00 30-Nov-18
DUCT-BANK / CONDUIT ID NUMBERS DUCT BANK DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
GRS Conduit and Fittings Listing: All GRS conduit, factory GRS elbows,
GRS couplings, and associated GRS fittings (i.e., uncoated and PVC-
SAES-P-104
A5 coated) shall be third-party listed as meeting the requirements of UL
Sec. 4.1
standards (UL 6, 514A, 514B, and 886 as applicable, or approved equal
standards). [NFPA 70 NEC 344.6 and Annex A]
GRS Conduit Fittings: Conduit fittings for rigid steel conduit and liquid-tight
flexible metal conduit used above ground in severe corrosive
environments shall be as specified in B2 & B3 above (SAES-P-104 Sec.
8.9.1) and in addition, shall be protected by one of the following methods:
(a) Factory-coating with PVC (minimum thickness of PVC: 40 mils) per
NEMA RN 1
SAES-P-104
B3 (b) Field-coating prior to installation in accordance with SAES-H-101
Sec. 8.9.2
APCS-22 (offshore), or APCS-26 (onshore), or
(c) By heat-shrinkable tubes or wrap-arounds, where the geometric
configuration permits it.
Exception: Red leaded brass or silicon bronze conduit fittings
may be used as an alternative to the above in severe corrosive
environments(only above ground).
GRS Conduit Fittings: Conduit fittings for direct buried PVC coated rigid SAES-P-104
B4
steel conduit shall be factory PVC coated. Sec. 8.9.3
Schedule G
B5 New and Unused - Electrical materials shall be new and unused.
Sec. 2
Schedule Q
B7 Free of Damage - Electrical materials shall be free of damage.
Att. lV, Sec. 3.3
GRS Conduit Minimum Size: The minimum conduit size shall be ¾ inch or SAES-P-104
C2
equivalent in metric size, except for prefabricated skids. Sec. 8.6
GRS Conduit Maximum Size: Conduit larger than 155 mm (6 inch) trade SAES-P-104
C3
size shall not be used. [NFPA 70 NEC 344.20(B)] Sec. 4.1
GRS Conduit Threading: Running threads shall not be used on conduit for SAES-P-104
D1
connection at couplings. [NFPA 70 NEC Art. 344.42(B)] Sec. 4.1
GRS Conduit Thread Protection: Thread protectors shall be used on the SAES-P-104
D2
exposed threads of the coated conduit. [NEMA RN 1 Sec 2.4] Sec. 8
GRS Conduit Threading: Conduit and threaded conduit fittings shall have SAES-P-104
D3
tapered NPT threads in accordance with ANSI/ASME B1.20.1. Sec. 8.7
GRS Conduit Threading: The number of threads per inch (threads per
25.4 mm), and the length of the threaded portion at each
end of each length of conduit, nipple and elbow shall be as indicated in SAES-P-104
D4
Table 1, and shall conform to ANSI/ASME B1.20.1. The perfect thread Sec. 8
shall be tapered for its entire length, and the taper shall be 1 in 16.
[ANSI/NEMA C80.1 Sec. 6.6]
GRS Conduit Reaming: All cut ends shall be reamed or otherwise finished SAES-P-104
D6
to remove rough edges. [NFPA 70 NEC 344.28] Sec. 4.1
GRS Conduit Threading: Field cut conduit threads shall be coated with a SAES-P-104
D7
zinc rich protective coating. Sec. 8.8
GRS Conduit Fitting Threads: Threads of plugs, junction boxes and other
fittings shall be lightly lubricated with a rust preventive grease such as SAES-P-104
D8
Crouse Hinds thread lubricant (1000405418) or High Purity Goop Sec. 8.9.4
(1000174895) before assembly.
E. Finishing and Identification Requirements - Galvanized Rigid Steel (GRS) Conduit and Fittings
GRS Conduit Marking: Nipples with unthreaded areas less than 2 inches
(51 mm) long may be marked in accordance with the requirements of SAES-P-104
E2
9.1.1 on the smallest unit of shipping carton. Sec. 8
[ANSI/NEMA C80.1 Sec. 9.1.2]
GRS Interior Surface: The interior surface shall be free from injurious SAES-P-104
E5
defects. [ANSI/NEMA C80.1 Sec. 5.3] Sec. 8
GRS Conduit Coating: The conduit shall be adequately cleaned before the
application of the protective coating. The cleaning process shall leave the
SAES-P-104
E6 exterior and interior surfaces of the conduit in such a condition that the
Sec. 8
protective coating shall be smooth and adhere firmly. [ANSI/NEMA C80.1
Sec. 5.5]
GRS Conduit Finish: The exterior and interior surfaces shall be free from
slivers, burrs, scale, or other similar injurious defects, and coverage of the SAES-P-104
E9
coating shall be complete. Sec. 8
[ANSI/NEMA C80.1 Sec. 8.2 and 5.3]
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract)
2. Schedule Q - Quality Requirements (Pro Forma Contract)
ATTACHMENT(S):
1. Attachment 1:
Table 2 - Dimensions and Weights for Rigid Steel ConduitA - ANSI/NEMA C80.1
Table 2, Chapter 9 - Radius of Conduit and Tubing Bends - NEC - 2011
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products or
services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
manufacturer indicates compliance with appropriate standards or performance in a specified manner.
Attachment - 1
Table 2 - Dimensions and Weights for Rigid Steel ConduitA - ANSI/NEMA C80.1