Professional Documents
Culture Documents
SAUDI ARAMCO ID/PIEU-30-September-2019 - REV.2019.09.00 (Standards Cutoff - Sep 30, 2019) Rev 47 30-Sep-19
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
LV Panelboard - Industrial Panelboard (≤400A) Material
SAIC-P-3859 15-Dec-19 ELECT
Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A. DOCUMENT REVIEW
B. GENERAL REQUIREMENT
Documented Control System shall be implemented for all Saudi Aramco Schedule Q
B2
supplied material and equipment. Att. lV Sec.5
C. MATERIAL INSPECTION
Schedule G
C3 LV Panelboard - Industrial Panelboard (≤400A) shall be new and unused.
Sec. 2.1
Check that the Contractor or it's Saudi Aramco approved third party
Schedule Q
inspector performed the quality activities at the supplier and sub-supplier
C5 Att. llI
locations as required by the inspection level assigned for the materials
Sec. 3.2
and equipment identified in SAEP-1151, Engineering Procedure.
Certifications:
Circuit Breaker Listing / Labeling - All main, feeder and branch circuit 16-SAMSS-518
C6
breakers and enclosures shall be third-party tested, and listed or labeled Sec 5.2
as meeting the requirements of UL standard 489.
16-SAMSS-518
C7 Panelboards shall fully comply with NEMA PB1 and UL67.
Sec 5.2
SAES-P-116
C12 Panelboards used in industrial facilities shall be rated 400A or less.
Sec. 15.3
Standard ratings of main bus shall be 100, 110, 125, 150, 175, 200, 225, 16-SAMSS-518
C13
250, 300, 350 & 400 amperes. (NEMA PB 1, Sec. 2.10.1) Sec. 7
16-SAMSS-518
The minimum wire-bending space at terminals shall be as shown in table
C14
16.1. (UL67, Sec. 16.1)
Sec. 5.2
16-SAMSS-518
The minimum width of wire gutter and wire-bending space shall be as
C15
shown in Table 16.2. (UL 67, Sec. 16.2)
Sec. 5.2
16-SAMSS-518
The ampacity of some of the more common size bus bars shall be as
C16
shown in Table 11.2. (UL 67, Sec. 11.3)
Sec. 5.2
The frequency rating of AC panelboards shall be 50, 60, or 50/60 Hz. 16-SAMSS-518
C20
(NEMA PB1, Sec.3.3) Sec.5.2
SAES-P-100
C29 Only secondary-selective switchgear shall be used to feed critical loads.
Sec. 5.5
Exception:
The circuit breakers installed shall be of the proper type and rating. SAES-P-100
C33
(NFPA 70, NEC 240.86) Sec. 5.5
If the breaker size is not specified within the purchasing documents, 16-SAMSS-518
C35
breakers shall have a minimum trip rating of 20 Amp. Sec. 12.1
Breakers operating at greater than 240 Volts shall be equipped with
padlockable lock-off devices.
16-SAMSS-518
C36
Sec. 12.2
12.2 (Addition) to NEMA PB 1 and UL 67: Breakers operating at greater
than 240 Volts shall be equipped with padlockable lock-off devices.
Circuit Breakers Types - Tandem, twin, or half-size breakers shall not be
used.
16-SAMSS-518
C37
Sec. 12.3
(Addition) to NEMA PB 1 and UL 67: Tandem, twin, or half-size breakers
shall not be used.
The circuit directory shall be located on the face or back of the panel door. SAES-P-100
C38
(NFPA 70, NEC 408.4). Sec. 5.2
16-SAMSS-518
The specific application of indoor and outdoor type enclosure shall be as
C39
shown in NEMA 250, Table 1 and 2. (NEMA 250, Sec. 2)
Sec. 5.2
16-SAMSS-518
The size of knockouts for panelboards shall be as shown in Table 3.
