You are on page 1of 124

PAITON Ⅲ EXPANSION PROJECT

COURSE – G (BOP)

CONTENTS : G-10 Fire Fighting System


(Part-1)
TRAINER: Iskandar Syah
Hirokazu Miyazaki

MITSUBISHI HEAVY INDUSTRIES, LTD.


NAGASAKI SHIPYARD & MACHINARY WORKS
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 2

FIRE PROTECTION SYSTEMS

TERMINAL OBJECTIVES
Upon completion of the training, the trainee
will be able to describe the main components
of Fire Protection Systems of the PAITON Ⅲ
Project.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 3

FIRE PROTECTION SYSTEMS


ENABLING OBJECTIVES
• To give an overview of the Fire Protection
Systems

• To describe the major components

• To explain functions of each major


components

• To state how all the component perform


together as a system

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 4

FIRE PROTECTION SYSTEMS


Contents
1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 FM200 System
3.5 Fire Extinguisher
3.6 Fire Pumps
4. Fire Detection System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM FIRE TRAINING (OVERALL) PAGE- 5

1. Introduction
Fire is a rapid oxidation process that creates light, heat and
smoke, and varies in intensity.
Controlling fire
- To cook food
- To generate power
- To bring happiness

Violent, destructive and Uncontrolled Burning


- To destroy nature
- To destroy property
- To take human life

From: Wikipedia
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM FIRE TRAINING (OVERALL) PAGE- 6

1. Introduction
Three Elements of Fire Triangle

Fuel
COMBUSTIBLE HEAT
Chemical

Atmosphere
OXYGEN
Air

From: Wikipedia
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM FIRE TRAINING (OVERALL) PAGE- 7

1. Introduction
Four Elements to sustain combustion (Fire)

COMBUSTIBLE HEAT

CHEMICAL
CHAIN
REACTION

OXYGEN

From: Wikipedia
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 8

1. Introduction FIRE CLASSIFICATION


Classification of Fire by NFPA

Class A: Fire in ordinary combustible material (Wood,


Cloth, paper, rubber, plastics)

Class B: Fire in flammable liquids, combustible liquid,


petroleum greases, tars, oils, flammable gases

Class C: Fire in electrical equipment

NFPA: National Fire Protection Association

From: Wikipedia
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 9

1. Introduction FIRE PROTECTION SYSTEM


Fire Protection System

Fire Detection System Fire Fighting System


• Early detection and • Fire Water system
Notification of Fire Activation • Foam system
Fire Fighting system • CO2 GAS SYSTEM
• Fire pump system
• Fire Extinguisher

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 10

FIRE PROTECTION SYSTEMS


Contents
1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 FM200 System
3.5 Fire Extinguisher
3.6 Fire Pumps
4. Fire Detection System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 11

2. System Application FIRE PROTECTION SYSTEM


Design Criteria

Application is decided based on the following criteria;

- Contract Specification

- NFPA Guideline (National Fire Protection Association)

- Indonesian Regulation (Regulations and Restriction in


each country)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 12

2. System Application Application Table (1/4)


O :APPLICABLE :NOT APPLICABLE
Water Foam LP CO2 FM200 Portable fire Fire Detection and
Building
system system system system extinguisher Alarm system

MAIN TURBINE BUILDING ○ ○ ○ ○

BOILER ○ ○ ○ ○

BOILER AREA (OUTDOOR) ○ ○ ○

SERVICE BUILDING ○ ○ ○

TRANSFORMERS AREA ○ ○ ○

FGD & EP & ASH


ELECTRICAL & CONTROL ○ ○ ○
BUILDING
AIR COMPRESSOR
○ ○ ○
BUILDING

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 13

2. System Application Application Table (2/4)


O :APPLICABLE :NOT APPLICABLE

Water Foam LP CO2 FM200 Portable fire Fire Detection and


Building
system system system system extinguisher Alarm system

DIESEL
○ ○ ○
GENERATOR

H2 & N2 & O2 STORAGE


○ ○ ○
HOUSE (WITH SUNSHADE)

FLY ASH
○ ○ ○
TRANSPORT BUILDING

FUEL OIL STORAGE


○ ○ ○ ○
TANK YARD

COAL CONVEYERS ○ ○

CRUSHER HOUSE ○ ○ ○

TRANSFOR TOWERS ○ ○ ○

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 14

2. System Application Application Table (3/4)


O :APPLICABLE :NOT APPLICABLE
Water Foam LP CO2 FM200 Portable fire Fire Detection and
Building
system system system system extinguisher Alarm system
COAL HANDLING
○ ○ ○
BUILDING

CHLORINATION HOUSE
○ ○ ○
(INCLUDING INTAKE ELEC.)

