1 SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - Mar - 2012) Rev 6 30-Apr-13
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
3 Material Receiving Insp - Portable Fire Protection Equip SAIC-B-2011 30-Apr-13 MECH-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
4
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
7
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
9
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
11
12 SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
13
SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL
15
18 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
19 No.

20 A General Requirements
Manufacturing & Testing Documentation has been submitted and Sch Q, Att. III,
21 A1
conforms to the applicable SA-175 Form Para. 3.21
Sch Q, Att. III,
22 A2 Final Material Disposition Report was submitted & verified complete.
Para. 3.21

Outstanding punch list items (pre-shipment inspection) are identified for Sch Q, Att III,
23 A3
tracking & follow-up. NCRs detail final disposition and resolution. Para. 3.24

Types and sizes of portable extinguisher units to be provided in the


various facility areas shall be as indicated in Section 4.2, in Table 1, as
specified in other applicable Saudi Aramco Standards, and as determined
SAES-B-019,
24 A4 by the Chief Fire Prevention Engineer or his designated representative.
Para. 4.1

Exceptions to Class 21 SA stock numbers listed above must be


SAES-B-019
25 A5 reviewed & approved by Chief Fire Prevention Engineer.
Para. 4.2.1
All portable fire extinguishers are "listed" as approved by a testing SAES-B-019
26 A6
authority, either Underwriters Labs (UL) or Factory Mutual (FM). Para. 4.2
Dry Chem 12.2 Kg Class BC (SAMS-21-102-840) extinguishers use SAES-B-019
27 A7
Purple K (potassium bicarbonate) as the extinguishing agent. Para. 4.2.2
Multi-purpose Dry Chemical Class ABC (SAMS-21-02-775) SAES-B-019
28 A8
extinguishers use monoammonium phosphate (extinguishing agent). Para. 4.2.3

Two-wheel cart-type Dry Chem 68 Kg Type BC extinguishers (specified


SAES-B-019 Para
29 A10 in Table 1) come with a manufacturer's cover provided. contractor can
4.6
provide a cover OR a shelter must be built.

30 B NFPA 10 Requirements (Classification, Marking, etc)


NFPA 10,
Instruction manuals are provided to detail instructions & cautions for
31 B1
extinguisher installation, operation, inspection, & maintenance.
Para. 4.3.1
Extinguisher operating instructions are located on the front of the NFPA 10,
32 B2
extinguisher & are clearly visible (with manufacturer's label). Para. 6.1.3.9

Extinguisher Classification Labels (on front) are as follows: A)


NFPA 10,
33 B3 Letters (A, B, C, D) show fire class extinguisher effectiveness. B) Class
Para. 6.1.3.9
A & B are preceded by a rating number (effectiveness).

Extinguisher Labels such as Hazardous material id system, six-year NFPA 10,


34 B4
maintenance & hydrotest labels are attached, but not on front. Para. 6.1.3.9
Markings located on the front of the fire extinguisher shells are of NFPA 10,
35 B5
adequate size & form to permit easy reading (legibility) at 1 meter. Annex B
Pictorial concept markings combine extinguisher use & nonuse on a
NFPA 10,
36 B6 single label. Fire extinguishers suitable for more than one fire class are
Annex B
identified by multiple symbols in a horizontal sequence.

Page 1 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - Mar- 2012) Rev 6 30-Apr-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Material Receiving Insp - Portable Fire Protection Equip SAIC-B-2011 30-Apr-13 MECH-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Fire extinguisher markings (label, tag, stencil, etc) attached provide the
following information:
A) Contents product name as it appears on the MSDS.
B) Listing of hazardous material identification per HMIS
NFPA 10,
C) Listing of hazardous material in excess of 1 percent of contents.
B7
D) Listing of each chemical in excess of 5 percent of contents.
Para. 4.2
E) Information (hazard of agents) per MSDS.
F) Manufacturer's name, mailing address & phone number

Decals applied are durable & resistant to color fading

Color separation identification for markings is as follows:


A) Picture symbol objects are white.
B) Background borders are white. NFPA 10,
B8 C) Background for "YES" symbols is blue. Annex B
D) Background for symbols with slash mark ("NO") is black.
E) Class of fire letters and wording are black.
F) Slash mark for black background symbols are red.

C Specific Inspection Points for Portable hand type extinguishers (4) as applicable

Pressurized Water 9.5L (2.5 gallon) Class A (21-104-550):


A) Storage area is not exposed to
direct sunlight or corrosive atmospheres or in environments exceeding
120°F.
B) Extinguisher mounting brackets or shelves are available.
C) Gauge reading is 95-100 psi or indicates full.
D) Gauge and glass is undamaged. GI-1781.001,
C1 E) Operating instructions are legible and facing outward. Supplement
F) Safety pin and seal are intact. Section 6.0
G) No sign of physical damage or corrosion exists.
H) Hose is free from cracks and cuts.

i) Nozzle is clear and not plugged.


J) Hydrotest date from manufacturer is shown on label.
K) Inspection tag exists showing last inspection date.

