EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A. Material Requirements
Schedule G
A1 Electrical materials shall be new and unused.
Sec. 2
Schedule Q
A3 Electrical materials shall be free of damage. Att. lV
Sec. 3
Electrical materials shall conform to all applicable requirements, Schedule Q
A4 standards, and specifications prior to release to be used as part of the Att. lV
work. Sec. 3
Electrical materials shall be identified by using tags, stamps, color Schedule Q
A5 coding, stencils or labels. The location and method of identification shall Att. lV
not affect the function or quality of the materials. Sec. 4
Electrical materials shall be traceable from the manufacturer and supplier Schedule Q
A6 through delivery, storage, fabrication, erection, installation, repair, Att. lV
modification and use. Sec. 4
The ground rod shall be copper or copper jacketed steel or galvanized SAES-P-111
A7
steel. Sec. 5.2 a
Check that the rod is free from nonconductive coatings such as paint or
SAES-P-111
A8 enamel prior to being driven to the ground.
Sec. 4.1
[NEC 250.53(A)]
SAES-P-111
A9 The ground rod shall not be less than 2.44 m (8 ft) long.
Sec. 5.2 c
Page 1 of 4
The ground rod shall not be less than 1.83 m (6 ft) from any other
SAES-P-111
B2 electrode of another grounding system.
Sec. 4.1
[NEC 250.53(B)]
Page 2 of 4
South Dhahran Home Ownership Project(SDHOP) Rev 0
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Grounding - GES - Copper, Copper-Clad (Jacketed) Steel,
SAIC-P-3711 ELECT-
Galvanized Steel Rod - Installation
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
SOUTH DHARAN HOMEOWERSHIP PROJECT BRANCH OF SINOHYDRO
28-00014-0002
ELEMENTARY SCHOOLS , KG AND SPECIAL SCHOOL CORPORATION COMPANY LTD.
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
The ground rod shall be installed such that at least 2.44 m (8 ft)
SAES-P-111
B3 of length is in contact with the soil.
Sec. 4.1
[NEC 250.53(G)]
The ground rod shall be driven to a depth of not less than 2.44 m
SAES-P-111
B4 (8 ft).
Sec. 4.1
[NEC 250.53(G)]
The upper end of the electrode shall be flush with or below ground level
unless the above ground end and the grounding electrode conductor SAES-P-111
B7
attachment are protected against physical damage. Sec. 4.1
[NEC 250.53(G)]
Soil resistivity of backfill material used for ground rods shall be the same SAES-P-111
B8
as or less than that of the surrounding soil. Sec. 4.1
C. Pre-Commissioning Requirements
The ground resistance of made electrodes (ground rods) used for system
grounding shall not exceed 1 ohm for solidly grounded systems above SAES-P-111
C4
600 V, 5 ohms for resistance grounded systems above 600V and 5 ohms Sec. 8.3
for systems under 600 V.
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule G -- Materials, Tools and Equipment (MP LSTK & LSPB Pro Forma, Revised 3/06)
2. Schedule Q -- Quality Requirements (MP LSTK & LSPB Pro Forma, Revised 2/08)
Page 3 of 4
South Dhahran Home Ownership Project(SDHOP) Rev 0
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Grounding - GES - Copper, Copper-Clad (Jacketed) Steel,
SAIC-P-3711 ELECT-
Galvanized Steel Rod - Installation
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
SOUTH DHARAN HOMEOWERSHIP PROJECT BRANCH OF SINOHYDRO
28-00014-0002
ELEMENTARY SCHOOLS , KG AND SPECIAL SCHOOL CORPORATION COMPANY LTD.
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
3. NFPA 70 -- National Electrical Code (NEC), 2008 Edition
4. SAES-P-111 -- Grounding, 16 July 2006
5. UL 467 -- UL Standard for Grounding and Bonding Equipment, 21 September, 2007
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing
states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified
purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer
indicates compliance with appropriate standards or performance in a specified manner.