CHEMICAL LABORATORY
BUILDING (INSERVICE ○ ○ ○
BUILDING.)

DESALINATION PLANT ○ ○ ○
DESALINATION PLANT
○ ○ ○
BUILDING
SERVICE WATER TANK ○ ○ ○
DIESEL GENERATOR
○ ○ ○ ○
FUEL OIL TANK

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 15

2. System Application Application Table (4/4)


O :APPLICABLE :NOT APPLICABLE

Water Foam LP CO2 FM200 Portable fire Fire Detection and


Building
system system system system extinguisher Alarm system

FIRE FIGHTING PUMP


○ ○ ○
BUILDING

SEA WATER FIRE PUMP


○ ○
(DIESEL ENGINE)

GATE HOUSE ○ ○ ○

GUARD HOUSE ○ ○ ○

CEM ELECTRICAL BUILDING ○ ○ ○

CHIMNEY ELEVATOR
○ ○ ○
MACHINE ROOM

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 16

FIRE PROTECTION SYSTEMS


Contents
1. Introduction
2. System Application
3. Fire Fighting System
3.1 Water System
3.2 Foam System
3.3 CO2 System
3.4 FM200 System
3.5 Fire Extinguisher
3.6 Fire Pumps
4. Fire Detection System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 17

3.Fire Fighting System Overall Fire Protection system


TYPE OF FIRE PROTECTION SYSTEM - Fire Water system
OUTDOOR HYDRANT General use to cover whole plant area

HOSE STATION Initial, small fire in building, self standing or wall mount

Hydraulic automatic actuated piping system with


SPRINKLER
thermal break element to discharge water from
nozzles opened by heat.

WATER SPRAY Electric automatic actuated (by electrical detectors) or


hydraulic automatic actuated (by pilot sprinklers) fixed
piping with water spray nozzles to discharge water
over the protected surface or area.
PRE-ACTION Hydraulic automatic activated fixed piping with thermal
break element to discharge water from nozzles
SPRINKLER SYSTEM
opened by heat. Water will only be released after
additional electrical signal from detectors.
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 18

3.Fire Fighting System Overall Fire Protection system

TYPE OF FIRE PROTECTION SYSTEM - Foam System

FOAM SYSTEM Manual operated foam system discharges through


foam chamber that directs the flow to the oil surface
in tank.
FOAM HOSE STATION Supplementary foam discharge from Foam Bladder
tank.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 19

3.Fire Fighting System Overall Fire Protection system


TYPE OF FIRE PROTECTION SYSTEM – CO2 system

LP CO2 SYSTEM Manually operated CO2 system discharges the gas


from Low Pressure storage tanks that directs the
flow to the area to be protected.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 20

3.Fire Fighting System Overall Fire Protection system


TYPE OF FIRE PROTECTION SYSTEM – FM200 system

FM200 SYSTEM Automatic operated FM-200 system discharges the


gas from high pressure cylinders that directs the
flow to the area to be protected.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 21

3.Fire Fighting System Overall Fire Protection system


TYPE OF FIRE PROTECTION SYSTEM – Portable Fire Extinguisher

DRY CHEMICAL
Initial, small fire, local application for
Class A, B, C fire
CARBON DIOXIDE GAS

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 22

FIRE PROTECTION SYSTEM


Contents

1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 FM200 System
3.5 Fire Extinguisher
3.6 Fire Pumps
4. Fire Detection System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 23

3.1 Fire Water System Fire Water Ring Main


• Purpose
To distribute fire water to the whole plant area through
underground piping.

