1 SAUDI ARAMCO ID/PIEU - 30-Nov-2017- REV. 2017.09.00 (Standards Cutoff - September 30, 2017) Rev. 2017.09.00 30-Sep-17
A) Fixed
carbon dioxide (CO2) (See Sect 2, 3 Checklists)
B) Fixed dry chemical system (Section 4, 5, 6
SAES-B-019
21 A1 Checklists)
Para 6.1
C) Fixed wet chemical system (Section 7, 8 Checklists)
D) Fixed
Halon 1301 system (Section 9, 10 Checklists)
E) Other Fixed
systems (approved by Chief Fire Prevention Eng.)
All new fire protection equipment is inspected and tested by the GI-1781.001,
24 A4
Fire Protection Department before placing in service. Section 4.1
SAES-B-019
26 B1 CO2 systems are prohibited for normally manned areas.
Para. 6.2
CO2 system design & installation follows NFPA 12 requirements and SAES-B-019
27 B2
Saudi Aramco SAES-B-019 exceptions listed below. Para. 6.2
SAES-B-019
30 B5 Enclosed rooms have an exterior exit door with panic hardware.
Para. 6.2
Air-moving power & fire dampers (HVAC system) shut down upon SAES-B-019
31 B6
system actuation. Para. 6.2
NFPA 12,
Determine proper CO2 system installation & functionality.
32 B7
Para 4.4.3.3
NFPA 12,
Completed CO2 systems are inspected and tested using qualified
33 B8
personnel to meet the approval of the authority having jurisdiction.
Para
4.4.3.1
NFPA 12,
34 B9 Only listed or approved equipment and devices are used in system. Para
4.4.3.2
4
PLANT NO.
7
9
TRAVEL TIME
11
E ONLY12
PERMIT REQUIRED?
13
15
18
RE-INSP DATE
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
NFPA 12,
A thorough visual inspection of the installed CO2 system and hazard area
9 B10
has been performed (walkdown)
Para
4.4.3.3.1
NFPA 12,
Piping, operational equipment & discharge nozzles are inspected for
10 B11
proper size and location.
Para
4.4.3.3.1.1
NFPA 12,
11 B12 Locations of alarms and manual emergency releases are correct. Para
4.4.3.3.1.2
NFPA 12,
Configuration of the hazard is compared to the original hazard
12 B13
specification and is within design limits.
Para
4.4.3.3.1.3
NFPA 12,
The hazard is inspected closely for unclosable openings & sources of
13 B14
agent loss that could have been overlooked in the original spec.
Para
4.4.3.3.1.4
Labelling of devices is checked as follows:
NFPA 12,
A) Proper designations and instructions exist.
14 B15
B) Nameplate data on
Para
4.4.3.3.2.1
storage containers matches specifications.
NFPA 12,
Nondestructive operational tests are performed on devices (includes
15 B16
detection & actuation) to assure proper system function.
Para
4.4.3.3.3
NFPA 12,
16 B17 A full discharge test is performed on all systems. Para
4.4.3.3.4.1
Where multiple hazards are protected from a common supply, a full NFPA 12,
17 B18 discharge test is performed for each hazard. Para
Prior to testing, proper safety procedures are reviewed. 4.4.3.3.4.2
GI-1781.001,
19 C1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 26
System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
20 C2
Supplement 26
GI-1781.001,
22 C4 Pipe manifolds are painted & pipe is not subject to external loading
Supplement 26
GI-1781.001,
23 C5 Pipe hangers are not damaged, loose, or missing.
Supplement 26
7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
GI-1781.001,
24 C6 Manual discharge is in normal standby mode.
Supplement 26
GI-1781.001,
26 C8 Discharge nozzles are unobstructed.
Supplement 26
GI-1781.001,
27 C9 Cylinder brackets are firmly attached to the cylinders.
Supplement 26
GI-1781.001,
28 C10 Operating instructions are posted and legible.
Supplement 26
GI-1781.001,
29 C11 All system hoses have valid hydrotest date (every five years).
Supplement 26
GI-1781.001,
31 C13 All cylinders are weighed and are fully charged.
Supplement 26
GI-1781.001,
32 C14 Cylinders have valid hydrostatic test date (every five years).
Supplement 26
GI-1781.001,
33 C15 Safety/warning signs are posted identifying the protected area.
Supplement 26
GI-1781.001,
34 C16 Protected space has not been altered.
Supplement 26
GI-1781.001,
36 C19 Inspection tag and logbook are signed and updated.
Supplement 26
SAES-B-019 Para
38 D1 Dry chemical systems are designed & installed per NFPA 17
6.3
NFPA 17,
39 D2 The completed system is tested by qualified personnel.
Section 10.4
NFPA 17,
Tests determine that the system has been properly installed & will function
40 D3
as intended.
