1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17

2 SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Special Fixed Extinguishing Equipment - Installation


3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
4
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
7
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
9
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
11
12 SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
13
SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL
15
18 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
19 No.

20 A General Requirements (As Applicable)

Special protection for fixed extinguishing/suppression systems:

A) Fixed
carbon dioxide (CO2) (See Sect 2, 3 Checklists)
B) Fixed dry chemical system (Section 4, 5, 6
SAES-B-019
21 A1 Checklists)
Para 6.1
C) Fixed wet chemical system (Section 7, 8 Checklists)
D) Fixed
Halon 1301 system (Section 9, 10 Checklists)
E) Other Fixed
systems (approved by Chief Fire Prevention Eng.)

Areas covered by special fixed equipment are as follows:


A) Kitchen exhaust hood & vent systems &
cooking appliances B) Gas turbine
enclosures
C) Special labs & chemical storage rooms SAES-B-019
22 A2
D) Communications rooms in critical Para 6.1
communications facilities E)
Computer rooms in central computer facilities
F) Rotating power generating equipment
enclosures.

Where fixed extinguishing systems protect enclosures of rotating


SAES-B-019
23 A3 equipment, those systems are furnished by the equipment vendor.
Para 6.1
These systems have 100% spare agent cylinders readily available.

All new fire protection equipment is inspected and tested by the GI-1781.001,
24 A4
Fire Protection Department before placing in service. Section 4.1

25 B Fixed CO2 Systems (NFPA 12 & GI-1781.001 Supplement 29)

SAES-B-019
26 B1 CO2 systems are prohibited for normally manned areas.
Para. 6.2

CO2 system design & installation follows NFPA 12 requirements and SAES-B-019
27 B2
Saudi Aramco SAES-B-019 exceptions listed below. Para. 6.2

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAF
AGAHAIAJAK
AAM
L ANAOAPAQARASATAU AV AW AXAY
CO2 systems have an alarm warning device that activates 30 seconds SAES-B-019
28 B3
prior to any discharge of CO2 into the area. Para. 6.2

Lock-out device to disarm CO2 systems if personnel are present is SAES-B-019


29 B4
installed (unless omission is approved by Chief Fire Prevention Eng) Para. 6.2

SAES-B-019
30 B5 Enclosed rooms have an exterior exit door with panic hardware.
Para. 6.2

Air-moving power & fire dampers (HVAC system) shut down upon SAES-B-019
31 B6
system actuation. Para. 6.2

NFPA 12,
Determine proper CO2 system installation & functionality.
32 B7
Para 4.4.3.3

NFPA 12,
Completed CO2 systems are inspected and tested using qualified
33 B8
personnel to meet the approval of the authority having jurisdiction.
Para
4.4.3.1

NFPA 12,
34 B9 Only listed or approved equipment and devices are used in system. Para
4.4.3.2

Saudi Aramco: Company General Use


AZ
1
2
3

4
PLANT NO.
7

9
TRAVEL TIME
11
E ONLY12
PERMIT REQUIRED?
13

15
18
RE-INSP DATE
19
20

21

22

23

24

25

26

27

Saudi Aramco: Company General Use


AZ

28

29

30

31

32

33

34

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAFAGAHAIAJAKALAMANAOAPAQARASATAUAV AW
1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
Special Fixed Extinguishing Equipment - Installation
3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.

NFPA 12,
A thorough visual inspection of the installed CO2 system and hazard area
9 B10
has been performed (walkdown)
Para
4.4.3.3.1
NFPA 12,
Piping, operational equipment & discharge nozzles are inspected for
10 B11
proper size and location.
Para
4.4.3.3.1.1
NFPA 12,
11 B12 Locations of alarms and manual emergency releases are correct. Para
4.4.3.3.1.2
NFPA 12,
Configuration of the hazard is compared to the original hazard
12 B13
specification and is within design limits.
Para
4.4.3.3.1.3
NFPA 12,
The hazard is inspected closely for unclosable openings & sources of
13 B14
agent loss that could have been overlooked in the original spec.
Para
4.4.3.3.1.4
Labelling of devices is checked as follows:
NFPA 12,
A) Proper designations and instructions exist.
14 B15
B) Nameplate data on
Para
4.4.3.3.2.1
storage containers matches specifications.
NFPA 12,
Nondestructive operational tests are performed on devices (includes
15 B16
detection & actuation) to assure proper system function.
Para
4.4.3.3.3
NFPA 12,
16 B17 A full discharge test is performed on all systems. Para
4.4.3.3.4.1
Where multiple hazards are protected from a common supply, a full NFPA 12,
17 B18 discharge test is performed for each hazard. Para
Prior to testing, proper safety procedures are reviewed. 4.4.3.3.4.2

