CIRCUIT DRAWN WITH POWER SUPPLY OFF FOR TYPICAL REMOTE CONTROL

DETAILS, SEE DOCUMENT

PLUG SELECTED VOLTAGE WIRE INTO


RWS122
TERMINAL "T"
PLACE TWO REMAINING WIRES INTO TRANSFORMER VOLTAGE OPTIONS:
POSITIONS "P"
(ORDER NOT IMPORTANT)
1 AC CONNECT CORRESPONDING
TOROIDAL
POWER COLOUR TO "T"
TRANSFORMER 2 SUPPLY
TYPE 1
3
GREY 100V
FS1 - 5A
E PURPLE 110V
ANTISURGE
SK20 FS1 BROWN 120V
FS2 P P T 3 TYPE 2
_ GREY 200V
FS1 - 2.5A
+

SK14 PURPLE 230V


ANTISURGE
BROWN 270V
SK15 TYPE 3
SK2
0VAC 1 GREY 380V
FS1 - 2.0A
M SK12 120VAC 4
PURPLE
BROWN
400V
415V
ANTISURGE
0VDC
3 4 TYPE 4
24VDC
24VDC 6 GREY 480V
POSITION _ 5 NOMINAL SUPPLY
FS1 - 2.0A
+
10 WAY SK1 (OUTPUT) PURPLE 575V
SENSOR PS1 SK11
BROWN 690V
ANTISURGE
0VDC 1
INTERNAL SUPPLY FS2 - 20A ATO FAST ACTING ALL TYPES
SK16 24VDC 2 FOLO / CPT PCB
SK4
3 2 1 4 SK9 1 2 TYPE 5 DC (ONLY)

FS1
SK7 SK2 1 +
BATTERY FS3
26 WAY
FS2

+ - SK6 SK3 2 -
FS3 (IF FITTED) 100mA SK3 1 4 3 2 SK13 2 1 SK14 DC/DC
CONVERTER
6 SK9 SK8 1 42
SK5 SK4
5 MONITOR 3 43
RELAY SK20
2 44
SK7
SK10
1 6 _
S1

+
MAKE AT FULLY SHUT SK14
8 7
2 8 SK15
MAKE AT FULLY OPEN S2 7 9
FUSE FS1 - 20A ATO FAST ACTING
3 10 FUSE FS2 - 500mA ANTI-SURGE
BREAK AT FULLY SHUT S3 6 11
4 12 REFER TO SHEET 2 FOR NOTES
BREAK AT FULLY OPEN S4 & OPTION PCB'S IF FITTED
5 13
SK4
CLOSE 9 33
STOP/ MAINTAIN 10 34
50% SK6 OPEN 8 35
COMMON -VE 1 36
18 WAY

ESD 12 25
STOP
CLOSE
LOCAL
OPEN INTERLOCK 13 37
OPEN REMOTE
CLOSE INTERLOCK 14 38
COMMON -VE 5 31
SK1 SK2
SLOT A SLOT B
SK1
SLOT C

Iss Date Chkd Revision Details IQT + SINGLE CHANNEL MODBUS MODULE +
1 141117 PJW FIRST ISSUE www. .com FOLOMATIC + CPT + RHS
2 260619 PMJ PUB002-065 WAS -039
ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: PJW Circuit Diagram Number Issue Sheet
BATH, BA1 3JQ ROCHESTER Date : 141217 No
ENGLAND NY 14624, USA
Base WD: 303B0006
Job No : - -
303M2006 2
1
of 2
Tel:01225-733200 Tel:585-247-2304 MI No : - - B1 C1 B2 C2
IQ3
CIRCUIT DRAWN WITH POWER SUPPLY OFF

SLOT A SK1
SLOT A SK3
-VE +VE
1 14 A
2 15
DEMAND +VE 3 16
COMMON -VE 4 17 } ANALOGUE INPUT SIGNAL
FOR FOLOMATIC
FOLOMATIC /

NO CONNECT 5
6 39
CPT

MANUAL/AUTO
COMMON -VE 24VDC 7 41
COMMON -VE 120VAC 8 45
SK6
1 0V SUPPLY FROM SK11 ON 50%
2 24V MOTOR CONTROL PCB
SK8
FOR MANUAL/AUTO CONNECTIONS AND 1 CLOSE
STOP

REMOTE HAND
LOCAL
DETAILS OF FOLOMATIC/CPT FUNCTIONS 2 OPEN REMOTE

REFER TO ROTORK PUBLICATION PUB002-041

STATION
18 WAY
SLOT B SK2
PASSIVE TERMINATION CONTROLLED
VIA SETTING IN ACTUATOR
SLOT B CONFIGURATION. SK2
REFER TO PUB002-040
(REFER TO MANUAL

SINGLE CHANNEL
MODBUS MODULE

SK3
INTERFACE
PUB091-004)

1 27 1A (Rx/Tx +)
2 28 1B (Rx/Tx -) RHS Bridge Board
3 29 COMMON
5 46 SCREEN SK1

47
MODBUS RS485 SIGNAL LINES REQUIRE EXTERNAL
ACTIVE BIASING TO BE PROVIDED AT ONE LOCATION
E
Terminal
FOR THE WHOLE BUS SEGMENT. REFER TO PUB091-004. 1 2 3 4 5 Block

SLOT C SK1 SLOT C

+24V (RHS)
20
CAN ISOLATOR

1
OPTION CARD

CAN H
2 32
CAN SHEILD
SK3 3
RHS

CAN L
4 40
5
0V (RHS) Actuator RHS
21
Terminal Terminal Function
24
Bung No. Block No.
30 20 1 +24V (RHS)
21 2 0V (RHS)
RHS CABLE IS CUSTOMER SUPPLIED, FOR E
SPECIFICATION SEE PUB002-059, MAXIMUM 32 3 CAN H
LENGTH OF CABLE TO BBE 100m.
40 4 CAN L
NOTES
24 5 SHEILD
1.FUSES:
-PS1 is a self-resetting fuse. 3.INDICATION:
-Refer to publication PUB002-065 for approved fuses FS1 and FS2. -For typical position, status and alarm indication see PUB002-041.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%, -“S” contacts are user configurable and are shown in their default
applies for rated torque performance; duty cycle is not guaranteed. setting.
2.REMOTE CONTROL: -Refer to PUB002-040 for functions and configuration instructions.
-For typical remote control circuits refer to: -Monitor Relay indicates actuator availability for remote control (shown
-RWS indicated or PUB002-041. “unavailable”). It can be configured to exclude local/remote selection.
-For DC and AC control, connect –ve/0V to terminal 36. -Refer to PUB002-040 for monitored functions and configuration
-(For negative switch / positive common, refer to RWS indicated). instructions.
-Control signal threshold voltages: -Voltage applied to indication contacts must not exceed 150Vac
-DC: “on” ≥16Vdc / “off” ≤8Vdc, max 60Vdc. -Individual Switch current must not exceed 3.5A inductive, 5A resistive
-AC: “on” ≥60Vac / “off” ≤40Vac, max 120Vac. and no more than 8A in total for all 4 contacts.
-Control signal duration to be 300ms minimum.
-Maximum current drawn from remote control signals is: 4.BATTERY:
-8mA at 24Vdc or 12mA at 120Vac. -Battery maintains local and remote “S” contact indication only.
-Supply provided on terminals 4 & 5: -Refer to installation manual for approved replacement battery types.
-Intended for remote control. Issue Sheet
-Max external load 5W at 24Vdc / 5VA at 120Vac Circuit Diagram Number
No
2
See Sheet 1 for all Revision details/information 303M2006 2 of 2