• Design Basis
Main pipe line size : 150A ~ 300A

• Manual Operation

• Fire Water Supply


Fire water is supplied by fire pumps from service water
tank

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 24

3.1 Fire Water System

Outdoor Hydrant

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 25

3.Fire Water System Fire Water Piping

Fire Water Ring Main Piping

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 26

3.Fire Water System


Outdoor Hydrant Layout
91.4m

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 27

3.1 Fire Water System Outdoor Hydrant Coverage Area


45.7 m (max.)
30 m (30m/hose x 1 hose) 15.7 m

Water Nozzle

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 28

3.1 Fire Water System


Outdoor Hydrant

Valve Box
Hydrant

Ground

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 29

3.1 Fire Water System Outdoor Hydrant


Outdoor Hydrant Assembly

Hose
Connection

Pumper
Connection

Hydrant
Body

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 30

3.1 Fire Water System Outdoor Hydrant


Fire Hose Box
Installed near Hydrant

Fire Hose Box

Fire Hose

Hinge
Hydrant Wrench
Key

Flow Nozzle

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 31

3.1 Fire Water System Outdoor Hydrant


Fire Hose Hand line Nozzle

2.5 inch Fire Hose (30m) x 2sets Used on Class A and B fires.
Used for Outdoor Hydrants Adjustable from fog to shut off.
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 32

3.1 Fire Water System Fire Water Ring Main


Post Indicator Post Indicator Valve
Post Indicator
Valve

Ground
Used to isolate the water ring main & indicates whether the
Isolation Valve is Open or Shut.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 33

3.1 Fire Water System Outdoor Hydrant

DESCRIPTION OUTDOOR HYDRANT

NFPA Class Class 1

Hose Connection Size 2-1/2” (635 mm)

No. of Hose Connections 2

Min. Water Flow Rate 125 gpm (475 lit./min)

Pressure Min. (Max.) 100 psi, (689 kPa)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 34

3.1 Fire Water System

Hose Station

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 35

3.1 Fire Water System Hose Station (Indoor Hydrant)

Main Turbine Building

Boiler Building

Hose Station

Main Turbine Building 2FL (FL+6,500)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 36

Hose Station (Indoor Hydrant)


3.1 Fire Water System

Main Turbine Building

Boiler Building

Hose Station

Boiler Building L3FL (FL+19,000)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 37

3.1 Fire Water System Indoor Hydrant


Hose Station

Used to store hose assembly


where it is readily available
whenever required.
Water retention device stops
water at its first fold, after valve
opens, until the preceding folds
are freed by removing the hose
from the hose rack.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 38

3.1 Fire Water System Indoor Hydrant


Hose Station - Nozzle
Used on Class A and B fires in
most industrial applications.
From fog to straight stream to
shut off

Variable Fog Nozzle

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 39

3.1 Fire Water System Indoor Hydrant


Hose Station
DESCRIPTION HOSE STATION

NFPA Class Class 3


1-1/2” (38 mm) to supply water for use
by building occupants and
Hose Connection Size
2-1/2”(65 mm) to supply larger volume of
water for use by fire departments

No. of Hose Connections 2

Min. Water Flow Rate 500 gpm (1893 lit./min)

Pressure Min. (Max.) 65 psi, (448 kPa)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 40

3.1 Fire Water System

Sprinkler Systems

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 41

3.1 Fire Water System Sprinkler Systems


Fire Alarm Panel
Quartzoid
Bulb
Detector
(Sprinkler
nozzle)
Pressure
switch

Alarm
Check
Valve

Water
Ring
Main
Water Motor
Gong

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 42

3.1 Fire Water System Sprinkler Systems

Purpose
To protect under Turbine Building, etc..

Design Basis
Heat detection : 68, 79 and 141°C

Water spray density : 8.1, 10.2 and 12.0 lit/min/m2

Operation
Automatic

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 43

3.1 Fire Water System Sprinkler Systems


Quartzoid Bulb Detector (Sprinkler nozzle)

Sprinkler Protected Area Temp. Setting


-Turbine Building
・Seal Oil Unit
・1F/L Oil Piping
・2F/L West Side
・T/G OPE FL (2FL east)
68 deg C
・T-BFP 3B
・T-BFP 3A Installed in such a way that
・Main Oil Tank the water spray is directed
upward against the deflector.
・M-BFP
-Chemical Laboratory

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 44

3.1 Fire Water System Sprinkler Systems


Quartzoid Bulb Detector (Sprinkler nozzle)

Sprinkler Protected Area Temp. Setting

-Coal Conveyor Area


-Transfer House No.8
-Boiler Burner Area
-Coal Handling Transformer
-Transformer Area 79 deg C
-Turbine Building
Installed in such a way that
・ST Generator Bearing
the water spray is directed
-Emergency Diesel
upward against the deflector.
Generator Area (provided by
EDG manufacturer)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 45

