Professional Documents
Culture Documents
C2-1
May 2001 Low-Voltage Busway – Pow-R-Way III
General Description
General Standards
Cutler-Hammer Pow-R-Way III is a 600 volt, Pow-R-Way III meets the requirements of fied in both the Uniform Building Code and
totally enclosed, non-ventilated, sandwich NEMA, UL 857, CSA C22.2 NO. 27-94, IEC 439- California Building Code. The seismic capa-
bus design available with copper bus bars in 1, 2 and 4, IEC 529 and IEC 947-1, IEEE, ANSI bility of Pow-R-Way III exceeds the worst-
ratings from 225 to 5000 amperes or with alu- and is manufactured in an ISO 9002 certified case Zone 4 required levels.
minum bus bars from 225 to 4000 amperes. facility. Pow-R-Way III complies with British
Pow-R-Way III is available in outdoor feeder, Standard 5490 for protection against ingress
indoor feeder, indoor plug-in and indoor of foreign bodies, 12 mm or larger, at the
sprinkler-proof configurations. All four types plug-in opening (Finger Safe) and is rated as
can be used interchangeably without adapt- IP2X. Pow-R-Way III complies with IEC 529,
ers or special splice plates provided they are and is self certified to IP40, IP43 and IP54 for
of the same current and system rating. The plug-in bus and IP40, IP43, IP54 and IP56 for
short circuit withstand ratings for plug-in feeder bus. Pow-R-Way III is also certified for
busway are equal to those of indoor and Seismic Withstand Capability in accordance
outdoor feeder busway. with the earthquake requirements as speci-
Pow-R-Way III Designations for Available Conductor Configurations Including Grounding and Neutral Options (see Figure 1)
3WG 3-Phase, 3-Wire, 50% Internal Ground 4WG 3-Phase, 4-Wire, 50% Internal Ground, 100% Neutral
3WI 3-Phase, 3-Wire, 50% Isolated Internal Ground 4WI 3-Phase, 4-Wire, 50% Isolated Internal Ground, 100% Neutral
3WH 3-Phase, 3-Wire, 50% Integral Housing Ground 4WH 3-Phase, 4-Wire, 50% Integral Housing Ground, 100% Neutral
3WHG 3-Phase, 3-Wire, 100% Ground➀ 4WHG 3-Phase, 4-Wire, 100% Ground➀, 100% Neutral
4WNG 3-Phase, 4-Wire, 50% Internal Ground, 200% Neutral
4WNI 3-Phase, 4-Wire, Isolated Internal Ground, 200% Neutral
4WNH 3-Phase, 4-Wire, 50% Integral Housing Ground, 200% Neutral
➀ 100% Ground consists of the 50% integral hous- 4WNHG 3-Phase, 4-Wire, 100% Ground➀, 200% Neutral
ing ground combined with a 50% internal ground
bus.
Busway Cutler-Hammer
C2-2 Low-Voltage Busway – Pow-R-Way III May 2001
General Description
Pow-R-Bridge (Figure 2) By releasing the bridge joint retainer screw, the Outdoor Pow-R-Bridge (Figure 2a)
Pow-R-Way III joint connections are made Pow-R-Bridge can provide an adjustment of Joint connections for outdoor feeder busway
with the Pow-R-Bridge joint package which is 1-inch (25.4 mm) at each joint. Over adjustment are made with a weatherized version of the
installed on each section of busway prior to is prevented by the joint covers, which will only Pow-R-Bridge joint. Aluminum water barriers,
shipment. A double headed, torque indicating allow a 1-inch adjustment to be made and by 1/16-inch thick, are provided across the “T” and
bolt is provided to ensure that proper installa- stopping lances on the conductor bars of the “T opposite” sides of both joint ends on each
tion torque is achieved. Fall-away instruction Pow-R-Bridge. The non-rotating design of section of outdoor busway. Closed cell, neo-
tags are furnished on the torque indicating the Pow-R-Bridge maintains its configuration prene gaskets are applied to the top of each
bolt heads to allow for visual inspection from integrity when it has been removed from a sec- water barrier and to the inside of the aluminum
a distance. When the proper torque value is tion of busway. The conductors and insulators side access covers. The aluminum side access
achieved, the top bolt head will shear off and will not displace or swivel, making reinstalla- covers overlap the top and bottom access cov-
allow the tag to fall to the floor. Any joint that tion of the Pow-R-Bridge quick and easy. ers and bolt directly onto the end blocks. Thus,
is improperly torqued will retain the highly the completed outdoor joint has a water-resis-
visible (caution yellow) tag at the bolt head. tant enclosure assembled around it. The out-
door Pow-R-Bridge has the same 1-inch (25.4
mm) adjustibility and features as the indoor
unit, is CSA and UL listed, and meets the IEC re-
quirements for IP56 applications. No field gas-
keting or caulking is required.
Bus bars for plug-in applications have full bottom sides only, below the bus bars with are furnished with ground path contact s
sized welded conductor tabs at the contact high tensile strength zinc plated hardware. urfaces on the inside of each end. When the
location points of the plug-in outlet. The tabs No fastening bolts or screws penetrate the covers are installed, the contact surfaces are
are of the same exact thickness as the con- housing or enter the bus bar package. bolted directly to the ground path end blocks
ductor bars. The plug-in conductor tabs with four 3/8-16 1/2-inch hex bolts per cover.
extend into the plug-in outlet, maintaining Pow-R-Way III achieves the highest 6-cycle
a true sandwich design throughout the entire short circuit withstand ratings available in A highly visible label is furnished on each
busway length. the industry today. The non-magnetic, all- joint cover to alert the installer that the
aluminum housing provides for excellent covers must be properly installed to maintain
The result is improved heat dissipation, heat dissipation and a significant reduction the ground path. The result is a 50% ground
better bracing and elimination of the need to in reactance and magnetic flux leakage as path that assures ground continuity with very
separate, or flare, the conductor bars at the compared to a steel or steel and aluminum low resistance characteristics.
plug-in opening. Maintaining a true sandwich combination housing. The integrity and
design also eliminates potential pathways for strength of the housing assures specifiers 200% Neutral Option
the propagation of flame, smoke and gas and users of a safe and durable installation Pow-R-Way III offers a fully rated, 200%
through the busway housing, commonly over a broad spectrum of industrial and neutral bus option for busway fed distribution
referred to as “chimney effect.” commercial applications. systems with non-linear loads. The additional
neutral capacity prevents the overheating
Silver plating is applied to all joint and con- A protective finish of ANSI 61, epoxy powder caused by zero sequence harmonic currents.
tact surfaces after the fluidized bed epoxy is paint is applied to the inside and outside sur- The Pow-R-Way III 200% neutral is manufac-
applied. Aluminum bus bars are silver plated faces by an automated electrostatic process. tured with a single 1/2-inch thick bus bar
by the ALSTAN 88C process. Copper bus bars which receives the same silver plating and
are plated with silver by a flashing process. Internal Ground Class B, 130°C Epoxy insulation as the phase
The silver plating of the conductor tabs pro- Pow-R-Way III offers a 50% ground bus bars.
vides an extremely durable contact surface (copper or aluminum) that is internal to the
for the spring loaded connections of bus plug busway. Isolated Ground Option
stab assemblies. To meet the growing demand for grounding
Integral Ground isolation, Pow-R-Way III offers a 50% isolated
Housing Details (Figure 3) The two-piece, extruded aluminum housing ground bus that is insulated and internal to
Pow-R-Way III is constructed with a rugged is designed, manufactured and UL listed as a the busway. This option is available for
two-piece extruded aluminum housing. Pow- 50% integral ground path (integral earth) and application to operations with heavy micro-
R-Way III is designed to prohibit the entry of is fully fault rated. The system ground conti- processor-based loads or large computer
dirt and moisture. There are no seams or nuity is maintained through each joint by the installations where grounding isolation is
welds across the top or bottom sides of the ground path end blocks, ground path plates essential.
housing. The housing is bolted along the and joint covers. The aluminum joint covers
Busway Cutler-Hammer
C2-4 Low-Voltage Busway – Pow-R-Way III May 2001
General Description
CL Plug-in T
F
Plug-in Unit
Opening
B
13⁄16
End View
Wall
4 in.
Minimum
T
Plug-in
C Unit
F
Operating
Plan View Handle
Wall
F Plug-in T
Unit
F
CL
Bolt-on Unit
General Description
Advanced Bus Plugs IQ Energy Sentinel Bus Plugs Ground Detector/Neutralizer Plug
The IQ Energy Sentinel is a UL listed micro- In rare cases, bus bars in a busway system
Clipper Power Systems TVSS Bus Plug processor-based metering module capable of pick up static electricity. In order to discharge
The Pow-R-Way III plug-in device product communicating energy usage and demand this potential, a neutralizer and ground detec-
offering includes Transient Voltage Surge values over the Cutler-Hammer IMPACC/ tor bus plug is available. The unit has three
Suppression (TVSS) which is ideal for PowerNet power monitoring network. These 18,000 ohm resistors connected between the
busway fed distribution systems. A transient innovative submetering devices are designed bus bars and the ground. Static electricity is
voltage surge can disrupt, damage or destroy to mount directly to Series C molded case discharged through these resistors. A neon
sensitive microprocessor-based equipment. breakers through 400 amperes and are avail- lamp is wired in series with the bus bar and
Cutler-Hammer has developed the Clipper able for universal mounting through 2500 part of the resistor and burns continuously. If
Power System (CPS) family of products to amperes. there is a ground anywhere on the system of
ensure that quality power is supplied to com- a lower resistance than the path through the
mercial, industrial, medical and institutional Digitrip OPTIM Bus Plugs lamp, the lamp will go out, indicating that
facilities. Digitrip OPTIM is a new programmable, there is a short in the system.
communicating, microprocessor-based elec-
The suppression of AC transients is accom- tronic trip unit system for Cutler-Hammer
plished through the utilization of Metal Oxide Series C Circuit Breakers. OPTIM is available for
Varistors (MOVs) which provide a low Pow-R-Way III bus plugs on the L-Frame (70 to
impedance path to divert surges away from 600 ampere) circuit breakers. Digitrip OPTIM
loads. TVSS and filtering reduce MOV stress provides superior programmable protection
resulting in a longer life cycle, lower let and coordination, and state-of-the-art monitor-
through voltage, better noise attenuation ing and communications.
levels and increased reliability. Electrical line
noise and ringing transients are eliminated Combination Starter Bus Plugs
by adding filtering capacitors to the suppres- Plug-in combination starters or contactors
sion device. are mounted in enclosures identical to the cir-
cuit breaker and fusible switch type bus plugs
Since the TVSS unit is directly connected to the including the clamp and guides, safety inter-
busway it is able to minimize let-through volt- locks and guide pin. They are available from
age to loads which are fed from a protected size 0 through 5 with a circuit breaker, motor
busway run. The integrated design of the CPS circuit protector or fusible disconnect. For
bus plug saves the user needed wall space and specific applications and outline dimensions
greatly reduces installed project cost. The CPS refer to Cutler-Hammer.
bus plug is furnished with a fusible disconnect.
Cutler-Hammer Busway
C2-7
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions
Table A. Configurations
Ampere Rating Figure
Cu Al
225 225 A
400 400 A
600 600 A
800 800 A
1000 1000 A
1200 1200 A
1350 1350 A
1600 — A
2000 — A
— 1600 B
2500 2000 B
3200 — C
4000 2500 C
— 3200 D
5000 4000 D
Plug-in Outlet
The plug-in outlets are rated for finger safety
to IP2X in accordance with IEC 529 and British Figure 8: Plug-in Busway
Standard 5490. These are internationally rec- tion. The plug-in cover is designed to protect As a countermeasure to the effects of thermal
ognized safety standards that ensure the de- the contact surfaces and prevent the entry of expansion and mechanical vibration, the plug-
gree of protection from accidental contact of dirt, dust or moisture. The cover has a posi- in outlet is secured to the busway housing
live parts by an operator or installer. The tive screw close feature that prohibits the with high tensile strength locking hardware.
plug-in outlet and cover are made from a opening of the cover without the use of a tool.
durable, high strength, polycarbonate mate- The cover is also Utility “lead lock” sealable.
rial which is rated as Class B, 130º C, insula-
Busway Cutler-Hammer
C2-8 Low-Voltage Busway – Pow-R-Way III May 2001
Layout Dimensions
Table A. Configurations
Ampere Rating Figure
Cu Al
225 225 A
400 400 A
600 600 A
800 800 A
1000 1000 A
1200 1200 A
1350 1350 A
1600 — A
2000 — A
— 1600 B
2500 2000 B
3200 — C
4000 2500 C
— 3200 D
5000 4000 D
Layout Dimensions
Figure 10
Fittings
There is a fitting to meet every application When making field measurements and All straight lengths and fittings are marked
need: flanges, elbows, offsets, tees, cable tap layouts, it should be remembered that the with a “T” label for TOP and an “F” label for
boxes, weatherheads, transformer connec- dimensions are given from the centerline FRONT. The “T” and “F” locations will also
tions, power take-off sections, reducers, of the Pow-R-Bridge. be noted on the construction, or as-built,
adapter cubicles, expansion joints and end drawings furnished by Cutler-Hammer.
closures. The relationship of fittings to straight lengths When installing the busway, the “T” and “F”
(forward, rearward, upward and downward) markings of each section must match. Fail-
These fittings, along with standard and is illustrated in Figure 11. ure to do so will result in an improper instal-
minimum dimensions, are described on the lation with the phase bars out of sequence.
following pages.
Figure 11: Top (T) and Front (F) Orientation for Fittings
Busway Cutler-Hammer
C2-12 Low-Voltage Busway – Pow-R-Way III May 2001
Layout Dimensions
Corner Joint Elbows Given the complexity of today’s industrial Pow-R-Way III Corner Joint Elbows can solve
When it comes to bends and turns in a bus and commercial distribution systems and the any serious pathway problem and contribute
run, specifiers often face serious limitations. need to coordinate layouts with the HVAC, to successful layouts with minimal space
The leg length of a traditional 90° elbow is plumbing and lighting requirements, space requirements. The Corner Joint Elbow is CSA
limited by the amount of space needed to quickly becomes a critical factor. and UL listed for indoor applications and is
weld or bend bus bars, provide an enclosure also certified for Seismic Withstand Capabili-
around the bars and create a connection to The Pow-R-Way III Corner Joint Elbow can be ty to worst-case, Zone 4 levels.
the adjacent section. In most applications, installed in areas where a traditional 90° turn All dimensions are to the centerline of the
especially with higher ampere ratings, a could never have been accomplished before. Corner Joint Connection.
significant area may be required. It enables plug-in openings to be maximized.
Forward/Rearward
Ampere Dimensions
Rating (X) (Y)
Cu Al Inches mm Inches mm
225 225 .94 23.88 5.38 136.65
400 400 .94 23.88 5.38 136.65
600 — .94 23.88 5.38 136.65
800 600 .94 23.88 5.38 136.65
1000 — 1.25 31.75 5.69 144.53
1200 800 1.50 38.10 5.94 150.88
1350 1000 1.75 44.45 6.19 157.23
1600 1200 2.25 57.15 6.69 169.93
2000 1350 2.88 73.15 7.31 185.67
— 1600 3.25 82.55 7.70 195.58
2500 2000 4.12 104.65 8.57 217.68
3200 — 6.64 168.66 11.07 281.18
4000 2500 7.89 200.41 12.32 312.93
— 3200 8.65 219.71 13.08 332.23
5000 4000 10.42 264.67 14.85 377.19
Layout Dimensions
Elbow Flanges
Flanges can be supplied on the end of the
right or left leg as required. Minimum leg
lengths are listed in the table below. Typical
uses are for busway entrance into low-
voltage switchgear, low-voltage switch-
boards and molded case circuit breakers.
All dimensions are to the centerline of the
Pow-R-Bridge.
Upward and Downward Elbow Flanges
Forward and Rearward Elbow Flanges Ampere Rating Minimum Dimensions
Ampere Minimum Dimensions Joint Leg, (X) Flange Leg, (Y)
Rating Cu Al Up Down Up Down
Joint Leg, (X) Flange Leg, (Y)
Cu Al Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm
225 225 13.00 330.20 8.75 222.25 225 225 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
400 400 13.00 330.20 8.75 222.25 400 400 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
600 — 13.00 330.20 8.75 222.25 600 — 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
800 600 13.00 330.20 8.75 222.25 800 600 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
1000 — 13.00 330.20 8.75 222.25 1000 — 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
1200 800 13.50 342.90 9.25 235.00 1200 800 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
1350 1000 13.50 342.90 9.25 235.00 1350 1000 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
1600 1200 14.00 355.60 9.75 247.65 1600 1200 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
2000 1350 14.50 368.30 10.25 260.35 2000 1350 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
— 1600 15.00 381.00 10.75 273.05 — 1600 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
2500 2000 16.00 406.40 11.75 298.45 2500 2000 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
3200 — 18.50 469.90 14.00 355.60 3200 — 12.00 304.80 13.00 330.20 7.75 196.85 8.75 222.25
4000 2500 19.50 495.30 15.25 387.35 4000 2500 12.00 304.80 13.00 330.20 7.75 196.85 8.75 222.25
— 3200 20.50 520.70 16.00 406.40 — 3200 12.00 304.80 13.00 330.20 7.75 196.85 8.75 222.25
5000 4000 22.50 571.50 17.75 450.85 5000 4000 12.00 304.80 13.00 330.20 7.75 196.85 8.75 222.25
Offsets
An offset is used to avoid obstacles and
to conform to building structure. It is two
elbows fabricated into a single fitting for
use where space restrictions prohibit the
use of a standard 90° elbow. The minimum
leg lengths are listed in the tables below.
All dimensions are to the centerline of the Upward and Downward Offsets
Pow-R-Bridge.
Ampere Rating Minimum Dimensions
Forward and Rearward Offsets Cu Al Upward Downward
Ampere Rating Minimum Dimensions (Y) (Y) (Z) (Y) (Z)
Cu Al Inches mm Inches mm Inches mm Inches mm Inches mm
225 225 13.00 330.20 225 225 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
400 400 13.00 330.20 400 400 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
600 — 13.00 330.20 600 — 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
800 600 13.00 330.20 800 600 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
1000 — 13.00 330.20 1000 — 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
1200 800 13.50 342.90 1200 800 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
1350 1000 13.50 342.90 1350 1000 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
1600 1200 14.00 355.60 1600 1200 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
2000 1350 14.50 368.30 2000 1350 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
— 1600 15.00 381.00 — 1600 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
2500 2000 16.00 406.40 2500 2000 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
3200 — 18.50 469.90 3200 — 12.00 304.80 13.00 330.20 13.00 330.20 12.00 304.80
4000 2500 19.50 495.30 4000 2500 12.00 304.80 13.00 330.20 13.00 330.20 12.00 304.80
— 3200 20.50 520.70 — 3200 12.00 304.80 13.00 330.20 13.00 330.20 12.00 304.80
5000 4000 22.50 571.50 5000 4000 12.00 304.80 13.00 330.20 13.00 330.20 12.00 304.80
Layout Dimensions
Cu Al (X) Inches (X) mm (Y) Inches (Y) mm Cu Al (X) Inches (X) mm (Y) Inches (Y) mm
225 225 13.00 330.20 13.00 330.20 225 225 21.25 539.75 25.50 647.70
400 400 13.00 330.20 13.00 330.20 400 400 21.25 539.75 25.50 647.70
600 — 13.00 330.20 13.00 330.20 600 — 21.25 539.75 25.50 647.70
800 600 13.00 330.20 13.00 330.20 800 600 21.25 539.75 25.50 647.70
1000 — 13.00 330.20 13.00 330.20 1000 — 21.88 555.75 25.50 647.70
1200 800 13.50 342.90 13.50 342.90 1200 800 22.38 568.45 25.50 647.70
1350 1000 13.50 342.90 13.50 342.90 1350 1000 22.88 581.15 25.50 647.70
1600 1200 14.00 355.60 14.00 355.60 1600 1200 23.88 606.55 25.50 647.70
2000 1350 14.50 368.30 14.50 368.30 2000 1350 25.12 638.05 25.50 647.70
— 1600 15.00 381.00 15.00 381.00 — 1600 25.88 657.35 25.50 647.70
2500 2000 16.00 406.40 16.00 406.40 2500 2000 27.62 701.55 25.50 647.70
3200 — 27.25 692.15 26.38 670.05 3200 — 23.88 606.55 25.50 647.70
4000 2500 28.50 723.90 27.62 701.55 4000 2500 25.12 638.05 25.50 647.70
— 3200 29.25 792.95 28.38 720.85 — 3200 25.88 637.35 25.50 647.70
5000 4000 31.00 787.40 30.12 765.05 5000 4000 27.62 701.55 25.50 647.70
Layout Dimensions
C Dimension
Copper Aluminum
225-1350A 1600-2000A 2500A 3200A 4000-5000A 225-1000A 1200-1350A 1600-2000A 2500-3200A 4000A
3.63 In. 4.75 In. 6.00 In. 10.75 In. 12.25 In. 3.63 In. 4.75 In. 6.00 In. 10.75 In. 12.25 In.
92.20 mm 120.65 mm 152.40 mm 273.05 mm 311.15 mm 92.20 mm 120.65 mm 152.40 mm 273.05 mm 311.15 mm
➀ All dimensions in figure 18 remain constant ➂ G Denotes quantity of terminals per ground bus.
regardless of system wiring configuration. P Denotes quantity of terminals per phase and
➁ Standard 600 kcmil compression lugs are avail- 100% neutral bus.
able in the same quantities shown for the mechan- N Denotes quantity of terminals per 200% neutral
ical terminals. bus option.
Cutler-Hammer Busway
C2-19
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions
End Closures
End closures terminate a bus run and can
be used to close either the right or left end.
Refer to page C2-2, Figure 1 for wiring con-
ductor configurations.
Dimension (B)
3WH, 3WG, 3WHG, 4WNH, 4WNG,
3WI, 4WH, 4WG, 4WNI, 4WNHG
4WHG, 4WI
Inches 5.00 5.50
mm 127.00 139.70
Layout Dimensions
Vertical Hangers This unique hanger equalizes the weight of and UL on vertical hangers is 16 feet.
When busway is to be installed vertically, a vertically mounted busway along all sup- Intermediate hangers are also required for
spring suspension type vertical hanger ports. A vertical hanger must be used on each floor heights exceeding 16 feet.
should be used. Vertical hangers are not floor and at the end of the bus run on the last
provided unless specified. floor. The maximum span permitted by CSA
Conductor Configuration Busway Height Hangers on “F” and “F” Opposite Sides
Inches mm (A) Inches (A) mm (B) Inches (B) mm Illustration Number
3WH/4WH 4.38 111.25 4.72 119.88 4.25 107.95 Figure A & B
3WG/3WHG/4WG/4WHG 4.50 114.30 4.91 124.71 4.44 112.77 Figure A & B
3WI/4WI 4.56 115.82 4.91 124.71 4.44 112.77 Figure A & B
4WHN 4.92 124.96 5.25 133.35 4.79 121.66 Figure A & B
4WNG/4WNHG 5.05 128.27 5.44 138.17 4.97 126.23 Figure A & B
4WNI 5.10 129.54 5.44 138.17 4.97 126.23 Figure A & B
Ampere Rating Busway Width Hangers on “T” and “T” Opposite Sides
Cu Al Inches mm (A) Inches (A) mm Illustration Number
225 225 4.75 120.65 4.62 117.34 Figure C
400 400 4.75 120.65 4.62 117.34 Figure C
600 — 4.75 120.65 4.62 117.34 Figure C
800 600 4.75 120.65 4.62 117.34 Figure C
1000 — 5.38 136.65 5.25 133.35 Figure D
1200 800 5.88 149.35 5.75 146.05 Figure D
1350 1000 6.38 162.05 6.25 158.75 Figure D
1600 1200 7.38 187.45 7.25 184.15 Figure D
2000 1350 8.64 219.45 8.50 215.90 Figure D
— 1600 9.40 238.76 9.25 234.95 Figure E
2500 2000 11.17 283.71 11.06 280.92 Figure E
3200 — 16.14 409.95 16.00 406.40 Figure F
4000 2500 18.64 473.45 18.50 469.90 Figure F
— 3200 20.16 512.06 20.06 510.00 Figure F
5000 4000 23.70 601.98 23.59 600.00 Figure F
Layout Dimensions
C
L
Figure 24
Plug-in Unit Max. Max. Ac Dimensions, Inches (mm) Mechanical Terminal Approx.
Amps Volts (A) (B) (C) (D) (E) (F) Wire Range Per Phase (mm2) Wghts.
Lbs. (Kgs)
P3F322R and 60 240 20.85 12.36 5.43 7.88 4.00 6.06 Cu – (1) #14 to #3, (2.5 to 35) 24
(530) (314) (138) (200) (102) (154) Al – (1) #12 to #2 (3.2 to 38) (10.88)
P3F362R 600 Cu – (1) #14 to 1/0 (2.5 to 50)
Al – (1) #12 to 1/0 (3.2 to 50)
P3F323R and 100 240 20.85 12.36 5.43 7.88 4.00 6.06 Cu – (1) #14 to 1/0, (2.5 to 50) 24
P3F363R (530) (314) (138) (200) (102) (154) Al – (1) #12 to 1/0 (3.2 to 50) (10.88)
600 (1) # 4 to 250 kcmil Cu/Al (25 to 120)
P3F324R and 200 240 23.52 15.57 7.19 8.20 4.00 7.63 (1) # 4 to 250 kcmil Cu/Al (25 to 120) 47
(597) (395) (183) (208) (102) (194) (21.31)
P3F364R 600 (1) #4 to 600 kcmil Cu/Al (25 to 300)
or (2) 250 kcmil (120)
P3F325R and 400 240 46.94 21.22 10.07 12.67 4.00 10.69 (2) #2 to 600 kcmil Cu/Al (35 to 300) 77
P3F365R 600 (1192) (539) (256) (322) (102) (272) (34.92)
P3F365H 400 600 23.47 21.22 21.00 12.67 4.00 10.69 (2) #2 to 600 kcmil Cu/Al (35 to 300) 81
(596) (539) (533) (322) (102) (272) (36.74)
P3F326R and 600 240 46.94 26.31 10.59 14.26 4.00 13.16 (2) #2 to 600 kcmil Cu/Al (35 to 300) 82
P3F366R 600 (1192) (669) (270) (362) (102) (334) (3) #4 to 600 kcmil Cu/Al (25 to 300) (37.19)
P3F327R and 800 240 46.94 26.31 10.59 14.26 4.00 13.16 (3) #4 to 600 kcmil Cu/Al (25 to 300) 108
P3F367R 600 (1192) (669) (270) (362) (102) (334) (48.98)
Cutler-Hammer Busway
C2-23
May 2001 Low-Voltage Busway – Pow-R-Way III
Technical Data
Plug-in Protective Devices, Circuit Breaker Selection and Interrupting Ratings Chart
Breaker Frame Ampere Rating 240 Vac 480 Vac 600 Vac
Symmetrical Symmetrical Symmetrical
Amperes Amperes Amperes
ED 100-225 65,000
EDH 100-225 100,000
EDC 100-225 200,000
EHD 15-100 18,000 14,000
FDB 15-100 18,000 14,000 14,000
FD 15-225 65,000 25,000 18,000
HFD 15-225 100,000 65,000 25,000
FDC 15-225 200,000 100,000 35,000
JDB, JD 70-250 65,000 25,000 18,000
HJD 70-250 100,000 65,000 25,000
JDC 70-250 200,000 100,000 35,000
DK 250-400 65,000
KDB 250-400 65,000 35,000 25,000
KD, CKD➀ 250-400 65,000 35,000 25,000
HKD, CHKD➀ 250-400 100,000 65,000 35,000
KDC 250-400 200,000 100,000 50,000
LDB 300-600 65,000 35,000 25,000
LD, CLD➀ 300-600 65,000 35,000 25,000
HLD, CHLD➀ 300-600 100,000 65,000 35,000
LDC, CLDC➀ 300-600 200,000 100,000 50,000
MD 400-800 42,000 35,000 22,000
MDS 400-800 42,000 35,000 22,000
MDSC➁ 400-800 42,000 35,000 22,000
ND➂ 600-1200 65,000 50,000 25,000
HND➂ 600-1200 100,000 65,000 35,000
NDC➂ 600-1200 200,000 100,000 50,000
Current Limiting Breakers
LA Tri-Pac 70-400 200,000 200,000 200,000
Fusible Switch Horsepower and Short Circuit Ratings (based on fuse class)
Ampere 240 Volts 480 Volts 600 Volts
Rating NEC Standard Maximum Max. Sym. NEC Standard Maximum Max. Sym. NEC Standard Maximum Max. Sym.
RMS @ Fuse RMS @ Fuse RMS @ Fuse
Class Class Class
30 3 7.5 200kA - R 5 15 200kA - R 7.5 20 200kA - R
60 7.5 15 200kA - R 15 30 200kA - R 15 50 200kA - R
100 15 30 200kA - R 25 60 200kA - R 30 75 200kA - R
200 25 60 200kA - R 50 125 200kA - R 60 150 200kA - R
400 50 125 200kA - R 100 250 200kA - R 125 350 200kA - J
600 75 200 200kA - R 150 400 200kA - J 200 500 200kA - J
800 100 250 200kA - L 200 500 200kA - L 250 500 200kA - L
➀ Indicates 100% rated breaker. Contact the Product ➂ Plug-in units available up to 800 amperes. Above
Line for application Information. 800 amperes only available in built-in or bridge
➁ Indicates 100% rated breaker available for built-in joint power take-off or bolt-on unit.
or bridge joint Power Take-off/Bolt-on units only,
from 800 amperes and above. Contact the
Product Line for application Information.
Busway Cutler-Hammer
C2-24 Low-Voltage Busway – Pow-R-Way III May 2001
Technical Data
Aluminum
Ampere 6-Cycle RMS Symmetrical IEC 439 Short Circuit Maximum Class L Fuse to Achieve
Rating Short Circuit Rating Rating 6-Cycle RMS Series Rating
Plug-in Feeder 1 Second (60 cycles)
Plug-in and Feeder 100 kA 200 kA
225 85,000 85,000 30,000 2000A 1200A
400 85,000 85,000 30,000 2000A 1200A
600 85,000 85,000 30,000 2000A 1200A
800 100,000 100,000 43,000 — 2500A
1000 100,000 100,000 52,000 — 2500A
1200 125,000 125,000 61,000 — 2500A
1350 150,000 150,000 87,000 — 4000A
1600 150,000 150,000 95,000 — 4000A
2000 150,000 150,000 121,000 — 4000A
2500 200,000 200,000 130,000 — —
3200 200,000 200,000 173,000 — —
4000 200,000 200,000 200,000 — —
Copper
Ampere 6-Cycle RMS Symmetrical IEC 439 Short Circuit Class L Fuse Needed to Achieve
Rating Short Circuit Rating Rating 6-Cycle RMS Series Rating
Plug-in Feeder 1 Second (60 cycles)
Plug-in and Feeder 100 kA 200 kA
225 85,000 85,000 43,000 2000 1600
400 85,000 85,000 43,000 2000 1600
600 85,000 85,000 43,000 2000 1600
800 85,000 85,000 43,000 2000 1600
1000 100,000 100,000 55,000 — 3000
1200 100,000 100,000 68,000 — 3000
1350 100,000 100,000 80,000 — 3000
1600 125,000 125,000 97,000 — 3000
2000 150,000 150,000 130,000 — 4000
2500 150,000 150,000 173,000 — 4000
3200 200,000 200,000 182,000 — —
4000 200,000 200,000 200,000 — —
5000 200,000 200,000 200,000 — —
Copper
Ampere Rating Percent Power Factor
0 10 20 30 40 50 60 70 80 90 100
225 Plug-in .235 .275 .31 .34 .375 .4 .425 .445 .455 .46 .40
Feeder .47 .55 .62 .68 .75 .80 .85 .89 .91 .92 .80
400 Plug-in .415 .485 .55 .615 .67 .72 .765 .80 .825 .825 .725
Feeder .83 .97 1.10 1.23 1.34 1.44 1.53 1.60 1.65 1.65 1.45
600 Plug-in .625 .735 .835 .935 1.025 1.105 1.175 1.235 1.27 1.28 1.13
Feeder 1.25 1.47 1.67 1.87 2.05 2.21 2.35 2.47 2.54 2.56 2.26
800 Plug-in .83 .99 1.13 1.27 1.40 1.52 1.62 1.70 1.76 1.79 1.59
Feeder 1.66 1.97 2.26 2.53 2.79 3.03 3.24 3.40 3.52 3.57 3.18
1000 Plug-in .82 .97 1.10 1.22 1.33 1.44 1.53 1.60 1.65 1.66 1.45
Feeder 1.64 1.93 2.19 2.43 2.66 2.88 3.06 3.19 3.29 3.31 2.90
1200 Plug-in .81 .95 1.08 1.21 1.32 1.43 1.52 1.59 1.64 1.65 1.45
Feeder 1.61 1.90 2.16 2.41 2.64 2.85 3.03 3.17 3.27 3.29 2.90
1350 Plug-in .77 .91 1.04 1.16 1.27 1.37 1.46 1.53 1.58 1.59 1.41
Feeder 1.54 1.81 2.07 2.31 2.53 2.74 2.92 3.06 3.16 3.18 2.81
1600 Plug-in .70 .83 .95 1.06 1.16 1.26 1.34 1.41 1.46 1.48 1.31
Feeder 1.39 1.65 1.89 2.11 2.32 2.52 2.68 2.82 2.91 2.95 2.62
2000 Plug-in .67 .80 .92 1.04 1.14 1.24 1.33 1.40 1.45 1.47 1.31
Feeder 1.34 1.60 1.84 2.07 2.28 2.48 2.65 2.79 2.89 2.93 2.62
2500 Plug-in .58 .70 .81 .91 1.01 1.10 1.18 1.25 1.30 1.32 1.20
Feeder 1.15 1.39 1.61 1.82 2.01 2.20 2.36 2.49 2.59 2.64 2.39
3200 Plug-in .81 .93 1.04 1.14 1.23 1.32 1.38 1.43 1.46 1.45 1.23
Feeder 1.61 1.85 2.07 2.27 2.46 2.63 2.76 2.86 2.92 2.89 2.46
4000 Plug-in .84 .96 1.08 1.19 1.29 1.38 1.46 1.51 1.54 1.54 1.31
Feeder 1.67 1.92 2.16 2.38 2.58 2.76 2.91 3.02 3.08 3.07 2.62
5000 Plug-in .72 .83 .94 1.04 1.14 1.22 1.29 1.35 1.38 1.38 1.20
Feeder 1.43 1.66 1.88 2.08 2.27 2.44 2.58 2.69 2.76 2.76 2.39
Aluminum
Ampere Rating Percent Power Factor
0 10 20 30 40 50 60 70 80 90 100
225 Plug-in .23 .305 .38 .45 .515 .585 .645 .70 .75 .79 .77
Feeder .46 .61 .76 .90 1.03 1.17 1.29 1.40 1.50 1.58 1.54
400 Plug-in .405 .545 .68 .81 .935 1.055 1.17 1.275 1.37 1.44 1.41
Feeder .81 1.09 1.36 1.62 1.87 2.11 2.34 2.55 2.74 2.88 2.81
600 Plug-in .61 .83 1.05 1.26 1.47 1.67 1.85 2.02 2.18 2.31 2.28
Feeder 1.21 1.66 2.10 2.52 2.93 3.33 3.70 4.04 4.35 4.61 4.55
800 Plug-in .69 .87 1.04 1.21 1.37 1.52 1.66 1.78 1.88 1.95 1.85
Feeder 1.37 1.73 2.08 2.41 2.73 3.03 3.31 3.55 3.76 3.90 3.69
1000 Plug-in .73 .92 1.11 1.29 1.46 1.62 1.77 1.90 2.02 2.09 1.99
Feeder 1.45 1.84 2.21 2.57 2.91 3.24 3.54 3.80 4.03 4.18 3.97
1200 Plug-in .67 .85 1.02 1.18 1.84 1.49 1.63 1.75 1.85 1.93 1.83
Feeder 1.33 1.69 2.03 2.36 9.68 2.98 3.25 3.50 3.70 3.85 3.65
1350 Plug-in .58 .74 .89 1.04 1.18 1.31 1.44 1.55 1.64 1.71 1.63
Feeder 1.15 1.47 1.78 2.07 2.36 2.62 2.87 3.09 3.28 3.41 3.25
1600 Plug-in .60 .78 .94 1.10 1.25 1.39 1.52 1.64 1.74 1.82 1.73
Feeder 1.20 1.55 1.87 2.19 2.49 2.78 3.04 3.28 3.48 3.63 3.46
2000 Plug-in .59 .63 .93 1.09 1.24 1.39 1.53 1.65 1.76 1.83 1.76
Feeder 1.18 1.25 1.86 2.18 2.48 2.78 3.05 3.29 3.51 3.66 3.51
2500 Plug-in .60 .75 .89 1.03 1.16 1.29 1.40 1.50 1.58 1.64 1.54
Feeder 1.19 1.49 1.78 2.05 2.32 2.57 2.80 2.99 3.16 3.27 3.07
3200 Plug-in .63 .79 .94 1.09 1.23 1.36 1.48 1.58 1.67 1.73 1.63
Feeder 1.26 1.58 1.88 2.17 2.45 2.71 2.96 3.16 3.34 3.46 3.25
4000 Plug-in .66 .83 1.00 1.15 1.31 1.45 1.58 1.70 1.80 1.86 1.76
Feeder 1.31 1.66 1.99 2.30 2.61 2.89 3.16 3.39 3.59 3.72 3.52
Busway Cutler-Hammer
C2-26 Low-Voltage Busway – Pow-R-Way III May 2001
Technical Data
Typical Specifications
1. Ratings B. Bus bars shall be insulated over their entire plug-in units shall be provided at each
length, except at joints and contact surfaces, plug-in opening to facilitate unit alignment
A. The busway shall be Cutler-Hammer type
with a CSA and UL listed insulating material and prevent improper installation.
Pow-R-Way III:
consisting of epoxy applied by fluidized bed
B. Where required, plug-in units of the types
[3-phase, 3-wire with 50% housing ground process. Tape or heat-shrink sleeve insula-
and ratings indicated on the plans and
and optional 50% internal ground] tion, or any other method of insulation
specifications shall be supplied. Plug-in
which can allow air-gaps or insulation
[3-phase, 3-wire with 50% housing ground units shall be mechanically interlocked
breakdown, shall not be acceptable.
