How do I size and wire a Buck


Boost transformer

Information

Validation
Validated
Status

Publication
Published
Status

URL Name How-do-I-size-and-wire-a-Buck-Boost-transformer

Article Details

Article
000001385
Number

Title How do I size and wire a Buck Boost transformer

Summary Buck Boost transformers can help convert power available to the needed
voltage for machinery. Multiple versions of buck/boost transformers are
available to convert voltages available to differing machine requirements.

Article Text Using an open delta boost or buck is a cost effective solution to changing 3
Phase power to the needed value.

"Boost" means adding to the supply voltage and "Buck" means to reduce the
supply voltage.
Transformers are commonly available for small boost and buck needs. An
isolation transformer can be used for bigger transformations.

Example 1:
To boost 208 to 240 you need a 32 volt boost. This is a common need so
transformers are available for 208V primary and a 32 volt secondary. Wired
in open delta boost as in the diagram, you can get 240V out of 208V cost
effectively.

All content copyright © 2021 Pellerin Milnor Corporation. All rights reserved.

L1 L2 L3 are the inbound 208v power


H1 H2 H3 are the outbound 32v power

The rating of the transormer is calculated by taking the "Boost" voltage (I.E. 32v)
and multiplying by the current of the load and the safety factor.

EXAMPLE:
The largest motor on the machine = 7.5 HP with a Full Load Amps of 21 amps at 240v.
This would size the transformer at 32 volts(Boost Voltage) x 21 amps(FLA of Motor) x
1.5(Safety Factor) = 1008 V.A.
Thus, we will use a 1 KVA Buck/Boost transformer.

Example 2:
To run a 480V machine on a 600V feed, we can use a 480 to 120 V isolation
transformer. The 120V winding is wired in series with the 480V winding and
we create a buck transformation.

Sizing the buck\boost transformer is generally done using the current across
the buck or boost winding at the current draw of the system, times a safety
factor of 150%

This auto transformer wiring solution is very cost effective and only requires
2 transformers. The alternative is an isolation transformer that would cost up
to 8 times more.

Attachment
1

Attachment
2

Attachment
3

Feedback
Was this article helpful?
Yes No

Need More Assistance?


Please fill out all parts of the form below for help
or send an email to service@milnor.com.

General Support
Case Type

Name - First and Last


E-mail Address Phone Number
Name - First and We'll never share Best Phone
Last your email with Number for
anyone else. Callback

Subject

Please enter description of the issue here.

Submit Case

You might also like