18 C Fixed CO2 Systems (GI-1781.001 Supp. 26 Insp & Testing)

GI-1781.001,
19 C1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 26

System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
20 C2
Supplement 26

Automatic fire detection system (AFDS) is on-line & operating.


• Normal power supply indicator is “ON."
• Battery power indicator reads 12/ 24 VDC.
• Master alarm visual indicator is "OFF.”
• Master trouble visual indicator is "OFF.”
• Zone trouble visual indicator is "OFF.”
• Lamp test lights all visual indicators when activated.
• Manual pull stations are in normal operational condition. GI-1781.001,
21 C3
• Automatic fire detectors are in normal operational condition. Supplement 26
• All visual and audible alarms operate when tested.*
• Batteries support operation of the system when tested.*
• Alarm signal from tests* is received at remote monitoring stations.
• Logbook is provided & utilized
• Zone layout plan is available.
• Inspection tag (interval) and logbook are up-to-date.
This 14-step AFDS checklist is used for all type fixed systems

GI-1781.001,
22 C4 Pipe manifolds are painted & pipe is not subject to external loading
Supplement 26

GI-1781.001,
23 C5 Pipe hangers are not damaged, loose, or missing.
Supplement 26

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAFAGAHAIAJAKALAMANAOAPAQARASATAUAV AW
1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
Special Fixed Extinguishing Equipment - Installation
3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.

GI-1781.001,
24 C6 Manual discharge is in normal standby mode.
Supplement 26

Solenoid/pneumatic discharge valves are firmly attached to the cylinder GI-1781.001,


25 C7
head. Supplement 26

GI-1781.001,
26 C8 Discharge nozzles are unobstructed.
Supplement 26

GI-1781.001,
27 C9 Cylinder brackets are firmly attached to the cylinders.
Supplement 26

GI-1781.001,
28 C10 Operating instructions are posted and legible.
Supplement 26

GI-1781.001,
29 C11 All system hoses have valid hydrotest date (every five years).
Supplement 26

Master/pilot cylinder pressure gauge indicates correct pressure for GI-1781.001,


30 C12
ambient temperature. Supplement 26

GI-1781.001,
31 C13 All cylinders are weighed and are fully charged.
Supplement 26

GI-1781.001,
32 C14 Cylinders have valid hydrostatic test date (every five years).
Supplement 26

GI-1781.001,
33 C15 Safety/warning signs are posted identifying the protected area.
Supplement 26

GI-1781.001,
34 C16 Protected space has not been altered.
Supplement 26

System alarm & equipment activates & operates properly.


GI-1781.001,
35 C18 • Alarm signals to building alarm control panel & remote stations test
Supplement 26
• Test results are recorded in the logbook.

GI-1781.001,
36 C19 Inspection tag and logbook are signed and updated.
Supplement 26

37 D Fixed Dry Chemical Systems (NFPA 17)

SAES-B-019 Para
38 D1 Dry chemical systems are designed & installed per NFPA 17
6.3

NFPA 17,
39 D2 The completed system is tested by qualified personnel.
Section 10.4
NFPA 17,
Tests determine that the system has been properly installed & will function
40 D3
as intended.
Section 10.4
NFPA 17,
Installers certify that installations are made in accordance with the
41 D4
approved plans and the listing of a testing laboratory.
Section 10.4
NFPA 17,
Acceptance tests include discharge of dry chemical in sufficient amount to
42 D5
verify the system is properly installed and functional.
Section 10.4
NFPA 17,
The method of verification shall be acceptable to the authority having
43 D6
jurisdiction.
Section 10.4

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAFAGAHAIAJAKALAMANAOAPAQARASATAUAV AW
1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
Special Fixed Extinguishing Equipment - Installation
3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.

