REBOUND HAMMER TEST - SUMMARY (WHARF - BEAMS)


PROJECT : ABOITIZ CONSTRUCTION INC. - STRUCTURAL ASSESSMENT AND EVALUATION OF LADATE TESTE07/12/2022 - 10/25/2022
LOCATION : INGORE, ILO-ILO CITY SHEET NO. : 1 of 4

WHARF AVERAGE COMPRESSIVE STRENGTH PER LOCATION


AVERAGE WHARF AVERAGE COMPRESSIVE STRENGTH PER LOCATION
AVERAGE
READING LOCATION : SUPPORT MIDSPAN SUPPORT PER BEAM READING LOCATION : SUPPORT MIDSPAN SUPPORT PER BEAM
MARK/GRIDLINE MARK/GRIDLINE
BEAM D-1-2 34.8 MPa 44.5 MPa 21.6 MPa 33.6 MPa BEAM D-12-13 31.2 MPa 36.3 MPa 30.6 MPa 32.7 MPa
BEAM F-G-2-3 41.0 MPa 31.0 MPa 31.3 MPa 34.4 MPa BEAM F-G-13-14 27.7 MPa 23.6 MPa 24.4 MPa 25.2 MPa
BEAM D-E-3 26.2 MPa 28.9 MPa 29.1 MPa 28.1 MPa BEAM C-D-14 27.7 MPa 23.6 MPa 24.4 MPa 25.2 MPa
BEAM B-C-4 27.4 MPa 32.1 MPa 27.7 MPa 29.1 MPa BEAM E-F-15 22.8 MPa 27.4 MPa 21.3 MPa 23.8 MPa
BEAM D-E-5 26.0 MPa 21.7 MPa 20.5 MPa 22.7 MPa BEAM C-15-16 20.1 MPa 20.1 MPa 18.9 MPa 19.7 MPa
BEAM F-G-6-7 28.8 MPa 25.2 MPa 23.1 MPa 25.7 MPa BEAM E-F-17 20.1 MPa 20.1 MPa 18.9 MPa 19.7 MPa
BEAM C-D-7 26.2 MPa 28.5 MPa 20.5 MPa 25.1 MPa BEAM D-18-19 17.2 MPa 18.8 MPa 15.0 MPa 17.0 MPa
BEAM E-F-8 24.2 MPa 23.1 MPa 21.2 MPa 22.9 MPa BEAM D-19-20 20.6 MPa 19.7 MPa 18.5 MPa 19.6 MPa
BEAM B-C-9 31.4 MPa 25.9 MPa 24.7 MPa 27.4 MPa BEAM E-F-20 20.4 MPa 21.8 MPa 20.6 MPa 20.9 MPa
BEAM D-E-10 28.9 MPa 29.6 MPa 29.0 MPa 29.2 MPa BEAM C-D-21 16.9 MPa 17.9 MPa 16.9 MPa 17.2 MPa
BEAM E-F-11 34.8 MPa 36.3 MPa 38.8 MPa 36.7 MPa BEAM B-22-23 22.4 MPa 23.0 MPa 23.0 MPa 22.8 MPa
BEAM B-C-12 29.3 MPa 31.7 MPa 19.7 MPa 26.9 MPa BEAM E-F-22 21.6 MPa 22.5 MPa 21.6 MPa 21.9 MPa
REMARKS : Test conducted in accordance with ASTM Standard

Prepared by : Noted by :

PATRICIA S. CALO MARTIN A. VILLAR


Structural & Engineering Staff Structural & Engineering Manager
CONCRETE RESTORATION AND REPAIR TECHNOLOGY (CORRTECH), INC.
2/F CORRTECH Compound, General Aviation Road, Bankal, Lapu-lapu City, Cebu, Philippines, 6015
Telephone No. (032) 239-1941 | Telefax (032) 239-2459
Email: info@corrtechinc.net | Website: www.corrtechinc.net

PCAB LICENSE A # 34492

REBOUND HAMMER TEST - SUMMARY (WHARF - BEAMS)


PROJECT : ABOITIZ CONSTRUCTION INC. - STRUCTURAL ASSESSMENT AND EVALUATION OF LADATE TESTE07/12/2022 - 10/25/2022
LOCATION : INGORE, ILO-ILO CITY SHEET NO. : 2 of 4