3.1 Fire Water System Sprinkler Systems


Quartzoid Bulb Detector (Sprinkler nozzle)

Sprinkler Protected Area Temp. Setting

-Dust Collector at Coal


Bunker
141 deg C
-Dust Collector at Coal
Crusher House CSH-2 Installed in such a way that
the water spray is directed
upward against the deflector.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 46

3.1 Fire Water System Sprinkler Systems


Sprinkler Systems Protected Areas

Main Turbine Building


(Operating floor, etc)

Boiler Building
(Burner area,)
Emergency Diesel
Generator Area
(Equipment room)

Service Building
(Chemical Laboratory,)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 47

3.1 Fire Water System

Pre-action Sprinkler Systems

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 48

3.1 Fire Water System Pre-action Sprinkler Systems


(Double interlock)
Heat
Detector Fire Alarm Panel

PS Air Maintenance
device
Compressed
air

PS
Deluge
Valve
Water Motor
Gong

S
Water
Ring
Main

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 49

3.1 Fire Water System Pre-action Sprinkler Systems

To activate pre-action deluge, the following two events


must take place.
- A fire detection device must operate, and
- the low-pressure switch must be operated
by the loss of system pressure.
These two signals must co-exist in the releasing
control panel, which will energize the solenoid-
releasing valve, causing water to flow into system.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 50

3.1 Fire Water System Pre-action Sprinkler Systems


Pre-action Sprinkler System Protected Areas

Main Turbine Building


(ST Generator
Bearing, etc)

Coal Handling
Conveyor
(Coal Conveyor J-1,
etc)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 51

3.1 Fire Water System

Water Spray System

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 52

3.1 Fire Water System Water Spray Systems


Pilot line
Quartzoid
Bulb Detector
Fire Alarm
Panel

Pressure
switch

Deluge
Valve

Water
Ring Main
Water Motor
Gong
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 53

3.1 Fire Water System


Water Spray Systems
Water Spray Systems
Purpose
To protect transformer, etc

Design Basis
Heat detection : 79 ºC (Pilot Sprinklers)
Water spray density : 6.1, 10.2 and 12.2 lit/min/m2

Operation
Automatic

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 54

3.1 Fire Water System Water Spray Systems

Water Piping

hydraulic line

DELUGE SPRAY SYSTEM (TRANSFORMER)


MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 55

3.1 Fire Water System Water Spray Systems

WATER SPRAY SYSTEM (DISCHARGE)


MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 56

3.1 Fire Water System Water Spray Systems


Quartzoid Bulb Detector / Spray Nozzle

Used as a Heat Detector in a Hydraulic Release Deluge


Water Spray System.
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 57

3.1 Fire Water System Water Spray Systems


Water Spray Systems Protected Areas

Main Turbine
Building
(Seal oil unit, etc)

Boiler Area
(Air heater, etc)

Transformer Area
(Generator transformer, etc)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 58

FIRE PROTECTION SYSTEM


Contents

1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 FM200 System
3.4 Fire Extinguisher
3.5 Fire Pumps
4. Fire Detection System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 59

3.2 Foam System Foam System


Principle of Foaming
Foam type: Extensid AFFF 3% Concentration (expansion ratio 6:1 to 10:1)

- Copy from MINIMAX Catalog

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 60

3.2 Foam System Foam System


Fire Extinguishing Effects
This is low expansion foam produced by foaming a water-foam mixture.
Film forming effect (Aqueous Film Forming Foam):
• A very thin, quick flowing tenside film develops on the burning surface
when using aqueous film forming foam concentrates, which serves the fire-
extinguishing foam a sliding surface. The tenside film also prevents re-
ignition and therefore also protects the surface of a combustible fluid, which
is not completely covered by the foam.
Separating effect:
• The closed foam cover causes the fire zone to separate the surrounding air
and shielding it from outside against any further oxygen supply.
Cooling effect:
• This effect specifically comes to fruition in fluid and solids fires, which have
extremely high temperatures at the burning surface. Based on the heat
effect, the water proportion in the foam evaporates very quickly, whereby
the combustion energy is removed from the burnt material.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 61

3.2 Foam System Foam System

Foam chamber

Fuel Oil
Tank
Foam
Concentrate
Bladder
Tank

Water Ring
Main Mixer Foam Solution Foam Hose Station

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 62

3.2 Foam System


Foam System for Fuel Oil Tank

FOAM
CHAMBER

FUEL OIL
TANK

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 63

3.2 Foam System Foam System for Fuel Oil Tank


(Foam Chamber Layout)

Fuel Oil
Tank

Air

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 64

3.2 Foam System Foam Systems - Fixed


Important Components
Bladder Tank

Foam concentrate is
stored in
bladder which is
pressurized by
fire water.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 65

3.2 Foam System Foam Systems - Fixed


Important Components
Flanged Mixer

Used to mix water and foam concentrate to make foam solution.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 66

3.2 Foam System Foam System


Foam Concentrate
Manufacturer of foam tank : K.C.A.
Manufacturer of foam making branch pipe, foam pourer and
foam chamber : Minimax
Manufacturer of foam concentrate: Fomtec

Foam concentrate : Fluoro protein

Type of application : Dark brown liquid

Foam Solution : 3% Foam concentrate and


97% Water

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 67

3.2 Foam System Foam System


Cover the Foam System Area

No.2 FUEL OIL


STORAGE TANK

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 68

3.2 Foam System

Foam Hose Station

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 69

3.2 Foam System Foam Hose Station

Foam System
Piping
Foam Hose
Station
(Foam hose length : 30m)

Approx : 17m
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 70

FIRE PROTECTION SYSTEM


Contents

1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 FM200 System
3.5 Fire Extinguisher
3.6 Fire Pumps
4. Fire Detection System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 71

3.3 CO2 System


CO2 System
CO2 (Carbon di-oxide) gas system is used to suppress the fire
in the Coal Silo by inerting.
Low pressure CO2 system is provided in the plant.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 72

3.3 CO2 System


CO2 System – Protected Area

LP CO2 SYSTEM ・Coal Silo

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 73

3.3 CO2 System CO2 System

Coal Silo

Equipment
Boiler
Arrangement
for LP CO2 System
LP CO2 Piping
LP CO2 Tank

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 74

3.3 CO2 System CO2 System


LP CO2 SYSTEM

Coal Silo

CO2 Pipe

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 75

3.3 CO2 System CO2 System

LP CO2 SYSTEM

Pressure Control Cabinet

LP CO2 Storage Tank

Direct to Process Vaporizers


MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 76

3.3 CO2 System CO2 System


LP CO2 SYSTEM

The storage tanks contain carbon dioxide at pressure up to 333


psi (23bar). Sudden release of this pressure may cause
personal injury. The accidental discharge of a carbon dioxide
system in an occupied area could cause injury or death due to
asphyxiation.
For Safety, only knowledgeable, qualified, service technicians,
trained specifically for this equipment, should perform
installation, service, or maintenance on the storage tanks. All
precautions must be taken to avoid accidental actuation or
discharge. Personnel in the protected hazard area should be
evacuated before servicing the system.
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 77

FIRE PROTECTION SYSTEM


Contents

1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 FM200 System
3.5 Fire Extinguisher
3.6 Fire Pumps
4. Fire Detection System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 78

3.4 FM200 System FM200 System – Protected Area

FM200 SYSTEM MAIN TURBINE BUILDING


・CENTRAL CONTROL ROOM (CCR)
・CONTROL EQUIPMENT ROOM (CER)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 79

3.4 FM200 System FM200 System


Chemical formula : CF3-CHF-CF3, or C3HF7
FM-200 is a colorless odorless gaseous halocarbon used as a total flood fire
suppression system for Class A and B hazards.

FM200 is known chemically as Heptafluoropropane which is liquified under


pressure for storage. It rapidly extinguishes most commonly found fires
through a combination of chemical and physical mechanisms. 80% of FM-
200 fire fighting effectiveness is achieved through heat absorption and 20%
through direct chemical means (action of the fluorine radical on the chain
reaction of a flame).

Unlike CO2 gas, FM-200 is a clean agent which does not displace oxygen
and therefore is safe for use in occupied spaces without fear of oxygen
deprivation, subject to correct design concentration.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 80

3.4 FM200 System FM200 System


FM-200 is thermally and chemically stable, but without the extremely long
atmospheric lifetimes associated with other proposed halon replacements.
The atmospheric lifetime of FM-200 has been determined to be 36.5 years.
The EPA does not consider FM-200 to be a long-lived substance when
discharged, and as such, has placed no restrictions on its use. FM-200 is
rated as Zero Ozone Depletion (ODP), is electrically non-conductive, clean
and leaves no residue.