NFPA 17,
44 D7 Piping is not hydrostatically tested. Dry gas is used as the medium.
Section 10.4
NFPA 17,
45 D8 Labeling of devices show proper designations & instructions exist.
Section 10.4
NFPA 17,
After discharge of dry chemical, all piping & nozzles are blown clean using
46 D9
compressed dry air or nitrogen.
Section 10.4
NFPA 17,
47 D10 System is properly charged & placed in the normal "set" condition.
Section 10.4
NFPA 17,
48 D11 Owner has manufacturer's installation & maintenance manuals
Section 10.5

49 E GI-1781.001 Supp. 27(Dry Chemical System - Kitchen Hood Testing & Inspection)

GI-1781.001,
50 E1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 27

System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
51 E2
Supplement 27

Automatic fire detection system (AFDS) is on-line & operating.


GI-1781.001,
52 E3 • The 14-step AFDS checklist (see
Supplement 27
3C) is applied

GI-1781.001,
53 E4 Dry chemical level is "FULL."
Supplement 27

GI-1781.001,
54 E5 Valves, pipes, and pipefittings are painted and not corroded.
Supplement 27

GI-1781.001,
55 E6 Manual actuators are unobstructed.
Supplement 27

GI-1781.001,
56 E7 Nozzle caps are intact and undamaged.
Supplement 27

GI-1781.001,
57 E8 Tamper indicators and seals are intact.
Supplement 27

GI-1781.001,
58 E9 Manual discharge button is provided with sealed safety pin.
Supplement 27

GI-1781.001,
59 E10 Fusible link/heat detectors are clean and not damaged.
Supplement 27

GI-1781.001,
60 E11 Cylinder/hose assemblies have valid hydrotest (every 12 years).
Supplement 27

GI-1781.001,
61 E12 Hoods & filters are free of combustibles & debris (accumulations).
Supplement 27

GI-1781.001,
62 E13 Operating instructions are posted and legible.
Supplement 27

System alarm & equipment activates & operates properly.


GI-1781.001,
63 E14 • Alarm signals to building alarm control panel & remote
Supplement 27
stations test • Test results are recorded in the logbook.

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAFAGAHAIAJAKALAMANAOAPAQARASATAUAV AW
1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
Special Fixed Extinguishing Equipment - Installation
3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.

GI-1781.001,
64 E15 Inspection tag and logbook are signed and updated.
Supplement 27

65 F GI-1781.001 Supp. 29 (Dry Chemical System - Industrial Plant Testing & Inspection)

GI-1781.001,
66 F1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 29

System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
67 F2
Supplement 29

Automatic fire detection system (AFDS) is on-line & operating.


GI-1781.001,
68 F3 • The 14-step AFDS checklist (see
Supplement 29
3C) is applied

GI-1781.001,
69 F4 Pilot cylinder disc/pneumatic valve is intact/closed.
Supplement 29

GI-1781.001,
70 F5 Nitrogen cylinder(s) gauge reads 2000-2500 psig.
Supplement 29

GI-1781.001,
71 F6 Cylinder brackets are firmly attached.
Supplement 29

GI-1781.001,
72 F7 Nitrogen cylinder(s) has valid hydrotest date (every five years).
Supplement 29

Fusible links/automatic fire detection devices are all in normal standby GI-1781.001,
73 F8
mode, clean, and show no sign of damage. Supplement 29

GI-1781.001,
74 F9 Pneumatic valves of each nitrogen cylinder are firmly attached.
Supplement 29

GI-1781.001,
75 F10 Nozzles are clean and not damaged.
Supplement 29

GI-1781.001,
76 F11 Cylinder/hose assemblies have valid hydrotest date (every 12 yrs).
Supplement 29

GI-1781.001,
77 F12 Operating instructions are posted and legible.
Supplement 29

System alarm & equipment activates & operates properly.


GI-1781.001,
78 F13 • Alarm signals to building alarm control panel & remote
Supplement 29
stations test • Test results are recorded in the logbook.