WHARF AVERAGE COMPRESSIVE STRENGTH PER LOCATION


AVERAGE WHARF AVERAGE COMPRESSIVE STRENGTH PER LOCATION
AVERAGE
READING LOCATION : SUPPORT MIDSPAN SUPPORT PER BEAM READING LOCATION : SUPPORT MIDSPAN SUPPORT PER BEAM
MARK/GRIDLINE MARK/GRIDLINE
BEAM C-23-24 39.9 MPa 36.8 MPa 35.8 MPa 37.5 MPa BEAM B-C-41 28.3 MPa 27.8 MPa 27.0 MPa 27.7 MPa
BEAM F-24-25 24.7 MPa 23.0 MPa 23.4 MPa 23.7 MPa BEAM D-E-42 29.1 MPa 27.2 MPa 28.9 MPa 28.4 MPa
BEAM B-C-25 25.0 MPa 22.0 MPa 24.9 MPa 24.0 MPa BEAM C-D-43 28.3 MPa 28.2 MPa 26.8 MPa 27.8 MPa
BEAM B-C-26 28.5 MPa 33.5 MPa 25.6 MPa 29.2 MPa BEAM B-C-44 23.9 MPa 23.1 MPa 25.5 MPa 24.2 MPa
BEAM C-27-28 25.5 MPa 27.1 MPa 26.0 MPa 26.2 MPa BEAM E-F-45 31.3 MPa 33.1 MPa 29.8 MPa 31.4 MPa
BEAM D-E-28 27.1 MPa 25.9 MPa 25.3 MPa 26.1 MPa BEAM A-B-46 27.7 MPa 27.7 MPa 28.6 MPa 28.0 MPa
BEAM B-C-29 26.2 MPa 24.4 MPa 24.9 MPa 25.2 MPa BEAM C-D-47 24.2 MPa 23.1 MPa 25.0 MPa 24.1 MPa
BEAM C-D-31 24.1 MPa 23.9 MPa 22.7 MPa 23.6 MPa BEAM D-48-49 32.3 MPa 29.8 MPa 30.7 MPa 30.9 MPa
BEAM D-E-32 26.1 MPa 24.1 MPa 23.6 MPa 24.6 MPa BEAM C-49-50 29.3 MPa 30.8 MPa 27.5 MPa 29.2 MPa
BEAM E-F-33 26.1 MPa 25.5 MPa 24.2 MPa 25.3 MPa BEAM F-G-50-51 24.8 MPa 26.3 MPa 27.8 MPa 26.3 MPa
BEAM C-D-34 39.5 MPa 39.0 MPa 38.9 MPa 39.1 MPa BEAM D-E-51 31.4 MPa 29.5 MPa 30.4 MPa 30.5 MPa
BEAM B-C-35 24.4 MPa 22.4 MPa 24.2 MPa 23.7 MPa MPa MPa MPa ### MPa
BEAM C-D-36 29.2 MPa 27.5 MPa 26.8 MPa 27.8 MPa MPa MPa MPa ### MPa
BEAM E-36-37 29.0 MPa 30.3 MPa 25.3 MPa 28.2 MPa MPa MPa MPa ### MPa
BEAM E-F 38 26.8 MPa 25.1 MPa 24.9 MPa 25.6 MPa MPa MPa MPa ### MPa
BEAM B-C-39 28.5 MPa 28.1 MPa 25.0 MPa 27.2 MPa MPa MPa MPa ### MPa
BEAM F-G-39-40 36.9 MPa 35.4 MPa 33.1 MPa 35.1 MPa MPa MPa MPa ### MPa
BEAM C-40-41 24.9 MPa 23.6 MPa 24.3 MPa 24.3 MPa MPa MPa MPa ### MPa
REMARKS : Test conducted in accordance with ASTM Standard

Prepared by : Noted by :

PATRICIA S. CALO MARTIN A. VILLAR


Structural & Engineering Staff Structural & Engineering Manager
CONCRETE RESTORATION AND REPAIR TECHNOLOGY (CORRTECH), INC.
2/F CORRTECH Compound, General Aviation Road, Bankal, Lapu-lapu City, Cebu, Philippines, 6015
Telephone No. (032) 239-1941 | Telefax (032) 239-2459
Email: info@corrtechinc.net | Website: www.corrtechinc.net

PCAB LICENSE A # 34492

REBOUND HAMMER TEST - SUMMARY ( WHARF & WHARF APPROACH - SLAB)


PROJECT : PIER INTEGRITY ASSESSMENT (STRUCTURAL ASSESSMENT AND INSPECTION OF MGC
DATE TESTE01/18/2021 - 3/19/2021
LOCATION : MARIVELES, BATAAN SHEET NO. : 3 of 4

WHARF AVERAGE COMPRESSIVE STRENGTH P AVERAGE WHARF AVERAGE COMPRESSIVE STRENGTH PER LOCATION
AVERAGE
READING LOCATION : SUPPORT MIDSPAN SUPPORT PER SLAB READING LOCATION : SUPPORT MIDSPAN SUPPORT PER SLAB
MARK/GRIDLINE MARK/GRIDLINE
SLAB 1-2-D-E 45.8 MPa 25.9 MPa 25.8 MPa 32.5 MPa SLAB 12-13-D-E 21.3 MPa 31.3 MPa 10.3 MPa 21.0 MPa
SLAB 2-3-E-F 24.2 MPa 20.4 MPa 23.5 MPa 22.7 MPa SLAB 13-14-E-F 43.3 MPa 42.2 MPa 23.6 MPa 36.4 MPa
SLAB 3-4-D-E 24.6 MPa 32.4 MPa 22.3 MPa 26.4 MPa SLAB 14-15-C-D 36.0 MPa 16.2 MPa 15.7 MPa 22.6 MPa
SLAB 4-5-B-C 21.7 MPa 23.5 MPa 23.9 MPa 23.0 MPa SLAB 15-16-E-F 29.5 MPa 31.7 MPa 26.3 MPa 29.2 MPa
SLAB 5-6-D-E 22.5 MPa 18.4 MPa 31.4 MPa 24.1 MPa SLAB 15-16-B-C 7.0 MPa 47.3 MPa 50.9 MPa 35.1 MPa
SLAB 6-7-E-F 39.7 MPa 18.4 MPa 43.1 MPa 33.7 MPa SLAB 17-18-E-F 48.8 MPa 54.0 MPa 62.3 MPa 55.0 MPa
SLAB 7-8-C-D 23.4 MPa 19.1 MPa 27.0 MPa 23.2 MPa SLAB 18-19-C-D 22.4 MPa 43.3 MPa 24.1 MPa 29.9 MPa
SLAB 8-9-E-F 39.8 MPa 29.1 MPa 40.5 MPa 36.5 MPa SLAB 19-20-B-C 49.5 MPa 62.3 MPa 65.4 MPa 59.1 MPa
SLAB 9-10-B-C 40.0 MPa 44.5 MPa 50.6 MPa 45.0 MPa SLAB 20-21-E-F 73.0 MPa 73.7 MPa 70.6 MPa 72.4 MPa
SLAB 10-11-D-E 27.9 MPa 29.5 MPa 43.8 MPa 33.7 MPa SLAB 21-22-C-D 67.3 MPa 52.4 MPa 72.0 MPa 63.9 MPa
SLAB 11-12-E-F 47.9 MPa 60.3 MPa 46.7 MPa 51.6 MPa SLAB 22-23-B-C 61.7 MPa 72.0 MPa 45.0 MPa 59.6 MPa
SLAB 12-13-B-C 51.1 MPa 33.4 MPa 53.7 MPa 46.1 MPa SLAB 22-23-E-F 62.7 MPa 73.0 MPa 46.0 MPa 60.6 MPa
REMARKS : Test conducted in accordance with ASTM Standard

Prepared by : Noted by :

DECIE L. OMICTIN MARTIN A. VILLAR


Structural & Engineering Staff Structural & Engineering Manager
CONCRETE RESTORATION AND REPAIR TECHNOLOGY (CORRTECH), INC.
2/F CORRTECH Compound, General Aviation Road, Bankal, Lapu-lapu City, Cebu, Philippines, 6015
Telephone No. (032) 239-1941 | Telefax (032) 239-2459
Email: info@corrtechinc.net | Website: www.corrtechinc.net

PCAB LICENSE A # 34492

REBOUND HAMMER TEST - SUMMARY (PIER 1 & 2 - PILE CAPS)


PROJECT : PIER INTEGRITY ASSESSMENT (STRUCTURAL ASSESSMENT AND INSPECTION OF MGC PIER) DATE TEST01/18/2021 - 3/19/2021
LOCATION : MARIVELES, BATAAN SHEET NO. 4 of 4