CO2 4.5 Kg (10 lb) Class BC Extinguisher (SAMS 21-102-223):


A) Storage area is not exposed to direct sunlight or corrosive
atmospheres or in environments exceeding 120°F.
B) Extinguisher mounting brackets or shelves are available.
C) Not sign of physical damage or corrosion exists.
GI-1781.001,
D) Operating instructions are legible and facing outward.
C2 Supplement
E) Safety pin and seal are intact.
Section 7.0
F) Horn is nonmetallic, clear and unplugged.
G) Hydrotest date from manufacturer is shown on label.
H) Weigh cylinder(s) to determine if fully charged.
i) Inspection tag exists showing last inspection date.

Page 2 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - Mar- 2012) Rev 6 30-Apr-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Material Receiving Insp - Portable Fire Protection Equip SAIC-B-2011 30-Apr-13 MECH-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Dry Chemical 12.2 Kg Class BC (SAMS-21-102-840) & the Multi-


purpose Dry Chemical Class ABC (21-102-775):
A) Storage area is not exposed to direct sunlight or corrosive
atmospheres or in environments exceeding 120°F.
B) Extinguisher mounting brackets or shelves are available.
C) Not sign of physical damage or corrosion exists.
D) Operating instructions are legible and facing outward.
GI-1781.001,
E) Safety pin and seal are intact.
C3 Supplement
F) CO2 cartridge disc is intact, weigh cartridge to check for leaks.
Section 8.0
G) Cap gasket is in good condition.
H) Puncture lever operates freely.
i) Nozzle is clear and unplugged.
J) Dry chemical level and type is correct with no caking.
K) Hydrotest date from manufacturel is shown on label.
L) Inspection tag exists showing last inspection date.

Portable Halon Fire Extinguishers are no longer allowed (ozone


GI-1781.001,
C4 depletion) & must be replaced with an approved type extinguisher.
Section 4.9

D Wheeled cart type extinguisher (2 types)

Dry Chem 68 Kg Type BC (SAMS-21-106-650):


A) Storage area is not exposed to direct sunlight or corrosive
atmospheres or in environments exceeding 120°F.
B) Manufacturer weather cover* (See 1G) is in good condition.

C) Wheels turn freely & tires are inflated properly in good condition.
E) Tamper seal and safety pin are intact.
F) Nitrogen pressure gauge reads full (at least 1600 psi). GI-1781.001,
D1 G) Extinguisher has no obvious damage or corrosion. Supplement
H) Rubber hose is coiled properly and in good condition. Section 10.0
i) Nozzle moves freely, is in holder, unplugged & in good condition.
J) Dry chemical level and type is correct with no caking.
K) Cap gasket is in good condition
L) Bursting disc is intact.
M) Hydrotest date from manufacturel is shown on
label.
N) Inspection tag exists showing last inspection date.

CO2 with dual 23 kg cylinders Type BC (SAMS-21-106-690):


A) Storage area is not exposed to direct sunlight or corrosive
atmospheres or in environments exceeding 120°F.
B) Hose is free from cracks & cuts.
C) Hose is coiled properly.
D) Tamper seal and safety pin are intact.
GI-1781.001,
E) Wheels rotate freely.
D2 Supplement
F) Tires are properly inflated and in good condition
Section 11.0
G) Manufacturer's weather cover is in good condition.
H) No obvious corrosion or physical damage exists.
i) Hydrotest date from manufacturel is shown on
label.
J) Inspection tag exists showing last inspection date.

E Twin agent Extinguishers (Unit Skid or trailer)

Page 3 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - Mar- 2012) Rev 6 30-Apr-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Material Receiving Insp - Portable Fire Protection Equip SAIC-B-2011 30-Apr-13 MECH-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Inspect the Twin Agent Unit Skid or Trailer Extinguisher:


A) Storage area is not exposed to direct sunlight or corrosive
atmospheres or in environments exceeding 120°F.
B) Unit has a Mfg's cover (or will be housed in shed, sunshade).
C) No obvious corrosion or physical damage.
D) Tires are properly inflated and in good condition.
E) Seal and safety pin are intact.
GI-1781.001,
F) Hoses are free from cracks, unplugged, & in good condition.
E1 Supplement
G) Dry chemical level and type is correct with no caking.
Section 12.0
H) Nitrogen pressure gauge reads at least 2000 psi.
i) CO2 cartridge disc is intact.
J) Foam (light water) solution is used.
K) Cap gasket in good condition.
L) Hydrotest date from manufacturer is shown on label.
M) Inspection tag exists showing last inspection date.

F GI-1781.001 General Requirements before Service


All new fire extinguishers are delivered to Local Fire Control Unit to be
inspected, commissioned, tagged, & numbered prior to service GI-1781
GI-1781.001,
F1 Checklists above are used by SA Fire Control Unit.
Section 5.10.1
Contractor has checked all equipment before delivery to SA
REMARKS:

REFERENCE DOCUMENTS:
1- Saudi Aramco GI-1781.001 -- Inspection, Test, and Maintenance of Fire Protection Equipment, 3 January 2009
2. Schedule Q Jazan Project Specific February 2008
2- SAES-B-019 -- Portable, Mobile and Special Fixed Firefighting Equipment, 22 July 2012

3- NFPA 10 -- Standard for Portable Fire Extinguishers, 2013 Edition


Contractor / Third-Party Saudi Aramco
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED