Abstract
Electric energy meter wiring error variety, detection method and circuit can only detect some kinds
of wrong wiring at present, as the current transformer and current detection unit terminal short-circuit
characteristics of conventional methods in existence, not take out stitches under the premise of not
achieving detection. Based on this, this paper puts forward a step detection method, detection circuit of
voltage and current lines one by one through right off and polarity of current, gradually show every junction
point junction and the fault point. Through the Multisim software simulation, and developed a set of wire
detecting device, simulation and experimental results prove that the method is correct. Compared with
conventional methods, can be more comprehensive and faster connection detection fault location.
Keywords: electric energy meter; wiring, detection, fault location, step by step
Copyright © 2015 Institute of Advanced Engineering and Science. All rights reserved.
1. Introduction
The smart grid and new energy [1-2] develop with the development of the society. The
accuracy of the power of information collection equipment is one of the significant factors of
fishery economy growth. The correct connection of electric energy metering device is the
necessary condition to guarantee the accuracy of the electric energy meter[3], with a new type
of meter and the new measuring means constantly updated, the way of power theft is
developing to a more subtle and more technological trend. Thus to ensure the accuracy of
electric energy meter and device is particularly important.
There are many kinds of wrong connection modes of watt-hour meter, for example,
there are 287 kinds of wrong connection modes to three-phase three -components, and 575
kinds of wrong connection modes to three-phase three-wire watt-hour meter [4]. At present
there are two common testing methods [5-12]. One method is to detect each of the lines item by
item, when there is no electricity and no loads for electric energy meter.However, because of
the electrical interference and short circuit characteristics of the electric energy meter wiring
circuit, the only way to detect the false connection is to rip out the wiring circuit. The other
method to detect error-wiring is suitable for the electric energy meter having been put into use,
which means there is electricity and loads for electric energy meter.This kind of method can only
detect a type of wrong wiring, which are complex and are not universal. In addition, this method
exist some safety problems.
Based on the disadvantages of the current methods, this paper analyzes the structure
and principle of electric energy meter and proposes a novel detection method of electric energy
meter. This novel method can detect all the wrong wiring in electric energy meter quickly, and
there is no need to rip out the existing circuit.Besides, this method can accomplish the fault
detection without electricity and loads.
Received January 4, 2015; Revised March 2, 2015; Accepted March 18, 2015
TELKOMNIKA ISSN: 2302-4046 91
stitch, it unable to detect the wrong wiring by measuring in the state of on and off. The positive
and negative terminals of current transformer, the positive and negative terminals of current test
unit are in short circuited state.
There are lots of electric energy meter device wiring errors including terminal short
circuit, so on the premise of not removing stitch, these errors bring certain difficulty to detection,
chose the process of three-phrase four-wire accessed by current transformer and voltage
transformer to introduce. As shown in Figure 2 there are 10 routes between two terminals about
3.62 million kinds of attachment, but only the one which is shown in the picture is correct. In
summary, the way of conventional detecting is screening each route, detecting the electrical
relationship between terminals can complicate the process of detection, and it requires higher
skill of people [13, 14]. At the same time, when there is short circuit, the detecting results can’t
reflect the actual state of wiring.
Study in Step by Step Electric Energy Meter Connection Detection Method (Qing Zhiming)
92 ISSN: 2302-4046
Through the above steps 1 and 2, it can detect to the common wrong connection type,
through the third step determining the current terminal polarity. To make up for the pick up
against the wrong type of polarity, eventually achieve the goal of complete detection.
Figure 4. Step 1 and step 2 test terminal and the attachment relations
Concrete realization principle is shown in Figure 5, the test system uses 555 timer and
192 counter to produce two sets of the pulse signal which has the same frequency different
width, the wide pulse generates two groups of test signal through decoder chip and test probe,
one group drives the LED of sender terminal directly, another group signal drives the LED of
receiving terminal after going through the measuring terminal. Compare the two sets of LED
lights, the fault point and the test process can be displayed clearly, at the same time, the
synchronous narrow pulse control alarm circuit gives the corresponding control signal, realizes
switching between automatic alarm and manual alarm.
For example, first output a wide pulse, and output 00000001 after counting and
decoding, divided into two groups, one group lights up the LED Ua, the rest LED lights of the
sender are not bright which means now is detecting the connection of Ua terminal, another
group lights up the LED after going through the input and output of the terminal under test, if the
connection is correct, the receiver Ua will be lighted up. The system will output 00000010 after
counting and decoding when the second pulse comes automatically to test the Ub terminal. If all
the receiving LED are not lighted which means disconnection or poor contact, the output fault
signal changes to manual reroute model, if Ub is lighted, it means Ua and Ub is connected, the
output alarm signal changes to manual reroute model. In manual reroute model, signal is not
produced by 555 but the switch signal and artificial button.
Synchronous narrow pulse: Because there may be some delay when the two testing
signal jump, so as to prevent the alarm module miscalculation, use the narrow pulse to filter
detection signal, namely only chose the middle part of the stable signal for testing and alarming.
Alarm module: The two signals input to the alarm module, if they are the same, it means
right, otherwise means wrong and alarm. The alarm signal outputs only when narrow pulse is
high level, it lights the alarm LED and prompts changing lines and cuts off the output signal of
555 then access the artificial input pulse into the manual model.
Study in Step by Step Electric Energy Meter Connection Detection Method (Qing Zhiming)
94 ISSN: 2302-4046
The test principle is shown in Figure 7, using crrent loop decision method to determine,
input test DC signal on both ends of current transformer, install the current sensor in the test
circuit, testing the direction of current, Op-amp and the thyristor amplify and latch the signal, if
correct polarity and current direction is positive, the LED light, if the polarity is correct, current
direction is positive, the LED lights, if the polarity is wrong, the current direction is negative,
alarm the indicator light, manually enter the reroute model. Through three times detection, can
complete the ABC three phase current terminal polarity decision, output "test is successful,
trouble-free" signal after complete.
Table 1. Accuracy comparison table after using the new type instrument
Validation Multimeter Experience to judge Accuracy of new instrument
company accuracy( %) accuracy( %) ( %)
NA company 90 50 100
JB company 80 40 100
WZ company Unused 40 100
TL company Unused 30 100
BB company Unused 20 100
DJ company Unused 30 100
As shown in Table 1, each unit of the employees in after the completion of the
installation of electric energy metering device, with a new type of instrument wiring check
accuracy reached 100%, intermediate and above staff members are able to operate properly.
Table 2. Time comparison table after using the new type instrument
Validation Multimeter Experience to judge New instrument
company ( Min) ( Min) ( Min)
NA company 25 10 <4
JB company 25 12 <4
WZ company 30 15 <5
TL company 35 15 <4
BB company 30 14 <5
DJ company 35 15 <5
As shown in Table 2, the time shortened to average less than 5 minutes after using the
new instruments to determine.
5. Conclusion
The step test in this paper, it’s main contribution is:
1) Simplifies the process of electric energy metering device wiring detection effectively,
realizes the fault accurate positioning, improves the detection efficiency and reduces the
dependence on testing staff skills. By analyzing the connection test difficulty, puts forward the
current loop direction decision to implement the polarity decision, without stitch line, make up for
the disadvantages of the conventional method can't detect such failure. Simulation and
experimental prototype data show that this method is aimed at all kinds of common errors wiring
detection and d the accuracy was 100%, the testing time is shorten by 5 minutes compared with
the common method.
2) This method can accomplish the fault detection without electricity and loads, which
can reduce the safty potential when there is some fault connection existing in the circuit.
3) Step test is successfully and effectively used in electric energy metering device
wiring tests, and has the certain theory reference significance to other electronic power
equipment in wiring detection the precondition of no power or no removing stitches.
References
[1] Awang Jusoh, Tole Sutikno, Tan Kar Guan, Saad Mekhilef. A Review on Favourable Maximum Power
Point Tracking Systems in Solar Energy Application. TELKOMNIKA Indonesian Journal of Electrical
Engineering. 2014; 12(1): 6-12.
[2] Huang Zhiwu, Wang Shuxia. Based on Fuzzy Hybrid Inverter Technology Solar Energy Application
Research. TELKOMNIKA Indonesian Journal of Electrical Engineering. 2014; 12(4): 2636-2644.
[3] Shtargot J. Advanced Power-Line Monitoring Requires a High-Performance Simultaneous-Sampling
ADC. In MAXIM Application Note. 2008: 42-81
[4] M Zhou, L Liu. Development of power metering device detection system based on the data of power
load management system. Information System Engineering. 2009: 49-51.
[5] JI X X. Research and analysis of intelligent watt-hour meter common faults. Disertation. North China
Electric Power University; 2012.
[6] MA L. The wrong wiring of electric energy metering device. Science and technology information. 2012;
11.
[7] ZHOU Y F. A typical wrong wiring analysis of electric energy metering device. Sichuan electric power
Study in Step by Step Electric Energy Meter Connection Detection Method (Qing Zhiming)
96 ISSN: 2302-4046