Inspection tags are installed & updated (logbook utilized) GI-1781.001,


79 F14
Inspection tag and logbook are signed and updated. Supplement 29

80 G Fixed Wet Chemical Systems (NFPA 17A) for Kitchens

SAES-B-019 Para
81 G1 Wet Chemical Systems are designed & installed per NFPA 17A.
6.4

Kitchen exhaust and vent systems and other applications (requested SAES-B-019 Para
82 G2
by Chief Fire Prevention Engineer) utilize wet chemicals. 6.4

Completed wet chemical systems are tested by trained personnel per NFPA 17A,
83 G3
manufacturer’s listed installation and maintenance manual. Section 6.4

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAFAGAHAIAJAKALAMANAOAPAQARASATAUAV AW
1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
Special Fixed Extinguishing Equipment - Installation
3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.

NFPA 17A,
84 G4 The system passed tests for properly installation & functionality
Section 6.4

Installers certified that the system was installed per approved plans and NFPA 17A,
85 G5
the manufacturer’s listed installation and maintenance manual. Section 6.4

Where required by Company, the approval tests include discharge of wet NFPA 17A,
86 G6
chemical to verify system installation is functional. Section 6.4

The owner shall be provided with a copy of the manufacturer’s listed NFPA 17A,
87 G7
installation and maintenance manual or listed owner’s manual. Section 6.4

88 H GI-1781.001 Supplement 28 (Wet Chemical System - Hood Type Testing & Inspection)

GI-1781.001,
89 H1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 28

System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
90 H2
Supplement 28

Automatic fire detection system (AFDS) is on-line & operating.


GI-1781.001,
91 H3 • The 14-step AFDS checklist (see
Supplement 28
3C) is applied

GI-1781.001,
92 H4 Manual actuators are unobstructed.
Supplement 28

GI-1781.001,
93 H5 Tamper indicators and seals are intact.
Supplement 28

GI-1781.001,
94 H6 Maintenance tag or certificate is in place.
Supplement 28

GI-1781.001,
95 H7 No obvious physical damage or condition exists to hinder operation.
Supplement 28

GI-1781.001,
96 H8 Pressure gauges, if provided, are in operable range.
Supplement 28

GI-1781.001,
97 H9 Nozzle blowout caps are intact and undamaged.
Supplement 28

GI-1781.001,
98 H10 Wet chemical pressure gauge reads full.
Supplement 28

GI-1781.001,
99 H11 Fusible links/heat detectors are clean and not damaged.
Supplement 28

GI-1781.001,
100 H12 Cylinder/hose assemblies have valid hydrotest date (every 12 yrs).
Supplement 28

GI-1781.001,
101 H13 Hoods & filters are free of combustibles & debris (accumulations).
Supplement 28

GI-1781.001,
102 H14 Operating instructions are posted and legible.
Supplement 28

System alarm & equipment activates & operates properly.


GI-1781.001,
103 H15 • Alarm signals to building alarm control panel & remote
Supplement 28
stations test • Test results are recorded in the logbook.

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAFAGAHAIAJAKALAMANAOAPAQARASATAUAV AW
1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
Special Fixed Extinguishing Equipment - Installation
3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.

GI-1781.001,
104 H16 Inspection tag and logbook are signed and updated.
Supplement 28

105 I GI-1781.001 Supp. 19 (Fire Detection and Alarm System Testing & Inspection)

GI-1781.001,
106 I1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 19

System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
107 I2
Supplement 19

Automatic fire detection system (AFDS) is on-line & operating.


GI-1781.001,
108 I3 • The 14-step AFDS checklist (see
Supplement 19
3C) is applied

GI-1781.001,
109 I4 Pilot cylinder disc/pneumatic valve is intact/closed.
Supplement 19

GI-1781.001,
110 I5 Nitrogen cylinder(s) gauge reads 2000-2500 psig.
Supplement 19

GI-1781.001,
111 I6 Cylinder brackets are firmly attached.
Supplement 19

GI-1781.001,
112 I7 Nitrogen cylinder(s) has valid hydrotest date (every five years).
Supplement 19

Fusible links/automatic fire detection devices are all in normal standby GI-1781.001,
113 I8
mode, clean, and show no sign of damage. Supplement 19

GI-1781.001,
114 I9 Pneumatic valves of each nitrogen cylinder are firmly attached.
Supplement 19

GI-1781.001,
115 I10 Nozzles are clean and not damaged.
Supplement 19

GI-1781.001,
116 I11 Cylinder/hose assemblies have valid hydrotest date (every 12 yrs).
Supplement 19

GI-1781.001,
117 I12 Operating instructions are posted and legible.
Supplement 19

System alarm & equipment activates & operates properly.


