Pipe Concrete Column Design Based on ACI 318-14
ANALYSIS
2 0.85 f '
C '
o , E c 57 f C , E s 29000ksi
Ec
900
2
800
0.85 f
'
C
2 c c , for 0 c o
f C o o
700 '
0.85 f C , for c o
600
s E s , for s y
f Pn (k) f
500 S
f , for s y
y
400 f Pn (kips) f Mn (ft-kips)
300 AT AXIAL LOAD ONLY 819 0
AT MAXIMUM LOAD 819 70
200
AT 0 % TENSION 643 148
100 AT 25 % TENSION 533 180
0 AT 50 % TENSION 444 197
0 50 100 150 200 250 AT e t = 0.002 318 206
f Mn (ft-k) AT BALANCED CONDITION 313 208
AT e t = 0.005 146 229
AT FLEXURE ONLY 0 164
CHECK FLEXURAL & AXIAL CAPACITY
f Pmax =0.85 f [ 0.85 fc' (Ag - Ast) + fy Ast] = 819.14 kips., (at max axial load, ACI 318-14 22.4)
where f = 0.65 (ACI 318-14 21.2) > Pu [Satisfactory]
Ag = 286 in2. Ast = 4.80 in2.
a = Cbb1 = 8 in (at balanced strain condition, ACI 21.2.2)
0.75 + ( et - 0.002 ) (50), for Spiral
f= = 0.656 (ACI 318-14 21.2)
0.65 + ( et - 0.002 ) (250 / 3), for Ties