Section 10.4
NFPA 17,
Installers certify that installations are made in accordance with the
41 D4
approved plans and the listing of a testing laboratory.
Section 10.4
NFPA 17,
Acceptance tests include discharge of dry chemical in sufficient amount to
42 D5
verify the system is properly installed and functional.
Section 10.4
NFPA 17,
The method of verification shall be acceptable to the authority having
43 D6
jurisdiction.
Section 10.4
7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
NFPA 17,
44 D7 Piping is not hydrostatically tested. Dry gas is used as the medium.
Section 10.4
NFPA 17,
45 D8 Labeling of devices show proper designations & instructions exist.
Section 10.4
NFPA 17,
After discharge of dry chemical, all piping & nozzles are blown clean using
46 D9
compressed dry air or nitrogen.
Section 10.4
NFPA 17,
47 D10 System is properly charged & placed in the normal "set" condition.
Section 10.4
NFPA 17,
48 D11 Owner has manufacturer's installation & maintenance manuals
Section 10.5
49 E GI-1781.001 Supp. 27(Dry Chemical System - Kitchen Hood Testing & Inspection)
GI-1781.001,
50 E1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 27
System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
51 E2
Supplement 27
GI-1781.001,
53 E4 Dry chemical level is "FULL."
Supplement 27
GI-1781.001,
54 E5 Valves, pipes, and pipefittings are painted and not corroded.
Supplement 27
GI-1781.001,
55 E6 Manual actuators are unobstructed.
Supplement 27
GI-1781.001,
56 E7 Nozzle caps are intact and undamaged.
Supplement 27
GI-1781.001,
57 E8 Tamper indicators and seals are intact.
Supplement 27
GI-1781.001,
58 E9 Manual discharge button is provided with sealed safety pin.
Supplement 27
GI-1781.001,
59 E10 Fusible link/heat detectors are clean and not damaged.
Supplement 27
GI-1781.001,
60 E11 Cylinder/hose assemblies have valid hydrotest (every 12 years).
Supplement 27
GI-1781.001,
61 E12 Hoods & filters are free of combustibles & debris (accumulations).
Supplement 27
GI-1781.001,
62 E13 Operating instructions are posted and legible.
Supplement 27
7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
GI-1781.001,
64 E15 Inspection tag and logbook are signed and updated.
Supplement 27
65 F GI-1781.001 Supp. 29 (Dry Chemical System - Industrial Plant Testing & Inspection)
GI-1781.001,
66 F1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 29
System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
67 F2
Supplement 29
GI-1781.001,
69 F4 Pilot cylinder disc/pneumatic valve is intact/closed.
Supplement 29
GI-1781.001,
70 F5 Nitrogen cylinder(s) gauge reads 2000-2500 psig.
Supplement 29
GI-1781.001,
71 F6 Cylinder brackets are firmly attached.
Supplement 29
GI-1781.001,
72 F7 Nitrogen cylinder(s) has valid hydrotest date (every five years).
Supplement 29
Fusible links/automatic fire detection devices are all in normal standby GI-1781.001,
73 F8
mode, clean, and show no sign of damage. Supplement 29
GI-1781.001,
74 F9 Pneumatic valves of each nitrogen cylinder are firmly attached.
Supplement 29
GI-1781.001,
75 F10 Nozzles are clean and not damaged.
Supplement 29
GI-1781.001,
76 F11 Cylinder/hose assemblies have valid hydrotest date (every 12 yrs).
Supplement 29
GI-1781.001,
77 F12 Operating instructions are posted and legible.
Supplement 29
SAES-B-019 Para
81 G1 Wet Chemical Systems are designed & installed per NFPA 17A.
6.4
Kitchen exhaust and vent systems and other applications (requested SAES-B-019 Para
82 G2
by Chief Fire Prevention Engineer) utilize wet chemicals. 6.4
Completed wet chemical systems are tested by trained personnel per NFPA 17A,
83 G3
manufacturer’s listed installation and maintenance manual. Section 6.4
7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
NFPA 17A,
84 G4 The system passed tests for properly installation & functionality
Section 6.4
Installers certified that the system was installed per approved plans and NFPA 17A,
