OWNER'S
ENGINEER : TRACTEBEL ENGINEERING PVT LTD
GE POWER
Gas Power Systems
Document ID HTGG610357
MK
Equipment Tag Number(s):
GE POWER HTGG610357
Resp. Dept.: Replaces: Revision: Doc Type: File no.:
9470 D EC
Prepared: Checked: Approved: Language: Page:
Table of contents:
1 General .......................................................................................................................................... 2
1.1 Definitions ............................................................................................................................. 2
1.2 Foreseen application and purpose ........................................................................................ 2
1.3 Categories and criticality ....................................................................................................... 2
2 Form, fit and function requirements ................................................................................................ 2
2.1 Nature of the foundation ....................................................................................................... 2
2.2 Foundation requirements for anchoring system .................................................................... 2
2.3 Foundation requirements for rotor removal ........................................................................... 8
2019-12-18 EN Approved
3 Notes ........................................................................................................................................... 13
3.1 Identification of changes ..................................................................................................... 13
Rev. Released
D
Type
EC
9470 HTGG610357
Dept. Document No.
Revision: Page:
GE POWER
D 2 / 13
HTGG610357
1 General
This document provides input from the generator perspective to specify and design the
generator foundation for air-cooled machines and water and hydrogen-cooled generator W88
(50WT25E-138) type. These requirements are mentioned herein as a guidance and Generator
Engineering shall be contacted in case of missing or additional inquiries.
1.1 Definitions
1) This specification applies to air-cooled generators of type A7x series (21Z and 23Z) and
water and hydrogen-cooled generator W88 (50WT25E-138) type.
Rev. Released
2) This specification defines the requirements for the Generator foundation from Generator
point of view in terms of design, construction and dimensions.
D
2.2.1 Description
The system consists of a long, pre-tensioned anchor, which his hold by a nut inside an anchor
box assembly. The anchor box assembly is embedded in the foundation. The assembly consists
of a pressure-plate, which itself transmits the anchor loads to the foundation. The anchor is
surrounded by a sleeve, which is connected to the pressure-plate. The entire assembly is seal-
welded. The nut shall be locked against rotation in the anchor box. The length of the anchor box
shall be designed to lower the anchor bolt below top of concrete level for generator installation.
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 3 / 13
HTGG610357
The detail of the generator anchoring system is shown in Generator and foundation outline
drawing (MLI A1B0 / B7G0).
The loads transmitted to the foundation are shown in Generator foundation loads plan (MLI
A1B1 / A1B3).
2019-12-18 EN Approved
Lng. Status
Foundation support
Support plate
Seal frame Top of concrete level
Pressure-plate (2)
Nut (4)
Figure 2. Anchor box assembly with anchor bolt of A7x (WY..Z) generator
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 4 / 13
HTGG610357
2019-12-18 EN Approved
Lng. Status
Special nut
Dept. Document No.
Support disc
Foot plate of generator
Bar
Foundation support
Foundation plate (5) Top of concrete level
Sleeve (3)
Figure 4. W88 (50WT25E-138) generator, Anchor box assembly with anchor bolt
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 5 / 13
HTGG610357
Material for the anchor box and supports shall provide sufficient strength for the design
requirements. The material should as a minimum be EN 10025 S235 JR or equivalent.
The arrangement of the foundation anchors is given by Generator and foundation outline
D
The anchor box systems shall be installed in the foundation before concrete placement. This
system allows the site to install the anchor bolts shortly before the installation of the Generator
instead of at the time of foundation construction.
9470 HTGG610357
Dept. Document No.
Before positioning of anchor boxes in the defined location, a dimensional check shall be
performed to verify that the dimensions correspond with the design documents. The vertical
alignment of the anchor boxes is critical to generator installation. The tube and box shall be
aligned to provide a 90-degree angle with a tolerance of +/- 0.2 degrees:
Anchor boxes shall be positioned in the foundation prior to concrete placement. The anchor
boxes and other embedment’s shall be adequately braced prior to the concrete placement to
meet the location requirements specified below. During the concrete placement, care should be
taken to avoid entrapping air under the embedment. Entrapped air shall be removed by
mechanical means as necessary.
Before concrete placement, the anchor box locations shall be surveyed and recorded in the X,
Y, and Z directions.
Before concrete placement, the straightness of the anchor box shall be measured and recorded.
The generator embedment’s, including anchor boxes, shall located according to the locations on
the drawings.
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 6 / 13
HTGG610357
(a)
(a)
(b)
(c), (d)
Figure 7. Vertical position (level of top of steel) of the center point of the fixed points, A7x series
(21Z and 23Z) generator
9470 HTGG610357
Dept. Document No.
Foundation steel plate (e), (f), (g) Foundation steel plate (e), (f), (g)
(a) (a)
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 7 / 13
HTGG610357
(b)
(c), (d)
(b)
Figure 10. Brush gear
(b) foundation anchor (c), (d)
2019-12-18 EN Approved
Lng. Status
(c), (d)
Figure 11. Bearing
foundation anchor
Rev. Released
D
Figure 9. Generator
Dept. Document No.
foundation anchor
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 8 / 13
HTGG610357
ATTENTION: All these tolerances are to be compliant after pour of concrete. Embedded parts
shall be installed with zero deviation from theoretical values before pour of concrete.
The top of the anchor box sleeve shall be set 15 mm (refer to Figure 16) above the final top of
2019-12-18 EN Approved
concrete elevation to avoid having concrete enter into the anchor box.
Lng. Status
Rev. Released
The anchor box shall be covered during concrete placement and remain covered until the
anchor bolts are installed to avoid having water, concrete, or other material enter into the anchor
box.
ATTENTION: The anchor box assemblies shall not be filled with concrete or grout and shall
remain free of grout after installation of the anchor bolts.
After concrete placement the final anchor box locations shall be surveyed and recorded in the X,
Y, and Z directions. GE shall be informed of any deviations from the above allowable tolerances.
2.3.1 For Generators A7x, type WY..Z (generator terminals installed on the top of the generator
housing)
The foundation load requirements for the rotor removal (e.g. support structure, intermediate
rotor support) shall be specified project specific. The length to which the rotor is withdrawn is
defined as well project specific.
IMPORTANT:
Foundation pits shall preferably not be placed in the area of any rotor removal supports, or shall
be designed to carry the expected loads.
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 9 / 13
HTGG610357
2.3.2 For Generators A7x, type WX..Z (generator terminals installed on the bottom of the generator
housing)
These rotors are mainly removed using a crane and only need an intermediate support at the
NDE side before being finally lifted by the crane. Detailed process and additional foundation
load requirements for intermediate rotor support shall be specified project specific.
DE NDE
2019-12-18 EN Approved
Lng. Status
Rev. Released
D
Intermediate support
Type
EC
Figure 17. Example of intermediate support of rotor during rotor removal, A7x (WX..Z)
9470 HTGG610357
Dept. Document No.
Detailed information about rotor removal and insertion procedure see drawing “Rotor Removal /
Insertion” MLI B8H0.
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 10 / 13
HTGG610357
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 11 / 13
HTGG610357
2019-12-18 EN Approved
Lng. Status
2.4.1 Construction requirements for cooling channels inside the foundation, applicable for all
generators with an open ventilated brush gear arrangement are given in HTGG611746.
2.4.2.1 For Generators A7x, type WY..Z (generator terminals installed on the top of the generator
housing)
The coolers are mounted in the generator frame. The generator frame is open at the bottom and
the change of direction of the air flow takes place within the foundation pit. Dimensions of the pit
shall be designed according to Generator and foundation outline drawing (MLI A1B0 / B7G0).
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 12 / 13
HTGG610357
2.4.2.2 For Generators A7x, type WX..Z (generator terminals installed on the top of the generator
housing)
The number and dimensions of the cooler varies, and depends on the generator length and
power output.
The cooler dimensions are specified in Generator and foundation outline drawing (MLI A1B0 /
B7G0).
Minimum height for cooler removal below the foundation table see dimension “g” in Figure 22.
Minimum height below the cooler see dimension “h” in Figure 22.
2019-12-18 EN Approved
Lng. Status
Rev. Released
D
Type
EC
9470 HTGG610357
Dept. Document No.
The heat exchangers, which cool the hydrogen within the generator, are surface heat
exchangers with water as a cooling medium. Each cooler consists of numerous straight tubes
with fins on their outer surface to increase the cooling surface and consequently the cooling
efficiency. Four coolers are installed vertically within the middle part of generator (in 2 cooler
pockets, on left and right side of the generator). Inlet and outlet of water are in the bottom part
of coolers in the foundation.
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.
Revision: Page:
GE POWER
D 13 / 13
HTGG610357
3 Notes
D
COPYRIGHT 2019 General Electric Company All rights reserved. The information herein is Proprietary and Technically Exclusive content
of the General Electric Company and/or its legitimate affiliates.