GI-1781.001,
118 I13 • Alarm signals to building alarm control panel & remote
Supplement 19
stations test • Test results are recorded in the logbook.

GI-1781.001,
119 I14 Inspection tag and logbook are signed and updated.
Supplement 19

120 J GI-1781.001 Supplement 25(Halon System Testing & Inspection)

GI-1781.001,
121 J1 Control panel’s main power indicator is “ON.”
Supplement 25

GI-1781.001,
122 J2 System activation indicator on fire control panel is "OFF.”
Supplement 25

GI-1781.001,
123 J3 Pipe manifolds are painted & pipe is not subject to external loading
Supplement 25

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAFAGAHAIAJAKALAMANAOAPAQARASATAUAV AW
1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
Special Fixed Extinguishing Equipment - Installation
3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.

GI-1781.001,
124 J4 Pipe hangers are not damaged, loose, or missing.
Supplement 25

GI-1781.001,
125 J5 Manual discharge & abort switches are in normal standby mode.
Supplement 25

GI-1781.001,
126 J6 Cylinder transfer key is set to primary.
Supplement 25

GI-1781.001,
127 J7 Cylinder brackets are firmly attached.
Supplement 25

Solenoid & pneumatic discharge valves are firmly attached to the cylinder GI-1781.001,
128 J8
head. Supplement 25

GI-1781.001,
129 J9 Discharge nozzles are unobstructed & blow-off caps are in place
Supplement 25

GI-1781.001,
130 J10 Discharge flexible hoses are in good condition.
Supplement 25

GI-1781.001,
131 J11 Cylinder(s) are fully charged to correct pressure (ambient temp)
Supplement 25

GI-1781.001,
132 J12 Manual & automatic actuating devices are operational
Supplement 25

GI-1781.001,
133 J13 Manual & automatic devices meet mfg's recommendations.
Supplement 25

GI-1781.001,
134 J14 As applicable, pneumatic type CO2 cartridge disc is intact.
Supplement 25

GI-1781.001,
135 J15 Hose assemblies have valid hydrotest date (every five years).
Supplement 25

GI-1781.001,
136 J16 Cylinders have valid hydrostatic test date (every five years).
Supplement 25

GI-1781.001,
137 J17 Safety/warning signs are posted identifying the protected area.
Supplement 25

GI-1781.001,
138 J18 Operating instructions are posted and legible.
Supplement 25

GI-1781.001,
139 J19 Protected space has not been altered.
Supplement 25

GI-1781.001,
140 J20 Inspection tag and logbook are signed and updated.
Supplement 25

Saudi Aramco: Company General Use


A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAAABACADAEAFAGAHAIAJAKALAMANAOAPAQARASATAUAV AW
1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
SAIC NUMBER DATE APPROVED QR NUMBER
2 SAUDI ARAMCO INSPECTION CHECKLIST
Special Fixed Extinguishing Equipment - Installation
3 SAIC-B-2015 30-Nov-17 MECH
Inspection & Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
REMARKS:

142

144 REFERENCE DOCUMENTS:


145 1- SAES-B-019 -- Portable, Mobile and Special Fixed Firefighting Equipment, (22 July 2012)
146 2- Saudi Aramco GI-1781.001 -- Inspection, Test, and Maintenance of Fire Protection Equipment, 3 Jan 2009
147 3- NFPA® 12, Standard on Carbon Dioxide Extinguishing Systems, 2011 Edition
4- NFPA® 17, Standard for Dry Chemical Extinguishing Systems, 2012 Edition
148
150 Contractor / Third-Party Saudi Aramco
151 Construction Representative* PMT Representative
152 Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed
Name, Initials and Date: Name, Initials and Date:
153
154 QC Inspector PID Representative
155 Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed
Name, Initials and Date: Name, Initials and Date:
156
157 QC Supervisor Proponent and Others
158 Quality Record Approved:
Name, Organization,
T&I Witnessed QC Record Reviewed
Name, Sign and Date:
159 Initials and Date:

160 *Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED