Design Area Calc. Mode Occupancy Area of Total Water Pressure @ Min. Min. Min. Calculated Hose Margin To
Name (Model) Application Source Density Pressure Flow Heads Streams Source
Required
ROCIADORES EC25 Demand (HW) 833.32 1057.5 0.662 30.5 138 4 500 33.5
132.4
Contractor Information
Name of Contractor: P&R Arquitectos Consultores
Design
Remote Area Name ROCIADORES EC25
Occupancy Classification
Special Heads
Location
Source W1
Notes
Supply Analysis
Residual Available
Static Pressure Flow Total Demand Required Pressure
Node at Source Pressure Pressure
(psi) (gpm) (gpm) (psi)
(psi) (psi)
W1 173 150 2000 165.9 1057.5 132.4
Hoses
Inside Hose Flow / Standpipe Demand (gpm) 500
Sprinklers
Ovehead Sprinkler Flow (gpm) 557.5
Other
Required Margin of Safety (psi) 0
Graph Labels
Values
Label Description
Flow (gpm) Pressure (psi)
S1 Supply point #1 - Static 0 173
S2 Supply point #2 2000 150
S3 Supply point #3 3000 114.5
D1 Elevation Pressure 0 16.9
D2 System Demand 1057.5 132.4
Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure
Overhead
P1 208.33 25 0.662 287.5 30.5 0.676 140.7 31.7
Sprinkler
Overhead
P2 208.33 25 0.662 287.5 30.5 0.662 138 30.5
Sprinkler
Overhead
P3 208.33 25 0.662 287.5 30.5 0.662 138 30.5
Sprinkler
Overhead
P4 208.33 25 0.662 287.5 30.5 0.676 140.8 31.7
Sprinkler
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)