FM-200 systems take up to less storage space than systems based on CO2
and inert gases. FM-200 based fire suppression system deploys quickly and
cleanly and won't leave behind oily residue, particulate, or water.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 81

3.4 FM200 System FM200 System


FM200 SYSTEM

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 82

3.4 FM200 System FM200 System

FM200 Bottle Area

Main Turbine Building 4FL (FL+19,000)


Equipment Arrangement for FM200 System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 83

3.4 FM200 System FM200 System

FM200 Gas Area

CCR CER

Main Turbine Building 3FL (FL+13,000)


Equipment Arrangement for FM200 System
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 84

FIRE PROTECTION SYSTEM


Contents

1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 Fire Extinguisher
3.5 Fire Pumps
4. Fire Detection System

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 85

3.4 Fire Extinguisher Types of Fire Extinguisher


Applicable Fire Type

Dry Chemical Class A, B, C

Carbon dioxide gas Class B, C

Class A: Fire in ordinary combustible material (Wood,


Cloth, paper, rubber, plastics)

Class B: Fire in flammable liquids, combustible liquid,


petroleum greases, tars, oils, flammable gases

Class C: Fire in electrical equipment

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 86

3.4 Fire Extinguisher Dry Chemical

Manufacturer : Badger

Application : Class A, B, C

Discharge Time : 22 sec

Discharge Range : 4.9 to 6.1 m


(16 to 20 ft)

Shipping Weight : 7.71 kg (17 lbs)

Operating Pressure : 1.34 kPa (195 psi)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 87

3.4 Fire Extinguisher Carbon Dioxide

Manufacturer : Badger

Application : Class B, C

Discharge Time : 14 sec

Discharge Range : 0.9 to 2.4 m


(3 to 8 ft)

Shipping Weight : 18.1 kg (40 lbs)

Operating Pressure : 5.86 MPa


(850 psi @ 70oF)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 88

FIRE PROTECTION SYSTEM


Contents

1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 Fire Extinguisher
3.5 Fire Pumps
4. Fire Detection System

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 89

3.5 Fire Pumps


Fire Fighting Pump Area

・Fire Pump Station


(With House)
・Sea Water Diesel Driven Fire Pump
(With Enclosure)
・Motor Driven Booster Fire Pump

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 90

3.5 Fire Pumps


Fire Fighting Pump Area

・Fire Pump Station

Motor Driven
Fire Water Pump Jockey Pump
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 91

3.5 Fire Pumps


Fire Fighting Pump Area

・Sea Water Diesel


Driven Fire Pump

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 92

3.5 Fire Pumps


Fire Fighting Pump Area

・Motor Driven
Booster Fire Pump

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 93

3.5 Fire Pumps Fire Pump Station


Motor
Driven (MD) Jockey
Fire Pumps Pump

MD Pump
Controllers
Jockey
Pump
Controller

Plan View
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 94

3.5 Fire Pumps Fire Pump Station


Motor Jockey
Driven (MD) Pump
Fire Pumps Controller
MD Pump
Controllers

Jockey
Pump

Side View
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 95

3.5 Fire Pumps


Motor Driven Pump

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 96

3.5 Fire Pumps Fire Pump Cut Section View

REFERENCE ONLY

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 97

3.5 Fire Pumps Motor Driven Controller

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 98

3.5 Fire Pumps


Diesel Engine Driven Pump

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 99

3.5 Fire Pumps Diesel Engine Driven Controller

REFERENCE ONLY

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 100

3.5 Fire Pumps


Jockey Pump

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 101

3.5 Fire Pumps Jockey Pump Controller

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 102

3.5 Fire Pumps


Motor Driven Booster Fire Pump

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 103

3.5 Fire Pumps


Motor Driven Booster Fire Pump Controller

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 104

FIRE PROTECTION SYSTEM


Contents

1. Introduction
2. System Application
3. Fire Fighting System
3.1 Fire Water System
3.2 Foam System
3.3 CO2 System
3.4 Fire Extinguisher
3.5 Fire Pumps
4. Fire Detection System

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 105

Fire Detection System

Fire Detection System consists of the following,

- Fire Alarm Panels

- Fire Detection Devices

- Fire Notification & Activation Devices

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 106

4. Fire Detection System F/F System Network Route


(Network Line)
Main Fire Alarm
Panel (MFAP)