AVERAGE COMPRESSIVE STRENGTH PER LOCATION


PIER 1 PIER 2
LOCATION/GRIDL
PILE CAP I-23
PILE CAP 1-25
PILE CAP 1-27 PILE CAP D-15ˊ
PILE CAP 1-31 PILE CAP D-17ˊ
PILE CAP D-21ˊ
PILE CAP D-23ˊ
PILE CAP D-25ˊ
PILE CAP D-27ˊ
PILE CAP D-29ˊ
PILE CAP D-31ˊ
MARK Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ
BS - 1 MPa MPa MPa 56.3 MPa MPa MPa MPa MPa MPa MPa MPa MPa
BS - 2 MPa MPa MPa 54.5 MPa MPa MPa MPa MPa MPa MPa MPa MPa
BS - SS MPa MPa MPa 36.6 MPa MPa MPa MPa MPa MPa MPa MPa MPa
BS - MS MPa MPa MPa 29.9 MPa MPa MPa MPa MPa MPa MPa MPa MPa
PS - SS MPa MPa MPa 38.2 MPa MPa MPa MPa MPa MPa 39.7 MPa 56.6 MPa MPa
PS - MS MPa MPa MPa 30.7 MPa 21.6 MPa MPa 30.5 MPa MPa 60.8 MPa 25.0 MPa 63.2 MPa MPa
PS - 1 MPa MPa MPa 28.2 MPa 24.9 MPa MPa 34.4 MPa 35.0 MPa 23.9 MPa 33.4 MPa 67.3 MPa 52.4 MPa
PS - 2 MPa MPa MPa 30.0 MPa 26.0 MPa MPa 28.9 MPa MPa 8.7 MPa 61.7 MPa 55.7 MPa 53.7 MPa
AVERAGE PER PILE CAP
### MPa ### MPa ### MPa 38.05 MPa 24.17 MPa ### MPa 31.27 MPa 35.00 MPa 31.13 MPa 39.95 MPa 60.70 MPa 53.05 MPa
MARK Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ
PS - 1 MPa MPa MPa 39.9 MPa 32.1 MPa 55.9 MPa 18.3 MPa 18.3 MPa 42.0 MPa 49.6 MPa 50.1 MPa 58.2 MPa
PS - 2 MPa MPa MPa 41.1 MPa 37.7 MPa 46.5 MPa 27.2 MPa 27.9 MPa 47.0 MPa 61.7 MPa 47.0 MPa 55.4 MPa
PS-SS MPa MPa MPa 47.9 MPa 26.7 MPa MPa MPa 30.9 MPa 38.8 MPa 37.4 MPa 50.0 MPa 57.2 MPa
PS-MS MPa MPa MPa 28.0 MPa MPa MPa MPa MPa MPa MPa 36.8 MPa MPa
BS-SS MPa MPa MPa 51.4 MPa MPa MPa MPa MPa MPa MPa MPa MPa
BS-MS MPa MPa MPa 46.5 MPa MPa MPa MPa MPa MPa MPa MPa MPa
BS - 1 MPa MPa MPa 47.6 MPa MPa MPa MPa MPa MPa MPa MPa MPa
BS - 2 MPa MPa MPa 53.4 MPa MPa MPa MPa MPa MPa MPa MPa MPa
AVERAGE PER PILE CAP
### MPa ### MPa ### MPa 44.48 MPa 32.17 MPa 51.20 MPa 22.75 MPa 25.70 MPa 42.60 MPa 49.57 MPa 45.98 MPa 56.93 MPa
REMARKS : Test conducted in accordance with ASTM Standard
BS-1 BS-2 BS-1 BS-2
BS - BALANGA SIDE ↓ ↓ ↓ ↓
PS - POBLACION SIDE BS-MS → ⃝ ⃝ ← BS-SS
MS - MOUNTAIN SIDE
SS - SEA SIDE Aˊ Cˊ
CONCRETE RESTORATION AND REPAIR TECHNOLOGY (CORRTECH), INC.
2/F CORRTECH Compound, General Aviation Road, Bankal, Lapu-lapu City, Cebu, Philippines, 6015
Telephone No. (032) 239-1941 | Telefax (032) 239-2459
Email: info@corrtechinc.net | Website: www.corrtechinc.net

PCAB LICENSE A # 34492

Prepared by : PS-MS → ⃝ ⃝ ← PS-SS Noted by :


↑ ↑ ↑ ↑
DECIE L. OMICTIN PS-1 PS-2 PS-1 PS-2 MARTIN A. VILLAR
Structural & Engineering Staff Structural & Engineering Manager
CONCRETE RESTORATION AND REPAIR TECHNOLOGY (CORRTECH), INC.
2/F CORRTECH Compound, General Aviation Road, Bankal, Lapu-lapu City, Cebu, Philippines, 6015
Telephone No. (032) 239-1941 | Telefax (032) 239-2459
Email: info@corrtechinc.net | Website: www.corrtechinc.net

PCAB LICENSE A # 34492

REBOUND HAMMER TEST - SUMMARY (WHARF - PILE CAPS)