85 G5
the manufacturer’s listed installation and maintenance manual. Section 6.4
Where required by Company, the approval tests include discharge of wet NFPA 17A,
86 G6
chemical to verify system installation is functional. Section 6.4
The owner shall be provided with a copy of the manufacturer’s listed NFPA 17A,
87 G7
installation and maintenance manual or listed owner’s manual. Section 6.4
88 H GI-1781.001 Supplement 28 (Wet Chemical System - Hood Type Testing & Inspection)
GI-1781.001,
89 H1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 28
System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
90 H2
Supplement 28
GI-1781.001,
92 H4 Manual actuators are unobstructed.
Supplement 28
GI-1781.001,
93 H5 Tamper indicators and seals are intact.
Supplement 28
GI-1781.001,
94 H6 Maintenance tag or certificate is in place.
Supplement 28
GI-1781.001,
95 H7 No obvious physical damage or condition exists to hinder operation.
Supplement 28
GI-1781.001,
96 H8 Pressure gauges, if provided, are in operable range.
Supplement 28
GI-1781.001,
97 H9 Nozzle blowout caps are intact and undamaged.
Supplement 28
GI-1781.001,
98 H10 Wet chemical pressure gauge reads full.
Supplement 28
GI-1781.001,
99 H11 Fusible links/heat detectors are clean and not damaged.
Supplement 28
GI-1781.001,
100 H12 Cylinder/hose assemblies have valid hydrotest date (every 12 yrs).
Supplement 28
GI-1781.001,
101 H13 Hoods & filters are free of combustibles & debris (accumulations).
Supplement 28
GI-1781.001,
102 H14 Operating instructions are posted and legible.
Supplement 28
7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
GI-1781.001,
104 H16 Inspection tag and logbook are signed and updated.
Supplement 28
105 I GI-1781.001 Supp. 19 (Fire Detection and Alarm System Testing & Inspection)
GI-1781.001,
106 I1 Control panel’s main power indicator is “ON.” (Weekly)
Supplement 19
System activation indicator on the fire alarm control panel is "OFF.” GI-1781.001,
107 I2
Supplement 19
GI-1781.001,
109 I4 Pilot cylinder disc/pneumatic valve is intact/closed.
Supplement 19
GI-1781.001,
110 I5 Nitrogen cylinder(s) gauge reads 2000-2500 psig.
Supplement 19
GI-1781.001,
111 I6 Cylinder brackets are firmly attached.
Supplement 19
GI-1781.001,
112 I7 Nitrogen cylinder(s) has valid hydrotest date (every five years).
Supplement 19
Fusible links/automatic fire detection devices are all in normal standby GI-1781.001,
113 I8
mode, clean, and show no sign of damage. Supplement 19
GI-1781.001,
114 I9 Pneumatic valves of each nitrogen cylinder are firmly attached.
Supplement 19
GI-1781.001,
115 I10 Nozzles are clean and not damaged.
Supplement 19
GI-1781.001,
116 I11 Cylinder/hose assemblies have valid hydrotest date (every 12 yrs).
Supplement 19
GI-1781.001,
117 I12 Operating instructions are posted and legible.
Supplement 19
GI-1781.001,
119 I14 Inspection tag and logbook are signed and updated.
Supplement 19
GI-1781.001,
121 J1 Control panel’s main power indicator is “ON.”
Supplement 25
GI-1781.001,
122 J2 System activation indicator on fire control panel is "OFF.”
Supplement 25
GI-1781.001,
123 J3 Pipe manifolds are painted & pipe is not subject to external loading
Supplement 25
7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
GI-1781.001,
124 J4 Pipe hangers are not damaged, loose, or missing.
Supplement 25
GI-1781.001,
125 J5 Manual discharge & abort switches are in normal standby mode.
Supplement 25
GI-1781.001,
126 J6 Cylinder transfer key is set to primary.
Supplement 25
GI-1781.001,
127 J7 Cylinder brackets are firmly attached.
Supplement 25
Solenoid & pneumatic discharge valves are firmly attached to the cylinder GI-1781.001,
128 J8
head. Supplement 25
GI-1781.001,
129 J9 Discharge nozzles are unobstructed & blow-off caps are in place
Supplement 25
GI-1781.001,
130 J10 Discharge flexible hoses are in good condition.
Supplement 25
GI-1781.001,
131 J11 Cylinder(s) are fully charged to correct pressure (ambient temp)
Supplement 25
GI-1781.001,
132 J12 Manual & automatic actuating devices are operational
Supplement 25
GI-1781.001,
133 J13 Manual & automatic devices meet mfg's recommendations.
Supplement 25
GI-1781.001,
134 J14 As applicable, pneumatic type CO2 cartridge disc is intact.
Supplement 25
GI-1781.001,
135 J15 Hose assemblies have valid hydrotest date (every five years).
Supplement 25
GI-1781.001,
136 J16 Cylinders have valid hydrostatic test date (every five years).
Supplement 25
GI-1781.001,
137 J17 Safety/warning signs are posted identifying the protected area.
Supplement 25
GI-1781.001,
138 J18 Operating instructions are posted and legible.
Supplement 25
GI-1781.001,
139 J19 Protected space has not been altered.
Supplement 25
GI-1781.001,
140 J20 Inspection tag and logbook are signed and updated.
Supplement 25
7 ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
8 No.
REMARKS:
142
160 *Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED