You are on page 1of 28

Cutler-Hammer Busway

C2-1
May 2001 Low-Voltage Busway – Pow-R-Way III
General Description

Pow-R-Way III Joint Design

General Standards
Cutler-Hammer Pow-R-Way III is a 600 volt, Pow-R-Way III meets the requirements of fied in both the Uniform Building Code and
totally enclosed, non-ventilated, sandwich NEMA, UL 857, CSA C22.2 NO. 27-94, IEC 439- California Building Code. The seismic capa-
bus design available with copper bus bars in 1, 2 and 4, IEC 529 and IEC 947-1, IEEE, ANSI bility of Pow-R-Way III exceeds the worst-
ratings from 225 to 5000 amperes or with alu- and is manufactured in an ISO 9002 certified case Zone 4 required levels.
minum bus bars from 225 to 4000 amperes. facility. Pow-R-Way III complies with British
Pow-R-Way III is available in outdoor feeder, Standard 5490 for protection against ingress
indoor feeder, indoor plug-in and indoor of foreign bodies, 12 mm or larger, at the
sprinkler-proof configurations. All four types plug-in opening (Finger Safe) and is rated as
can be used interchangeably without adapt- IP2X. Pow-R-Way III complies with IEC 529,
ers or special splice plates provided they are and is self certified to IP40, IP43 and IP54 for
of the same current and system rating. The plug-in bus and IP40, IP43, IP54 and IP56 for
short circuit withstand ratings for plug-in feeder bus. Pow-R-Way III is also certified for
busway are equal to those of indoor and Seismic Withstand Capability in accordance
outdoor feeder busway. with the earthquake requirements as speci-

Figure 1: Conductor Configurations

Pow-R-Way III Designations for Available Conductor Configurations Including Grounding and Neutral Options (see Figure 1)
3WG 3-Phase, 3-Wire, 50% Internal Ground 4WG 3-Phase, 4-Wire, 50% Internal Ground, 100% Neutral
3WI 3-Phase, 3-Wire, 50% Isolated Internal Ground 4WI 3-Phase, 4-Wire, 50% Isolated Internal Ground, 100% Neutral
3WH 3-Phase, 3-Wire, 50% Integral Housing Ground 4WH 3-Phase, 4-Wire, 50% Integral Housing Ground, 100% Neutral
3WHG 3-Phase, 3-Wire, 100% Ground➀ 4WHG 3-Phase, 4-Wire, 100% Ground➀, 100% Neutral
4WNG 3-Phase, 4-Wire, 50% Internal Ground, 200% Neutral
4WNI 3-Phase, 4-Wire, Isolated Internal Ground, 200% Neutral
4WNH 3-Phase, 4-Wire, 50% Integral Housing Ground, 200% Neutral
➀ 100% Ground consists of the 50% integral hous- 4WNHG 3-Phase, 4-Wire, 100% Ground➀, 200% Neutral
ing ground combined with a 50% internal ground
bus.
Busway Cutler-Hammer
C2-2 Low-Voltage Busway – Pow-R-Way III May 2001

General Description

Pow-R-Bridge (Figure 2) By releasing the bridge joint retainer screw, the Outdoor Pow-R-Bridge (Figure 2a)
Pow-R-Way III joint connections are made Pow-R-Bridge can provide an adjustment of Joint connections for outdoor feeder busway
with the Pow-R-Bridge joint package which is 1-inch (25.4 mm) at each joint. Over adjustment are made with a weatherized version of the
installed on each section of busway prior to is prevented by the joint covers, which will only Pow-R-Bridge joint. Aluminum water barriers,
shipment. A double headed, torque indicating allow a 1-inch adjustment to be made and by 1/16-inch thick, are provided across the “T” and
bolt is provided to ensure that proper installa- stopping lances on the conductor bars of the “T opposite” sides of both joint ends on each
tion torque is achieved. Fall-away instruction Pow-R-Bridge. The non-rotating design of section of outdoor busway. Closed cell, neo-
tags are furnished on the torque indicating the Pow-R-Bridge maintains its configuration prene gaskets are applied to the top of each
bolt heads to allow for visual inspection from integrity when it has been removed from a sec- water barrier and to the inside of the aluminum
a distance. When the proper torque value is tion of busway. The conductors and insulators side access covers. The aluminum side access
achieved, the top bolt head will shear off and will not displace or swivel, making reinstalla- covers overlap the top and bottom access cov-
allow the tag to fall to the floor. Any joint that tion of the Pow-R-Bridge quick and easy. ers and bolt directly onto the end blocks. Thus,
is improperly torqued will retain the highly the completed outdoor joint has a water-resis-
visible (caution yellow) tag at the bolt head. tant enclosure assembled around it. The out-
door Pow-R-Bridge has the same 1-inch (25.4
mm) adjustibility and features as the indoor
unit, is CSA and UL listed, and meets the IEC re-
quirements for IP56 applications. No field gas-
keting or caulking is required.

Figure 2: Pow-R-Bridge Features

Figure 2a: Outdoor Bridge Joint Features


Cutler-Hammer Busway
C2-3
May 2001 Low-Voltage Busway – Pow-R-Way III
General Description

Construction Details (Figure 3)


Conductor/Insulation System
Bus bars are fabricated from high strength,
98% conductivity copper or 55% conductivity
aluminum. The joint edge of each busway con-
ductor bar is beveled while the Pow-R-Bridge
conductor bars have full rounded edges. This
makes for a smooth and easy connection be-
tween the busway and Pow-R-Bridge joint. The
phase and neutral bars are insulated with Class
B 130°C epoxy insulation. The epoxy powder is
applied by an automated fluidized bed process
to ensure uniform thickness. The epoxy pow-
der is applied over the full length of the pre-
heated bar except for the joint and plug-in
contact surfaces. After the powder has been
fused to the bus bar, the bars enter an oven to
cure. This process ensures that all of the epoxy
powder cross links and hardens to the bus bar.

Fluidized bed applied epoxy is non-hygroscop-


ic and chemical resistant. Epoxy has outstand-
ing heat transfer characteristics and is ideally
suited for sandwich bus applications. The uni-
form thickness and smooth surface provided
by epoxy ensures that the insulation will have
no cavities or voids and also provides excellent
edge coverage to the bars. Epoxy has excellent
dielectric strength, is flame retardant and
resists impacts that other Class B insulating
material could not withstand. Figure 3: Housing Assembly

Bus bars for plug-in applications have full bottom sides only, below the bus bars with are furnished with ground path contact s
sized welded conductor tabs at the contact high tensile strength zinc plated hardware. urfaces on the inside of each end. When the
location points of the plug-in outlet. The tabs No fastening bolts or screws penetrate the covers are installed, the contact surfaces are
are of the same exact thickness as the con- housing or enter the bus bar package. bolted directly to the ground path end blocks
ductor bars. The plug-in conductor tabs with four 3/8-16 1/2-inch hex bolts per cover.
extend into the plug-in outlet, maintaining Pow-R-Way III achieves the highest 6-cycle
a true sandwich design throughout the entire short circuit withstand ratings available in A highly visible label is furnished on each
busway length. the industry today. The non-magnetic, all- joint cover to alert the installer that the
aluminum housing provides for excellent covers must be properly installed to maintain
The result is improved heat dissipation, heat dissipation and a significant reduction the ground path. The result is a 50% ground
better bracing and elimination of the need to in reactance and magnetic flux leakage as path that assures ground continuity with very
separate, or flare, the conductor bars at the compared to a steel or steel and aluminum low resistance characteristics.
plug-in opening. Maintaining a true sandwich combination housing. The integrity and
design also eliminates potential pathways for strength of the housing assures specifiers 200% Neutral Option
the propagation of flame, smoke and gas and users of a safe and durable installation Pow-R-Way III offers a fully rated, 200%
through the busway housing, commonly over a broad spectrum of industrial and neutral bus option for busway fed distribution
referred to as “chimney effect.” commercial applications. systems with non-linear loads. The additional
neutral capacity prevents the overheating
Silver plating is applied to all joint and con- A protective finish of ANSI 61, epoxy powder caused by zero sequence harmonic currents.
tact surfaces after the fluidized bed epoxy is paint is applied to the inside and outside sur- The Pow-R-Way III 200% neutral is manufac-
applied. Aluminum bus bars are silver plated faces by an automated electrostatic process. tured with a single 1/2-inch thick bus bar
by the ALSTAN 88C process. Copper bus bars which receives the same silver plating and
are plated with silver by a flashing process. Internal Ground Class B, 130°C Epoxy insulation as the phase
The silver plating of the conductor tabs pro- Pow-R-Way III offers a 50% ground bus bars.
vides an extremely durable contact surface (copper or aluminum) that is internal to the
for the spring loaded connections of bus plug busway. Isolated Ground Option
stab assemblies. To meet the growing demand for grounding
Integral Ground isolation, Pow-R-Way III offers a 50% isolated
Housing Details (Figure 3) The two-piece, extruded aluminum housing ground bus that is insulated and internal to
Pow-R-Way III is constructed with a rugged is designed, manufactured and UL listed as a the busway. This option is available for
two-piece extruded aluminum housing. Pow- 50% integral ground path (integral earth) and application to operations with heavy micro-
R-Way III is designed to prohibit the entry of is fully fault rated. The system ground conti- processor-based loads or large computer
dirt and moisture. There are no seams or nuity is maintained through each joint by the installations where grounding isolation is
welds across the top or bottom sides of the ground path end blocks, ground path plates essential.
housing. The housing is bolted along the and joint covers. The aluminum joint covers
Busway Cutler-Hammer
C2-4 Low-Voltage Busway – Pow-R-Way III May 2001

General Description

Plug-in Protective Devices


All Pow-R-Way III plug-in units are designed
with the safety of the installer and user as the
key criteria. The following features are stan-
dard for both fusible and circuit breaker type
plug-in units:

Pow-R-Way III bus plugs have extended


ground and neutral bars which bring the
termination points down into the cable entry
area making for a safer, easier connection.

A barrier is provided over the line side


connections from the bus plug stab assembly
to the fusible switch or circuit breaker.

The bus plug ground stab makes positive


contact with the busway ground (integral or
internal) before the phase or neutral stabs
contact the bus bars.

A bus plug guide port is provided in the


busway housing, to the right of each plug-in
outlet. A polarizing alignment pin is located
at the line side end of each bus plug enclo-
sure. The alignment pin must be inserted into Figure 4: Typical Circuit Breaker Plug-in Unit
the guide port for proper installation. The
plug-in unit and the busway are interlocked
to ensure that the device is in the “OFF”
position prior to installation or removal of
the unit.

To ensure that the bus plug is seated onto the


busway, the clamping mechanism will draw
the unit tight onto the busway housing as the
installer tightens the clamps.

Plug-in units have an interference bracket


which prevents the cover from being opened
while the device is in the “ON” position and
to prevent accidental closing of the device
while the cover is open.

There are two locations available for field


positioning of the bus plug operating handle.
On vertical bus run applications the handle
can be mounted on the side of the plug and
for horizontal runs the handle can be mount- Figure 5: Plug-in Stab Details
ed on the (line side) end of the unit. Bus plugs
are shipped with the handle mounted on
the side as standard. Mounting positions
are illustrated in Figure 7.

Plug-in outlets are rated for finger safety to


British Standard 5490-IP2X and IEC 529.
These are internationally recognized safety
standards that certify the degree of protec-
tion from accidental contact with a “live” part
by an installer or operator.

As a countermeasure to the effects of thermal


expansion and vibration, the plug-in outlet is
secured to the busway housing with high ten-
sile strength, locking hardware.

When a plug-in unit is installed, the bus plug


stab base assembly engages a seating ridge
provided on the plug-in outlet. The stab base
is drawn in to overlap the ridge and form a
tight seal against moisture and dust.
Figure 6: Plug-in Outlet Details
Cutler-Hammer Busway
C2-5
May 2001 Low-Voltage Busway – Pow-R-Way III
General Description

Plug-in Device Mounting


The load end of a plug-in unit varies with the
orientation of the busway as determined by
the “F” and “T” markings. See illustrations
below.
Preferred Arrangements for Wiring Closets➀➁

CL Plug-in T
F
Plug-in Unit
Opening

B
13⁄16

End View

Wall

4 in.
Minimum

T
Plug-in
C Unit

F
Operating
Plan View Handle

Wall

Two Per ¯ Duct

F Plug-in T
Unit
F
CL

Power Take Off

Bolt-on Unit

Typical Bolt-on with Operating Handle


Power Take Off

Figure 7: Plug-in Device Mounting

➀ See page C2-22 for dimensions of plug-in units.


➁ Clearance in front of plug-in device must be greater
than “A” (page C2-22) to allow 90° door swing.
Busway Cutler-Hammer
C2-6 Low-Voltage Busway – Pow-R-Way III May 2001

General Description

Advanced Bus Plugs IQ Energy Sentinel Bus Plugs Ground Detector/Neutralizer Plug
The IQ Energy Sentinel is a UL listed micro- In rare cases, bus bars in a busway system
Clipper Power Systems TVSS Bus Plug processor-based metering module capable of pick up static electricity. In order to discharge
The Pow-R-Way III plug-in device product communicating energy usage and demand this potential, a neutralizer and ground detec-
offering includes Transient Voltage Surge values over the Cutler-Hammer IMPACC/ tor bus plug is available. The unit has three
Suppression (TVSS) which is ideal for PowerNet power monitoring network. These 18,000 ohm resistors connected between the
busway fed distribution systems. A transient innovative submetering devices are designed bus bars and the ground. Static electricity is
voltage surge can disrupt, damage or destroy to mount directly to Series C molded case discharged through these resistors. A neon
sensitive microprocessor-based equipment. breakers through 400 amperes and are avail- lamp is wired in series with the bus bar and
Cutler-Hammer has developed the Clipper able for universal mounting through 2500 part of the resistor and burns continuously. If
Power System (CPS) family of products to amperes. there is a ground anywhere on the system of
ensure that quality power is supplied to com- a lower resistance than the path through the
mercial, industrial, medical and institutional Digitrip OPTIM Bus Plugs lamp, the lamp will go out, indicating that
facilities. Digitrip OPTIM is a new programmable, there is a short in the system.
communicating, microprocessor-based elec-
The suppression of AC transients is accom- tronic trip unit system for Cutler-Hammer
plished through the utilization of Metal Oxide Series C Circuit Breakers. OPTIM is available for
Varistors (MOVs) which provide a low Pow-R-Way III bus plugs on the L-Frame (70 to
impedance path to divert surges away from 600 ampere) circuit breakers. Digitrip OPTIM
loads. TVSS and filtering reduce MOV stress provides superior programmable protection
resulting in a longer life cycle, lower let and coordination, and state-of-the-art monitor-
through voltage, better noise attenuation ing and communications.
levels and increased reliability. Electrical line
noise and ringing transients are eliminated Combination Starter Bus Plugs
by adding filtering capacitors to the suppres- Plug-in combination starters or contactors
sion device. are mounted in enclosures identical to the cir-
cuit breaker and fusible switch type bus plugs
Since the TVSS unit is directly connected to the including the clamp and guides, safety inter-
busway it is able to minimize let-through volt- locks and guide pin. They are available from
age to loads which are fed from a protected size 0 through 5 with a circuit breaker, motor
busway run. The integrated design of the CPS circuit protector or fusible disconnect. For
bus plug saves the user needed wall space and specific applications and outline dimensions
greatly reduces installed project cost. The CPS refer to Cutler-Hammer.
bus plug is furnished with a fusible disconnect.
Cutler-Hammer Busway
C2-7
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions

Pow-R-Way III Plug-in Busway


Figure 8, Tables A and B
225 to 5000 amperes Copper
225 to 4000 amperes Aluminum

Straight sections of plug-in are made only in


24-inch (609.6 mm.) incremental lengths with
a maximum length of 10 feet (3048 mm). Fig-
ure 8 depicts the configuration of plug-in
busway and Pow-R Bridge for the available
ampere ratings. See Table A for reference to
the proper configuration.

Table A. Configurations
Ampere Rating Figure
Cu Al
225 225 A
400 400 A
600 600 A
800 800 A
1000 1000 A
1200 1200 A
1350 1350 A
1600 — A
2000 — A
— 1600 B
2500 2000 B
3200 — C
4000 2500 C
— 3200 D
5000 4000 D

Table B illustrates the quantity of plug-in


openings per side that are available per stan-
dard section.

Table B. Number of Plug-in Openings


Duct Length Number of Plug-in Openings
Inches mm Front Back
24 610 1 1
48 1219 2 2
72 1829 3 3
96 2438 4 4
120 3048 5 5

Each section will include one, factory installed,


Pow-R-Bridge mounted to the left end of the
busway (with the Top “T” label to the top,
when viewing the bus from the “F” front side).
Each Pow-R-Bridge will have a “T” label which
must always match the “T” orientation of the
busway.

Plug-in Outlet
The plug-in outlets are rated for finger safety
to IP2X in accordance with IEC 529 and British Figure 8: Plug-in Busway
Standard 5490. These are internationally rec- tion. The plug-in cover is designed to protect As a countermeasure to the effects of thermal
ognized safety standards that ensure the de- the contact surfaces and prevent the entry of expansion and mechanical vibration, the plug-
gree of protection from accidental contact of dirt, dust or moisture. The cover has a posi- in outlet is secured to the busway housing
live parts by an operator or installer. The tive screw close feature that prohibits the with high tensile strength locking hardware.
plug-in outlet and cover are made from a opening of the cover without the use of a tool.
durable, high strength, polycarbonate mate- The cover is also Utility “lead lock” sealable.
rial which is rated as Class B, 130º C, insula-
Busway Cutler-Hammer
C2-8 Low-Voltage Busway – Pow-R-Way III May 2001

Layout Dimensions

Pow-R-Way III Feeder Busway


Figure 9 and Table A
225 to 5000 amperes Copper
225 to 4000 amperes Aluminum

Straight sections of feeder busway can be


supplied in any length, at 1/8-inch (3.18 mm)
increments, from a 21-inch (533.4 mm.)
minimum to a 10-foot (3048 mm.) maximum.
Figure 9 illustrates the configuration of
feeder busway and Pow-R-Bridge for the
available ampere ratings. See Table A for
reference to the proper configuration.

Table A. Configurations
Ampere Rating Figure
Cu Al
225 225 A
400 400 A
600 600 A
800 800 A
1000 1000 A
1200 1200 A
1350 1350 A
1600 — A
2000 — A
— 1600 B
2500 2000 B
3200 — C
4000 2500 C
— 3200 D
5000 4000 D

Each section will include one, factory in-


stalled, Pow-R-Bridge mounted to the left end
of the busway (with the Top “T” to the top,
when viewing the bus from the “F” front side).
Each Pow-R-Bridge will have a “T” label which
must always match the “T”orientation of the
busway.

Figure 9: Feeder Busway


Cutler-Hammer Busway
C2-9
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions

Dimensions – Bus Bar and Housing


3-Wire with No Neutral
Ampere Rating Phase Bar Size Bar Conductor Configuration and Housing Size (Width x Height) Inches (mm) Figure
Cu Al (Depth and Width) Per 50% Integral Housing 50% Internal Ground Bus 50% Internal Isolated ➀
Inches (mm) Phase Ground 3WH 3WHG Ground 3WI
225 225 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.38 (121 x 111) 4.75 x 4.50 (121 x 114) 4.75 x 4.55 (121 x 116) A
400 400 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.38 (121 x 111) 4.75 x 4.50 (121 x 114) 4.75 x 4.55 (121 x 116) A
600 – .25 x 1.62 (6.35 x 41) 1 4.75 x 4.38 (121 x 111) 4.75 x 4.50 (121 x 114) 4.75 x 4.55 (121 x 116) A
800 600 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.38 (121 x 111) 4.75 x 4.50 (121 x 114) 4.75 x 4.55 (121 x 116) A
1000 – .25 x 2.25 (6.35 x 57) 1 5.38 x 4.38 (137 x 111) 5.38 x 4.50 (137 x 114) 5.38 x 4.55 (137 x 116) A
1200 800 .25 x 2.75 (6.35 x 70) 1 5.88 x 4.38 (149 x 111) 5.88 x 4.50 (149 x 114) 5.88 x 4.55 (149 x 116) A
1350 1000 .25 x 3.25 (6.35 x 83) 1 6.38 x 4.38 (162 x 111) 6.38 x 4.50 (162 x 114) 6.38 x 4.55 (162 x 116) A
1600 1200 .25 x 4.25 (6.35 x 108) 1 7.38 x 4.38 (187 x 111) 7.38 x 4.50 (187 x 114) 7.38 x 4.55 (187 x 116) A
2000 1350 .25 x 5.50 (6.35 x 140) 1 8.64 x 4.38 (219 x 111) 8.64 x 4.50 (219 x 114) 8.64 x 4.55 (219 x 116) A
– 1600 .25 x 6.25 (6.35 x 159) 1 9.40 x 4.38 (239 x 111) 9.40 x 4.50 (239 x 114) 9.40 x 4.55 (239 x 116) A
2500 2000 .25 x 8.00 (6.35 x 203) 1 11.17 x 4.38 (284 x 111) 11.17 x 4.50 (284 x 114) 11.17 x 4.55 (284 x 116) A
3200 – .25 x 4.25 (6.35 x 108) 2 16.14 x 4.38 (410 x 111) 16.14 x 4.50 (410 x 114) 16.14 x 4.55 (410 x 116) B
4000 2500 .25 x 5.50 (6.35 x 140) 2 18.64 x 4.38 (473 x 111) 18.64 x 4.50 (473 x 114) 18.64 x 4.55 (473 x 116) B
– 3200 .25 x 6.25 (6.35 x 159) 2 20.16 x 4.38 (512 x 111) 20.16 x 4.50 (512 x 114) 20.16 x 4.55 (512 x 116) B
5000 4000 .25 x 8.00 (6.35 x 203) 2 23.70 x 4.38 (602 x 111) 23.70 x 4.50 (602 x 114) 23.70 x 4.55 (602 x 116) B

4-Wire with 100% Neutral


Ampere Rating Phase and Neutral Bar Bar Conductor Configuration and Housing Size (Width x Height) Inches (mm) Figure
Cu Al Size (Depth and Width) Per 50% Integral Housing 50% Internal Ground Bus 50% Internal Isolated ➀
Inches (mm) Phase Ground 4WH 4WHG Ground 4WI
225 225 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.38 (121 x 111) 4.75 x 4.50 (121 x 114) 4.75 x 4.55 (121 x 116) A
400 400 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.38 (121 x 111) 4.75 x 4.50 (121 x 114) 4.75 x 4.55 (121 x 116) A
600 – .25 x 1.62 (6.35 x 41) 1 4.75 x 4.38 (121 x 111) 4.75 x 4.50 (121 x 114) 4.75 x 4.55 (121 x 116) A
800 600 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.38 (121 x 111) 4.75 x 4.50 (121 x 114) 4.75 x 4.55 (121 x 116) A
1000 – .25 x 2.25 (6.35 x 57) 1 5.38 x 4.38 (137 x 111) 5.38 x 4.50 (137 x 114) 5.38 x 4.55 (137 x 116) A
1200 800 .25 x 2.75 (6.35 x 70) 1 5.88 x 4.38 (149 x 111) 5.88 x 4.50 (149 x 114) 5.88 x 4.55 (149 x 116) A
1350 1000 .25 x 3.25 (6.35 x 83) 1 6.38 x 4.38 (162 x 111) 6.38 x 4.50 (162 x 114) 6.38 x 4.55 (162 x 116) A
1600 1200 .25 x 4.25 (6.35 x 108) 1 7.38 x 4.38 (187 x 111) 7.38 x 4.50 (187 x 114) 7.38 x 4.55 (187 x 116) A
2000 1350 .25 x 5.50 (6.35 x 140) 1 8.64 x 4.38 (219 x 111) 8.64 x 4.50 (219 x 114) 8.64 x 4.55 (219 x 116) A
– 1600 .25 x 6.25 (6.35 x 159) 1 9.40 x 4.38 (239 x 111) 9.40 x 4.50 (239 x 114) 9.40 x 4.55 (239 x 116) A
2500 2000 .25 x 8.00 (6.35 x 203) 1 11.17 x 4.38 (284 x 111) 11.17 x 4.50 (284 x 114) 11.17 x 4.55 (284 x 116) A
3200 – .25 x 4.25 (6.35 x 108) 2 16.14 x 4.38 (410 x 111) 16.14 x 4.50 (410 x 114) 16.14 x 4.55 (410 x 116) B
4000 2500 .25 x 5.50 (6.35 x 140) 2 18.64 x 4.38 (473 x 111) 18.64 x 4.50 (473 x 114) 18.64 x 4.55 (473 x 116) B
– 3200 .25 x 6.25 (6.35 x 159) 2 20.16 x 4.38 (512 x 111) 20.16 x 4.50 (512 x 114) 20.16 x 4.55 (512 x 116) B
5000 4000 .25 x 8.00 (6.35 x 203) 2 23.70 x 4.38 (602 x 111) 23.70 x 4.50 (602 x 114) 23.70 x 4.55 (602 x 116) B

➀ Refer to Figure 10 on page C2-10 for Figures A


and B.
Busway Cutler-Hammer
C2-10 Low-Voltage Busway – Pow-R-Way III May 2001

Layout Dimensions

Dimensions – Bus Bar and Housing, Continued


4-Wire with 200% Neutral
Ampere Rating Phase Bar Size Bar Conductor Configuration and Housing Size (Width x Height) Inches (mm) Figure
Cu Al (Depth and Width) Per 50% Integral Housing 50% Internal Ground Bus 50% Internal Isolated ➀
Inches (mm)➁ Phase Ground 4WNH 4WNG➂ Ground 4WNI
225 225 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.92 (121 x 125) 4.75 x 5.05 (121 x 128) 4.75 x 5.10 (121 x 130) A
400 400 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.92 (121 x 125) 4.75 x 5.05 (121 x 128) 4.75 x 5.10 (121 x 130) A
600 – .25 x 1.62 (6.35 x 41) 1 4.75 x 4.92 (121 x 125) 4.75 x 5.05 (121 x 128) 4.75 x 5.10 (121 x 130) A
800 600 .25 x 1.62 (6.35 x 41) 1 4.75 x 4.92 (121 x 125) 4.75 x 5.05 (121 x 128) 4.75 x 5.10 (121 x 130) A
1000 – .25 x 2.25 (6.35 x 57) 1 5.38 x 4.92 (137 x 125) 5.38 x 5.05 (137 x 128) 5.38 x 5.10 (137 x 130) A
1200 800 .25 x 2.75 (6.35 x 70) 1 5.88 x 4.92 (149 x 125) 5.88 x 5.05 (149 x 128) 5.88 x 5.10 (149 x 130) A
1350 1000 .25 x 3.25 (6.35 x 83) 1 6.38 x 4.92 (162 x 125) 6.38 x 5.05 (162 x 128) 6.38 x 5.10 (162 x 130) A
1600 1200 .25 x 4.25 (6.35 x 108) 1 7.38 x 4.92 (187 x 125) 7.38 x 5.05 (187 x 128) 7.38 x 5.10 (187 x 130) A
2000 1350 .25 x 5.50 (6.35 x 140) 1 8.64 x 4.92 (219 x 125) 8.64 x 5.05 (219 x 128) 8.64 x 5.10 (219 x 130) A
– 1600 .25 x 6.25 (6.35 x 159) 1 9.40 x 4.92 (239 x 125) 9.40 x 5.05 (239 x 128) 9.40 x 5.10 (239 x 130) A
2500 2000 .25 x 8.00 (6.35 x 203) 1 11.17 x 4.92 (284 x 125) 11.17 x 5.05 (284 x 128) 11.17 x 5.10 (284 x 130) A
3200 – .25 x 4.25 (6.35 x 108) 2 16.14 x 4.92 (410 x 125) 16.14 x 5.05 (410 x 128) 16.14 x 5.10 (410 x 130) B
4000 2500 .25 x 5.50 (6.35 x 140) 2 18.64 x 4.92 (473 x 125) 18.64 x 5.05 (473 x 128) 18.64 x 5.10 (473 x 130) B
– 3200 .25 x 6.25 (6.35 x 159) 2 20.16 x 4.92 (512 x 125) 20.16 x 5.05 (512 x 128) 20.16 x 5.10 (512 x 130) B
5000 4000 .25 x 8.00 (6.35 x 203) 2 23.70 x 4.92 (602 x 125) 23.70 x 5.05 (602 x 128) 23.70 x 5.10 (602 x 130) B

Figure 10

➀ Refer to Figure 10 for Figures A and B.


➁ Neutral bar is 0.5 (12.7) x width shown.
➂ 100% ground available with same dimensions,
which utilizes 50% internal ground and 50%
integral housing ground.
Cutler-Hammer Busway
C2-11
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions

Fittings
There is a fitting to meet every application When making field measurements and All straight lengths and fittings are marked
need: flanges, elbows, offsets, tees, cable tap layouts, it should be remembered that the with a “T” label for TOP and an “F” label for
boxes, weatherheads, transformer connec- dimensions are given from the centerline FRONT. The “T” and “F” locations will also
tions, power take-off sections, reducers, of the Pow-R-Bridge. be noted on the construction, or as-built,
adapter cubicles, expansion joints and end drawings furnished by Cutler-Hammer.
closures. The relationship of fittings to straight lengths When installing the busway, the “T” and “F”
(forward, rearward, upward and downward) markings of each section must match. Fail-
These fittings, along with standard and is illustrated in Figure 11. ure to do so will result in an improper instal-
minimum dimensions, are described on the lation with the phase bars out of sequence.
following pages.

