SAUDI ARAMCO INSPECTION CHECKLIST
Cable Tray, Metallic Tray Systems - Material Receiving SAIC-P-3302 3-Jul-18 ELECT
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A. General Requirements

Schedule G
A1 Electrical materials shall be new and unused.
Sec. 2.1

Electrical materials shall be in accordance with the Saudi


Schedule G
A2 Aramco-approved project-specific design drawings, diagrams,
Sec. 2.1
schedules, lists, databases, and associated documents.

Schedule Q
A3 Electrical materials shall be free of damage.
Att. lV, Sec.3.3

Electrical materials shall conform to all applicable requirements,


Schedule Q
A4 standards, and specifications prior to release to be used as part of the
Att. lV, Sec.3.3
work.

Electrical materials shall be identified by using tags, stamps, color coding,


Schedule Q
A5 stencils or labels. The location and method of identification shall not affect
Att. lV, Sec.4.2
the function or quality of the materials.

Electrical materials shall be traceable from the manufacturer and supplier


Schedule Q
A6 through delivery, storage, fabrication, erection, installation, repair,
Att. lV, Sec.4.3
modification and use.

B. Specific Requirements for Cable Tray

Refer to Saudi Aramco SAP system for approved cable tray


manufacturers
SAES-P-101
B1
Sec. 6.1

Cable tray material shall be:


SAES-P-104
B2 a) copper-free aluminum (aluminum with a maximum of 0.4% copper)
Sec. 9.1
b) ladder type (two side-rail)

Aluminum cable tray shall:


a) be designed, manufactured, rated, and tested in accordance with
NEMA VE-1
b) tested to method A (Loading to Destruction) for determining the rated SAES-P-104
B3
load capacity Sec. 9.2
c) have minimum individual rung load capacity of 90 kg
d) have manufacturer test report at cable tray material receiving area
e) have flanged covers of minimum thickness of 1 mm