and optional 50% isolated ground] with the busway housing to prevent their
C. The busway shall be capable of carrying installation or removal while the switch is
[3-phase, 4-wire with 100% neutral, rated current continuously without exceed- in the ON position. The enclosure of any
50% housing and optional 50% internal ing a temperature rise of 55 degrees C plug-in unit shall make positive ground
ground] based on a 40 degrees C ambient. connection to the duct housing before the
stabs make contact with the bus bars. All
[3-phase, 4-wire with 100% neutral, 4. Bus Joints
plug-in units shall be equipped with a
50% housing and optional 50% isolated A. Each busway section shall be furnished defeatable interlock to prevent the cover
ground] complete with joint hardware and covers. from being opened while the switch is in
[3-phase, 4-wire with 200% neutral] The busway joints shall be a single-bolt, the ON position and to prevent accidental
non-rotating, removable bridge design. All closing of the switch while the cover is
[3-phase, 4-wire with 200% neutral, bridge joints shall be furnished with open. The plugs shall be provided with a
50% housing ground and optional torque-indicating double head joint bolts means for padlocking the cover closed and
and Belleville washers. The bridge joint padlocking the disconnect device in the
50% internal ground] shall utilize a captive nut retainer on the OFF position. The operating handle and
[3-phase, 4-wire with 200% neutral, opposite side of the torque indicating bolt. mechanism shall remain in control of the
50% housing ground and optional The bridge joint design shall ensure disconnect device at all times, permitting
50% isolated ground] proper installation without the use of a its easy operation from the floor by means
torque wrench, and provide visual indica- of a hookstick or chain. Plug-in units shall
with voltage and current ratings as tion that the joint is properly torqued. Each be equipped with a means for direct posi-
indicated on the contract drawings. busway joint shall allow for a minimum tioning or hanging, so that the weight is
B. The busway shall, have a minimum of length adjustment of +/- 0.5 inches. De- borne by the duct before the stabs make
6-cycle short-circuit rating of 85 kA RMS energization of busway shall not be contact with the bus bars. For safety rea-
symmetrical for ratings through 800A, 100 required for safe testing of joint tightness. sons, no projections shall extend into the
kA RMS symmetrical for ratings through 5. Housing busway housing other than the plug-in
1350A, 125 kA RMS symmetrical for rat- stabs. All plug-in units shall be inter-
ings through 1600A, 150 kA RMS symmet- A. The busway housing shall be a 2-piece changeable without alteration or modifica-
rical ratings through 2500A, and 200 kA design fabricated from extruded aluminum. tion of plug-in duct.
RMS symmetrical for ratings through The 2-piece housing shall be bolted
together along the bottom flange using C. Fusible-type plugs shall have a quick-
5000A. make/quick-break disconnect switch and
grade 5, 1/4x20 zinc-plated fasteners on
2. Construction 3-inch centers for maximum mechanical positive pressure fuse clips
A. The busway and associated fittings shall strength. The busway enclosure finish shall – OR –
consist of [aluminum] [copper] conductors be ANSI 61 gray baked epoxy powder paint
C. Circuit breaker-type plugs shall have an
totally enclosed in a 2-piece extruded alumi- applied by an electrostatic process.
interrupting rating of not less than ____
num housing. Outdoor feeder, indoor feeder B. Outdoor feeder busway housing shall be symmetrical RMS amperes or be series-
and indoor plug-in busway shall be inter- identical to indoor feeder busway hous- rated as otherwise shown in the contract
changeable at the same rating without the ings, and shall be UL listed for outdoor document and shall meet all requirements
use of adapters or special splice plates. use. Busway shall be completely weather- of UL Standard 489. It shall be possible to
Where indicated on the drawings, provide ized at the factory, and designed such that increase the interrupting rating of a
indoor, sprinkler-proof plug-in busway. Out- only protective joint covers are required breaker plug-in device having ampere rat-
door designs requiring addition of caulking for outdoor application. ings through 400A up to 100 kAIC at 480
or gasketing in the field are not acceptable. Vac and 200 kAIC at 240 Vac by changing
Fittings such as – elbows, tees, flanges, etc. – 6. Plug-in Busway
out the circuit breaker only and leaving the
shall be identical for use with both the plug- A. Where required, busway shall be of the enclosure intact. All breaker plug-in
in and feeder types of busway. The busway plug-in type. Plug-in busway shall be avail- devices shall be Cutler-Hammer type
shall be capable of being mounted flatwise, able in standard 2-, 4-, 6-, 8-, and Series C.
edgewise, or vertically without derating. The 10-foot lengths, with plug-in openings pro-
busway shall consist of standard 10-foot sec- vided on both sides of the busway sec- D. Current-limiting circuit breaker-type plug-
tions with special sections and fittings pro- tions on 24-inch centers. Plug-in in devices shall be units which provide
vided to suit the installation. Horizontal runs covers shall prohibit dirt and debris from integral time delay/thermal trip protection
shall be suitable for hanging on 10-foot max- entering contact plug-in openings in the and current-limiting protection in one
imum centers. Vertical runs shall be suitable busway. The design shall allow for ten (10) assembly. These breakers shall be UL
for mounting on 16-foot maximum centers. hinged cover outlets per ten (10) feet of rated at 200 kAIC at 240 Vac, and 150 kAIC
Provide one (1) hanger for every ten (10) feet plug-in length, and covers shall be field- at 480 Vac, and shall be series-rated to pro-
of horizontally mounted duct. On vertical convertible to hinge on either side. Covers tect all molded case breakers downstream
runs provide one adjustable hanger per for plug-in openings shall have a positive as shown on the drawings.
floor. screw close feature and provisions for 7. Transient Voltage Surge Suppression
3. Bus installation of power company seals. The
A. Provide transient voltage surge sup-
contact surfaces for bus plug stabs shall
A. Bus bars shall be fabricated from high pression.
be silver-plated of the same material, thick-
strength, [55% conductivity aluminum] ness, and rating as the phase bars. The B. Refer to the TVSS Bus Plug, Clipper
[98% conductivity copper] and suitably tabs shall be welded to the busbars. A Power Systems Selection Chart page C2-
plated at all electrical contact surfaces. standard silver-plated housing ground 27 and select the TVSS as required.
connection shall be supplied in each plug-
in opening. Positive mechanical guides for