Prepared for:
Revision 1.3
November 20th, 2020
Prepared By:
SUBMITTAL NO.
055000-073-00
D NOT APPROVED
Matthew Sangen D
REVIEWED BY (SIGN): MR
DATE: 9/18/2020
THIS DOCUMENT HAS BEEN REVIEWED FOR
GENERAL CONFORMANCE WITH THE DESIGN
DRAWINGS AND SPECIFICATIONS.
SPAN SCHEDULE
TYPE LOCATION SPAN 1 LENGTH "A" DIMENSION Any review
Any review does
does not
not relieve
relieve the
the contractor
contractor oror any
any
TYP1‐32/33 NORTH PIER 24'‐0" 12'‐0" subcontractor of
subcontractor of responsibility
responsibility forfor full
full compliance
compliance
TYP1‐30/31 NORTH PIER 22'‐0" 11'‐0" with contract requirements; for correctness
with contract requirements; for correctness of of
TYP1‐28/29 NORTH PIER 24'‐6" 12'‐3"
dimensions, clearances
dimensions, clearances and and material
material quantities;
quantities;
for proper
for proper design
design of of details,
details, for
for proper
proper fabrication
fabrication
TYP1‐5/6 SOUTH PIER 34'‐0" 17'‐0"
and construction techniques; for
and construction techniques; for proper proper
TYP1‐3/4 SOUTH PIER 25'‐0" 12'‐6" coordination with
with other
other trades;
trades; and
and for
for providing
providing
coordination
TYP1‐26/27 MAIN TERMINAL 23'‐7" 11'‐9 1/2" required forfor safe
safe and
and satisfactory
satisfactory
all devices required
TYP1‐8/7 MAIN TERMINAL 25'‐8 1/4" 12'‐10 1/8" construction and
and operation.
operation.
(E) W12 x 26 (VERIFY) documents and, in fact these drawings are "APPROVED" or "APPROVED AS NOTED" unless specifically stated otherwise.
(N) L6" x 3-1/2" x 3/8" (LLV)
B B
3) These drawings are our interpretation of what is necessary to meet your specifications. It is most important therefore
that they are checked by the G.C./Architect/Engineer against drawings provided by other trades to assure proper installation
to those surrounding materials.
W8x15 4) This drawing is for the exclusive use of Transcontinental.
3" 5) Work areas must br free of duct, pipe, electrical work, etc. prior to installation of steel.
6) Chopping, patching, dry pack, grout, fireproofing or field painting/ touch-up are by others (U. N.)
7) Location of holes, clips, cuts for other trades, if required by contract. MUST be shown or verified by others on
this drawing when submitted for approval.
8) Do not scale this drawing.
9) New steel is shown as [________________________], existing steel is shown as [______ ______ ______].
3'-10"
15
(N) W8 x 15
200 lbs/ft 290 lbs/ft 3'-9" A992 SHOP PRIMER
16" U.O.N.
7
8" U.O.N. E70XX
2'-0"
B 2'-8" 6'-0" 1'-10" B
(N) W8 x 15 TO (E) W16 x 31 200 lbs/ft 19'-0"
3
2
1
W8x15
(N) L6" x 3-1/2" x 3/8" (LLV) NO. DATE COMMENTS NO. DATE ISSUED FOR
(N) L6" x 3-1/2" x 3/8" (LLV) 145 lbs/ft REVISIONS PRINT RECORD
7'-4" (VERIFY)
TRANSCONTINENTAL STEEL
1'-0"
(VERIFY) 256 PACIFIC STREET, NEWARK, N.J. 07114 TEL: (973) 596-0148 FAX: (973) 596-0679
(N) L6" x 3-1/2" x 3/8" (LLV) 334"
1" (E) W12 x 26 (N) L6" x 3-1/2" x 3/8" (LLV)
STRUCTURAL STEEL FABRICATIONS
STAIRS AND HEAVY WELDING SPECIALIST
DWG TITLE
(N) W8 x 15 TYPE 1 FBE ROOF
REINFORCEMENT AT SLAB OPENINGS
PROJECT NAME
3/16"
NEWARK LIBERTY
TYP.
3/16" INTERNATIONAL AIRPORT
(E) W12 x 26
(E) W12 x 26 ARCH'T
1 3
(N)L6"x 3 2" x 8" (LLV) TO (E)W12 x 26 DRN BY CHK'D BY JOB NO. SEARCH DWG NO.
REINFORCEMENT AT SLAB OPENINGS (TYPE 1) JMS
PLAN VIEW DATE
8/20/2020
DATE
19033
ME-130 0
8 7 6 5 4 3 2 1
Calculations – Reinforcement required For Slab Openings
C1-1 to C1-3
XS-01
Job Newark AP-FBE Strengtheining
SHEET XS-01 OF
BY GSN DATE 12-24-20
8 Hillside Ave-Montclair NJ-07042 CHECKED DATE
Z Y
V
U
Print Time/Date: 02/11/2020 14:22 STAAD.Pro V8i (SELECTseries 5) 20.07.10.64 Print Run 1 of 1
Monday, November 02, 2020, 02:14 PM
PAGE NO. 1
****************************************************
* *
* STAAD.Pro V8i SELECTseries5 *
* Version 20.07.10.64 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= NOV 2, 2020 *
* Time= 14: 6:26 *
* *
* USER ID: Newmark Engineering, P.C. *
****************************************************
1. STAAD SPACE
INPUT FILE: REPAIR.STD
2. START JOB INFORMATION
3. ENGINEER DATE 11-2-20
4. JOB NAME ST NICHOLOS CHURCH
5. JOB CLIENT TRANSCONTINENTAL
6. ENGINEER NAME GSN
7. JOB NO ELEVATOR PIT STEEL
8. END JOB INFORMATION
9. INPUT WIDTH 79
10. UNIT INCHES KIP
11. JOINT COORDINATES
12. 1 0 0 0; 2 32 0 0; 3 104.004 0 0; 4 156 0 0
13. MEMBER INCIDENCES
14. 1 1 2; 2 2 3; 3 3 4
15. DEFINE MATERIAL START
16. ISOTROPIC STEEL
17. E 29000
18. POISSON 0.3
19. DENSITY 0.000283
20. ALPHA 6E-006
21. DAMP 0.03
22. TYPE STEEL
23. STRENGTH FY 36 FU 58 RY 1.5 RT 1.2
24. END DEFINE MATERIAL
25. UNIT FEET KIP
26. MEMBER PROPERTY AMERICAN
27. 1 TO 3 TABLE ST W8X15
28. CONSTANTS
29. MATERIAL STEEL ALL
30. UNIT INCHES KIP
31. SUPPORTS
32. 1 PINNED
33. 4 FIXED BUT MY MZ
34. UNIT FEET POUND
35. LOAD 2 LOADTYPE LIVE TITLE LOAD CASE 2 LL
36. UNIT FEET KIP
P R O B L E M S T A T I S T I C S
-----------------------------------
FOR LOADING - 2
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
1 0.00000E+00-2.66667E-01 0.00000E+00 0.00000E+00 0.00000E+00-1.42222E+00
2 0.00000E+00-1.13671E+00 0.00000E+00 0.00000E+00 0.00000E+00-9.01894E+00
3 0.00000E+00-1.30335E+00 0.00000E+00 0.00000E+00 0.00000E+00 6.68618E+00
4 0.00000E+00-4.33300E-01 0.00000E+00 0.00000E+00 0.00000E+00 3.75498E+00
X = 0.762805201E+02
Y = 0.000000000E+00
Z = 0.000000000E+00
JT EXT FX/ EXT FY/ EXT FZ/ EXT MX/ EXT MY/ EXT MZ/
INT FX INT FY INT FZ INT MX INT MY INT MZ
SUPPORT=1
1 0.00 -0.27 0.00 0.00 0.00 -1.42
0.00 -1.34 0.00 0.00 0.00 1.42 111000
JOINT COORDINATES
-----------------
COORDINATES ARE INCH UNIT
JOINT X Y Z
MEMBER INFORMATION
------------------
1 1 2 32.000 0.00
2 2 3 72.004 0.00
3 3 4 51.996 0.00
MATERIAL PROPERTIES.
--------------------
ALL UNITS ARE - KIP INCH
MATERIAL
KIND E POIS DENS ALPHA DAMP G
STEEL
1D 2.90000E+04 0.300 2.83000E-04 6.00000E-06 0.030 1.11538E+04
MATERIAL PROPERTIES.
--------------------
ALL UNITS ARE - KIP INCH
1 1 1 1 0 0 0
0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 0.000E+00 0.000E+00
4 1 1 1 1 0 0
0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 0.000E+00 0.000E+00
43. PARAMETER 1
44. CODE AISC
45. PARAMETER 2
46. CODE AISC
47. FINISH
************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2014 Bentley Systems, Inc.
* http://www.bentley.com *
************************************************************
Print Time/Date: 20/11/2020 10:20 STAAD.Pro V8i (SELECTseries 5) 20.07.10.64 Print Run 1 of 1
Friday, November 20, 2020, 10:31 AM
PAGE NO. 1
****************************************************
* *
* STAAD.Pro V8i SELECTseries5 *
* Version 20.07.10.64 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= NOV 20, 2020 *
* Time= 10:10:24 *
* *
* USER ID: Newmark Engineering, P.C. *
****************************************************
1. STAAD SPACE
INPUT FILE: REPAIR17.STD
2. START JOB INFORMATION
3. ENGINEER DATE 11-2-20
4. JOB NAME ST NICHOLOS CHURCH
5. JOB CLIENT TRANSCONTINENTAL
6. ENGINEER NAME GSN
7. JOB NO ELEVATOR PIT STEEL
8. END JOB INFORMATION
9. INPUT WIDTH 79
10. UNIT INCHES KIP
11. JOINT COORDINATES
12. 1 0 0 0; 2 32 0 0; 3 104.004 0 0; 4 204 0 0
13. MEMBER INCIDENCES
14. 1 1 2; 2 2 3; 3 3 4
15. DEFINE MATERIAL START
16. ISOTROPIC STEEL
17. E 29000
18. POISSON 0.3
19. DENSITY 0.000283
20. ALPHA 6E-006
21. DAMP 0.03
22. TYPE STEEL
23. STRENGTH FY 36 FU 58 RY 1.5 RT 1.2
24. END DEFINE MATERIAL
25. UNIT FEET KIP
26. MEMBER PROPERTY AMERICAN
27. 1 TO 3 TABLE ST W8X15
28. CONSTANTS
29. MATERIAL STEEL ALL
30. UNIT INCHES KIP
31. SUPPORTS
32. 1 PINNED
33. 4 FIXED BUT MY MZ
34. UNIT FEET POUND
35. LOAD 2 LOADTYPE LIVE TITLE LOAD CASE 2 LL
36. UNIT FEET KIP
P R O B L E M S T A T I S T I C S
-----------------------------------
FOR LOADING - 2
APPLIED JOINT EQUIVALENT LOADS
JOINT FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM-Z
1 0.00000E+00-2.66667E-01 0.00000E+00 0.00000E+00 0.00000E+00-1.42222E+00
2 0.00000E+00-1.13671E+00 0.00000E+00 0.00000E+00 0.00000E+00-9.01894E+00
3 0.00000E+00-1.70335E+00 0.00000E+00 0.00000E+00 0.00000E+00-3.44662E+00
4 0.00000E+00-8.33300E-01 0.00000E+00 0.00000E+00 0.00000E+00 1.38878E+01
X = 0.973401530E+02
Y = 0.000000000E+00
Z = 0.000000000E+00
JT EXT FX/ EXT FY/ EXT FZ/ EXT MX/ EXT MY/ EXT MZ/
INT FX INT FY INT FZ INT MX INT MY INT MZ
SUPPORT=1
1 0.00 -0.27 0.00 0.00 0.00 -1.42
0.00 -1.79 0.00 0.00 0.00 1.42 111000
JOINT COORDINATES
-----------------
COORDINATES ARE INCH UNIT
JOINT X Y Z
MEMBER INFORMATION
------------------
1 1 2 32.000 0.00
2 2 3 72.004 0.00
3 3 4 99.996 0.00
MATERIAL PROPERTIES.
--------------------
ALL UNITS ARE - KIP INCH
MATERIAL
KIND E POIS DENS ALPHA DAMP G
STEEL
1D 2.90000E+04 0.300 2.83000E-04 6.00000E-06 0.030 1.11538E+04
MATERIAL PROPERTIES.
--------------------
ALL UNITS ARE - KIP INCH
1 1 1 1 0 0 0
0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 0.000E+00 0.000E+00
4 1 1 1 1 0 0
0.0000E+00 0.0000E+00 0.0000E+00 0.000E+00 0.000E+00 0.000E+00
43. PARAMETER 1
44. CODE AISC
45. FYLD 36 ALL
46. MAIN 1 ALL
47. BEAM 1 ALL
48. TRACK 1 ALL
49. CHECK CODE ALL
-----------------------------------------------------------------------
| MEM= 1, UNIT KIP-INCH, L= 32.0 AX= 4.44 SZ= 11.8 SY= 1.7|
| KL/R-Y= 36.6 CB= 1.00 YLD= 36.00 ALLOWABLE STRESSES: FCZ= 23.76 |
| FTZ= 23.76 FCY= 27.00 FTY= 27.00 FC= 19.46 FT= 21.60 FV= 14.40 |
-----------------------------------------------------------------------
-----------------------------------------------------------------------
| MEM= 2, UNIT KIP-INCH, L= 72.0 AX= 4.44 SZ= 11.8 SY= 1.7|
| KL/R-Y= 82.3 CB= 1.00 YLD= 36.00 ALLOWABLE STRESSES: FCZ= 21.60 |
| FTZ= 21.60 FCY= 27.00 FTY= 27.00 FC= 15.10 FT= 21.60 FV= 14.40 |
-----------------------------------------------------------------------
-----------------------------------------------------------------------
| MEM= 3, UNIT KIP-INCH, L= 100.0 AX= 4.44 SZ= 11.8 SY= 1.7|
| KL/R-Y= 114.3 CB= 1.00 YLD= 36.00 ALLOWABLE STRESSES: FCZ= 18.71 |
| FTZ= 21.60 FCY= 27.00 FTY= 27.00 FC= 11.09 FT= 21.60 FV= 14.40 |
-----------------------------------------------------------------------
50. FINISH
************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2014 Bentley Systems, Inc.
* http://www.bentley.com *
************************************************************
Glenn,
Thank you,
Charlie
Frank,
Thank you,
Charlie
From: Frank Duba <FDuba@perini.com>
Sent: Tuesday, October 13, 2020 4:37 PM
To: Charlie Chin <cchin@transsteel.net>
Cc: Doron Brand <doron@transsteel.net>; Terry Flynn <TFlynn@perini.com>; Ahmed Ali
<AAli@perini.com>
Subject: RE: RFI #11 FBE RTU Pipe Supports Installed Angle vs reviewed W8x15
STV has rejected the use of the single angle in-lieu of the W8.
They do provide the following option:
“To get it to work for the ~3500 lb units, we would need a double angle. So if one angle is already
installed, you could add a second back-to-back angle. They would need to be bolted together for
shear transfer (3/4” A325 bolt @ 12” OC).”
I reviewed this issue with Ahmed and Terry, and Ahmed provided the attached email to Doron
showing that the pieces in question were taken off as W8x15’s. I was not involved in Ahmed’s and
Doron’s conversations scoping the work, but would think that this would have been flagged if there
was any question.
From: Charlie Chin [mailto:cchin@transsteel.net]
Sent: Wednesday, September 23, 2020 1:15 PM
To: Frank Duba <FDuba@perini.com>
Cc: Doron Brand <doron@transsteel.net>
Subject: RFI #11 FBE RTU Pipe Supports Installed Angle vs reviewed W8x15
Frank,
Attached, please find the RFI #11 FBE RTU Pipe Supports Installed Angle vs reviewed W8x15.
Thank you,
Charlie
From: Frank Duba <FDuba@perini.com>
Sent: Wednesday, September 23, 2020 7:42 AM
To: Doron Brand <doron@transsteel.net>; Charlie Chin <cchin@transsteel.net>
Cc: Ahmed Ali <AAli@perini.com>
Subject: Returned Submittals
Please see attached.
Frank Duba
Tutor Perini Civil Group
1000 Main Street
New Rochelle, NY 10801
T: 914-739-1908
C: 914-441-3743
This email message is for the sole use of the intended recipient(s) and may contain confidential and privileged information. Any
unauthorized review, use, disclosure or distribution is prohibited. If you are not the intended recipient, please contact the sender by reply
email and destroy all copies of the original message.
THIS COMPANY IS AN EQUAL OPPORTUNITY EMPLOYER AND PROVIDES OPPORTUNITIES TO SMALL, WOMAN OWNED,
MINORITY OWNED, LOCALLY OWNED, VETERAN OWNED, DISABLED OWNED, AND DISADVANTAGED BUSINESSES (M/F/V/D).
This email message is for the sole use of the intended recipient(s) and may contain confidential and privileged information. Any
unauthorized review, use, disclosure or distribution is prohibited. If you are not the intended recipient, please contact the sender by reply
email and destroy all copies of the original message.
THIS COMPANY IS AN EQUAL OPPORTUNITY EMPLOYER AND PROVIDES OPPORTUNITIES TO SMALL, WOMAN OWNED,
MINORITY OWNED, LOCALLY OWNED, VETERAN OWNED, DISABLED OWNED, AND DISADVANTAGED BUSINESSES (M/F/V/D).