe
P = unknown & E = Quality Factor from Table A-1A or Table A-1B (Quality factor for API 5L Seamless Pipe is 1.00),
therefore E = 1.00
D = outside diameter of piping (all sizes are considered in calcs), therefore 2 calcs will be performed, one for 24” and
the other for 12”
Calc for 12” pipe ... P=.328 x (2)(35,000)(0.9) / 12 = 1,722.66 or 1,723 psi is rating for limiting factor for 12” pipe
Calc for 24” pipe ... P=.328 x (2)(35,000)(0.9) / 24 = 861.33 or 861 psi is rating for limiting factor for 24” pipe
Notice how pipe diameter affects pressure! Neither pipe size is near our 400 psi limiting factor
5.Check FBE internal coating spec (APCS 101) indicates pressure rating of 5,000 psi per SAES-H-002, not a factor!
ACTION: Review Complete. Return test package to Engineering. Test pressure and arrangement are unacceptable:
1. Test pressure of 450 psig is unacceptable as Ductile Iron Valves are rated for 400 psig.
2. Use of a closed ductile iron valve at test limits is unacceptable.
Recommendation: Reduce Test pressure to 400 psig. Test valves in open position with blind at test limit.
Page 20 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
Attachment 3 - Saudi Aramco Pressure Testing Inspection Guide For Procedures
OVER PRESSURIZATION ALERT FOR LATERALS
1. 100% HOLD POINT ON LATERAL BRANCH CONNECTION WELDS FOR COMPANY VISUAL
EXAMINATION OF ROOT ID. MEANS OF VISUAL EXAM MUST BE PROVIDED (EXTENSION
MIRROR / REMOTE VIDEO). USE WINDOW TECHNIQUE FOR ROOT EXAM
2. LATERALS MUST RECEIVE NDE ON ANY EXISTING /
SUSPECT ROOT CONDITIONS TO PREVENT POSSIBILITY OF FAILURE DURING PRESSURE
TESTING. 3. FULL ENCIRCLEMENT SLEEVES MUST REINFORCE ALL
LATERALS. 4. LESSONS
LEARNED (HAWIYEH FATALITY) ... NEVER ALLOW LATERALS ON ANY SYSTEM ABOVE
CLASS 150# ... CALCS PER ASME B31.3 Appendix H apply. Do not allow overpressurization.
See acceptable detail below. Angle may vary.
Page 21 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
OVER PRESSURIZATION ALERT FOR LATERALS (60 Degree Lateral Branch Code Calc Example)
Page 22 of 23
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Review Procedure - Pressure Testing for Plant Piping SAIC-A-2001 30-Apr-13 MECH-
Page 23 of 23