C41
(NEMA 250 Sec.3)
Sec. 5.2
Enclosures rated Type 3, 4 or 4X per NEMA 250 shall be equipped with 16-SAMSS-518
C47
Type 300 Series stainless steel hardware. Sec. 9.2.3
A filler plate shall provided to close an opening that would otherwise be 16-SAMSS-518
C48 closed by subsequent installation of a circuit breaker other device. ( UL
67, Sec 10) Sec. 5.2
The neutral busbar shall have an ampacity not less than that of the other
busbars, except that the neutral in a 3-wire d-c system or single-phase a-c 16-SAMSS-518
C50 panelboard or in a 3-phase, 4 wire panelboard, rated more than 200
amperes , shall not be have an ampacity less than 200 amperes . Sec. 5.2
(UL 67 , Sec. 11.6.1)
A neutral busbar intended for use in a panelboard with increased neutral 16-SAMSS-518
C51 ampacity shall have an ampacity of 125%, 150%, 175%, or 200% of the
other phase bars. (UL 67, Sec 11.6.2) Sec. 5.2
When the main neutral terminal is located at the electrical center of the
main neutral bus bar, the ampacity of each half of the bus bar shall not be
less than half the values specified in Section 11.6.1 above. The electrical 16-SAMSS-518
C52 center is identified as the point at which the neutral current to one side of
the bus bar is equal to the other side, taking into considerations the total Sec. 5.2
number of terminals located in the neutral bus bar and the current
associated with each. (UL 67, Sec. 11.6.3)
16-SAMSS-518
Lugs shall be UL listed to accept solid or stranded copper cables. Lugs
C53
shall be bolted in place.
Sec. 5.2
16-SAMSS-518
Panelboard shall be deadfront unless it is intended for use where it will be
C55
accessible only to qualified personnel. (UL 67, Sec 9.1.3)
The main terminal may be in the form of a main terminal kit if the Sec. 5.2
panelboard is specifically designed for use interchangeably either with
those terminals or with a main circuit breaker. The main terminal kit may
consist of individual terminals of may be an assembly consisting of:
a) Terminals
16-SAMSS-518
C56
b) Bus bars that provide connection between those
Sec. 5.2
terminals and the main bus bars of the panelboard, and
c) A mounting means for those components.
The number of individual branch circuit neutral terminals shall not be less 16-SAMSS-518
C58 than 75 percent of the total number of poles provided for in the
panelboard. (UL 67, Sec.12.3.11) Sec. 5.2
All conductors shall be copper, silver or alloys of these materials with the
following exceptions: (1)
Parts which are internal to a pre-manufactured device
16-SAMSS-518
C59 (e.g., internals circuit breaker).
Sec. 10.1
( 2 ) Connectors supplied as integral parts or components of
manufactured equipment such as molded case circuit breakers provided
the connectors are approved for copper conductors.
Plating of the copper, silver or copper/silver alloy base conductor material 16-SAMSS-518
C60
is acceptable. Sec. 10.1.3
The main circuit bus system shall be of rigid material (i.e., cable or flexible 16-SAMSS-518
C61
conductors shall not be used). Sec. 10.2
16-SAMSS-518
C62 A ground bus shall be provided within the panelboard.
Sec. 11
White Nameplates with black lettering shall be provided to identify the 16-SAMSS-518
C63
panelboard with the tag number indicated within Data Schedule 1. Sec. 13
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule G -- Materials, Tools and Equipment (MP LSTK & LSPB Pro Forma), Contract Specific
2. Schedule Q -- Quality Requirements (MP LSTK & LSPB Pro Forma), Contract Specific
3. SAES-P-100 -- Basic Power System Design Criteria, 01 January 2018
4. SAES-P-116 -- Switchgear and Control Equipment, 8 August 2017
5. NEMA PB1 -- Panelboards, 2011
6. UL 67 -- Panelboards, 23 May 2008
7. NEMA 250 -- Enclosures for Electrical Equipment (1000 Volts Maximum), 2003
8. UL 489/NEMA AB 1 -- Molded-Case Circuit Breakers, Molded Case Switches, and Circuit-Breaker Enclosures, 2002
9. NFPA 70 -- National Electrical Code, 2017
10. SAES-P-104 - Wiring Methods and Materials, 01 January 2018
11.16-SAMSS-518 -- Low Voltage Panelboards, 22 August 2019
12. NEMA AB3 -- Molded Case Circuit Breakers and their Application - 2013
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products or
services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
manufacturer indicates compliance with appropriate standards or performance in a specified manner.