Local Fire Alarm


Panel (LFAP)

Network Line
(Optical Fiber
Cable)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 107

4. Fire Detection System F/F System Network Route 1/2


(SLC Loop)
Main Fire Alarm
Panel (MFAP)

Local Fire Alarm


Panel (LFAP)

SLC Loop
(Copper cable)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 108

4. Fire Detection System F/F System Network Route 2/2


(SLC Loop)
Main Fire Alarm
Panel (MFAP)

Local Fire Alarm


Panel (LFAP)

SLC Loop
(Copper cable)

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 109

Fire Detection System

Fire Alarm Panel


Used to control the Fire Alarm System whether alarm or
trouble conditions have been detected.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 110

Fire Detection System


ONYX SERIES
Fire Detection and Extinguishing
Control Panel FMZ 5000

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 111

Fire Detection System

• Provides network annunciation and control


– Extended labeling aids in pin pointing the location of
events
– Multiple event screens for fire tracking

• Network history buffers


– Advanced filters for quicker data access

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 112

FIRE ALARM EVENT on Panel


• How the LFAP indicates a FIRE ALARM
- Produce a steady audible alarm
- Flash the FIRE ALARM LED
- Display FIRE ALARM in the upper left corner of the display, etc.
• How to respond to a FIRE ALARM
- Acknowledge the event will Silence the panel sounder
- Check the alarm message for its location and type, etc.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 113

FIRE ALARM EVENT on Panel

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 114

Fire Detection System


Fire Detection Device

Input Fire Alarm Devices

Smoke detector Output Fire


Alarm Devices
Heat detector Manual fire alarm

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 115

Fire Detection System


Smoke Detector (Optical)

Laser Receiver
V
Scatter Laser Beam Laser Beam

Lens
Laser Diode Diaphragm

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 116

Fire Detection System


Fire Detection Device
Input Fire Alarm Devices

Smoke detector Output Fire


Alarm Devices
Heat detector Manual fire alarm
Optical

Office Room, Locker Room,


Electrical Room, etc,.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 117

Fire Detection System


Smoke Detector (Optical)

Detector Spacing : 9.144 m x 9.144 m

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 118

Fire Detection System


Fire Detection Device
Input Fire Alarm Devices

Heat detector Output Fire


Alarm Devices
Smoke detector Manual fire alarm

Rate of Rise Fixed Temperature Liner Heat

Kitchen, Electrical room, Coal handling system, Coal conveyor


VAC room / Fan room, etc Fuel oil storage tank, etc

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 119

Fire Detection System


Heat Detector (Rate of Rise) Heat Detector (Fixed Temp) Liner Heat

Designed to initiate an
Rate-Of-Rise Heat Detectors Designed to initiate an alarm alarm when the
are designed to compensate when the temperature of the temperature of the
for the normal changes in surrounding reaches an surrounding reaches
ambient temperature. specific point. an specific point.
Alarm temperature Alarm temperature Alarm temperature
Electrical room, etc : 57C Fuel oil tank : 88C Coal conveyor : 88C
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 120

Fire Detection System


Fire Detection Device
Input Fire Alarm Devices

Smoke detector Manual fire alarm


Heat detector Output Fire
Alarm Devices
Manual call point

Outdoor / Indoor type Explosion Proof type

Electrical room, etc H2 / O2 / N2 gas supply house, etc


MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 121

Fire Detection System


Outdoor / Indoor / Explosion Proof type

Used as a manual mean to initiate an alarm when


fire is detected by occupants.

Indoor& Outdoor type Explosion Proof type


MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 122

Fire Detection System


Fire Detection Device

Output Fire Alarm Devices

Bell Horn Solenoid valve *Mini switch


monitor

*Mini Switch Monitor:


Pressure switch, Position switch, Other system Input, Motorised
valve (Open, Close, Fault),
Fire pump controller, Linear heat detector,CO2 Control panel.

MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 123

Fire Detection System


Alarm Bell Alarm Horn & Strobe

- Used to notify occupants that - Used to notify occupants that


fire has been detected. fire has been detected.
- Installed outside wall
(above door) of building
MHI BUSINESS
CONFIDENTIAL
G-10 FIRE FIGHTING SYSTEM TRAINING (OVERALL) PAGE- 124

Fire Fighting System


Operation & Maintenance
to be continued in Part-2

MHI BUSINESS
CONFIDENTIAL

You might also like