PROJECT : ABOITIZ CONSTRUCTION INC. - STRUCTURAL ASSESSMENT AND EVALUATION OF LAPAZ PIER DATE TEST01/18/2021 - 3/19/2021
LOCATION : INGORE, ILO-ILO CITY SHEET NO. 1 of 4

AVERAGE COMPRESSIVE STRENGTH PER LOCATION


WHARF
LOCATION/GRIDLINE PILE CAP D-2
PILE CAP E-3
PILE CAP D-4
PILE CAP B-5
PILE CAP E-6
PILE CAP D-7
PILE CAP C-8
PILE CAP F-9
PILE CAP B-10
PILE CAP D-11
PILE CAP E-12
PILE CAP C-13
MARK Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ Aˊ
NORTH 25.5 MPa 28.7 MPa 15.3 MPa 22.0 MPa 24.3 MPa 29.0 MPa 26.1 MPa 16.2 MPa 20.5 MPa 27.1 MPa 29.6 MPa 35.2 MPa
EAST 24.3 MPa 24.1 MPa 14.8 MPa 21.0 MPa 23.9 MPa 28.5 MPa 28.3 MPa 34.2 MPa 16.9 MPa 28.6 MPa 26.8 MPa 24.5 MPa
SOUTH 23.9 MPa 32.2 MPa 16.3 MPa 36.9 MPa 22.0 MPa 29.3 MPa 25.8 MPa 16.8 MPa 29.8 MPa 27.5 MPa 26.5 MPa 26.0 MPa
WEST 22.3 MPa 25,42 MPa 15.6 MPa 28.3 MPa 21.6 MPa 21.1 MPa 26.4 MPa 17.9 MPa 21.3 MPa 26.8 MPa 30.5 MPa 27.4 MPa
AVERAGE PER PILE CAP 24.02 MPa 28.34 MPa 15.49 MPa 27.06 MPa 22.97 MPa 26.98 MPa 26.66 MPa 21.27 MPa 22.14 MPa 27.49 MPa 28.34 MPa 28.28 MPa
LOCATION/GRIDLINE PILE CAP D-13
PILE CAP F-14
PILE CAP D-15
PILE CAP E-16
PILE CAP B-16
PILE CAP E-18
PILE CAP B-20
PILE CAP E-21
PILE CAP C-22
PILE CAP B-23
PILE CAP E-23
PILE CAP E-25
MARK Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ Cˊ
NORTH 25.8 MPa 24.0 MPa 21.7 MPa 26.0 MPa 19.5 MPa 17.8 MPa 14.4 MPa 20.3 MPa 25.6 MPa 24.7 MPa 20.7 MPa 18.1 MPa
EAST 25.3 MPa 21.2 MPa 23.3 MPa 28.1 MPa 24.0 MPa 27.4 MPa 12.4 MPa 18.5 MPa 24.4 MPa 25.3 MPa 21.8 MPa 17.2 MPa
SOUTH 22.9 MPa 21.2 MPa 24.8 MPa 26.7 MPa 21.1 MPa 20.6 MPa 17.0 MPa 16.9 MPa 27.6 MPa 25.0 MPa 21.2 MPa 16.3 MPa
WEST 21.2 MPa 20.4 MPa 23.4 MPa 26.6 MPa 20.9 MPa 17.9 MPa 14.7 MPa 18.2 MPa 24.0 MPa 25.0 MPa 19.3 MPa 16.6 MPa
AVERAGE PER PILE CAP 23.78 MPa 21.70 MPa 23.30 MPa 26.85 MPa 21.38 MPa 20.94 MPa 14.62 MPa 18.47 MPa 25.43 MPa 25.02 MPa 20.74 MPa 17.06 MPa
REMARKS : Test conducted in accordance with ASTM Standard
= INACCESSIBLE BY DRUMBOAT BS-1 BS-2 BS-1 BS-2 BS-1 BS-2 BS-1 BS-2
↓ ↓ ↓ ↓ ↓ ↓ ↓ ↓
BS-MS → ⃝ ⃝ ← BS-SS BS-MS → ⃝ ⃝ ← BS-SS

Aˊ Cˊ Aˊ Cˊ

Prepared by : PS-MS → ⃝ ⃝ ← PS-SS PS-MS → ⃝ ⃝ ← PS-SS Noted by :


↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑
PATRICIA S. CALO PS-1 PS-2 PS-1 PS-2 PS-1 PS-2 PS-1 PS-2 MARTIN A. VILLAR
Structural & Engineering Staff PIER 1 - PILE CAP REBOUND HAMMER TEST PLAN PIER 2 - PILE CAP REBOUND HAMMER TEST PLAN Structural & Engineering Manager