Figure 11: Top (T) and Front (F) Orientation for Fittings
Busway Cutler-Hammer
C2-12 Low-Voltage Busway – Pow-R-Way III May 2001

Layout Dimensions

Traditional Indoor and Outdoor Elbows


Elbows are used to make 90° changes in the Upward and Downward Elbows
direction of busway runs. The four types that Ampere Rating Minimum Leg Lengths (X)
are available are forward, rearward, upward
and downward. See minimum leg lengths Upward Downward
listed for each type in the tables below. All Cu Al Inches mm Inches mm
dimensions are to the centerline of the 225 225 10.00 254.00 13.00 330.20
Pow-R-Bridge.
400 400 10.00 254.00 13.00 330.20
Forward and Rearward Elbows 600 — 10.00 254.00 13.00 330.20
Ampere Rating Minimum Leg Lengths (X) 800 600 10.00 254.00 13.00 330.20
Cu Al Inches mm 1000 — 10.00 254.00 13.00 330.20
225 225 13.00 330.20 1200 800 10.00 254.00 13.00 330.20
400 400 13.00 330.20 1350 1000 10.00 254.00 13.00 330.20
600 — 13.00 330.20 1600 1200 10.00 254.00 13.00 330.20
800 600 13.00 330.20 2000 1350 10.00 254.00 13.00 330.20
1000 — 13.00 330.20 — 1600 10.00 254.00 13.00 330.20
1200 800 13.50 342.90 2500 2000 10.00 254.00 13.00 330.20
1350 1000 13.50 342.90 3200 — 12.00 304.80 13.00 330.20
1600 1200 14.00 355.60 4000 2500 12.00 304.80 13.00 330.20
2000 1350 14.50 368.30 — 3200 12.00 304.80 13.00 330.20
— 1600 15.00 381.00 5000 4000 12.00 304.80 13.00 330.20
2500 2000 16.00 406.40
3200 — 18.50 469.90
4000 2500 19.50 495.30
— 3200 20.50 520.70
5000 4000 22.50 571.50

Figure 12: Traditional Elbows


Cutler-Hammer Busway
C2-13
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions

Corner Joint Elbows Given the complexity of today’s industrial Pow-R-Way III Corner Joint Elbows can solve
When it comes to bends and turns in a bus and commercial distribution systems and the any serious pathway problem and contribute
run, specifiers often face serious limitations. need to coordinate layouts with the HVAC, to successful layouts with minimal space
The leg length of a traditional 90° elbow is plumbing and lighting requirements, space requirements. The Corner Joint Elbow is CSA
limited by the amount of space needed to quickly becomes a critical factor. and UL listed for indoor applications and is
weld or bend bus bars, provide an enclosure also certified for Seismic Withstand Capabili-
around the bars and create a connection to The Pow-R-Way III Corner Joint Elbow can be ty to worst-case, Zone 4 levels.
the adjacent section. In most applications, installed in areas where a traditional 90° turn All dimensions are to the centerline of the
especially with higher ampere ratings, a could never have been accomplished before. Corner Joint Connection.
significant area may be required. It enables plug-in openings to be maximized.
Forward/Rearward
Ampere Dimensions
Rating (X) (Y)
Cu Al Inches mm Inches mm
225 225 .94 23.88 5.38 136.65
400 400 .94 23.88 5.38 136.65
600 — .94 23.88 5.38 136.65
800 600 .94 23.88 5.38 136.65
1000 — 1.25 31.75 5.69 144.53
1200 800 1.50 38.10 5.94 150.88
1350 1000 1.75 44.45 6.19 157.23
1600 1200 2.25 57.15 6.69 169.93
2000 1350 2.88 73.15 7.31 185.67
— 1600 3.25 82.55 7.70 195.58
2500 2000 4.12 104.65 8.57 217.68
3200 — 6.64 168.66 11.07 281.18
4000 2500 7.89 200.41 12.32 312.93
— 3200 8.65 219.71 13.08 332.23
5000 4000 10.42 264.67 14.85 377.19

Ampere Upward Downward


Rating (X) (Y)
Cu Al Inches mm Inches mm
225 225 4.71 119.63 4.35 110.49
400 400 4.71 119.63 4.35 110.49
600 — 4.71 119.63 4.35 110.49
800 600 4.71 119.63 4.35 110.49
1000 — 4.71 119.63 4.35 110.49
Figure 13: Corner Joint Elbows
1200 800 4.71 119.63 4.35 110.49
1350 1000 4.71 119.63 4.35 110.49
1600 1200 4.71 119.63 4.35 110.49
2000 1350 4.71 119.63 4.35 110.49
— 1600 4.71 119.63 4.35 110.49
2500 2000 4.71 119.63 4.35 110.49
3200 — 4.71 119.63 4.35 110.49
4000 2500 4.71 119.63 4.35 110.49
— 3200 4.71 119.63 4.35 110.49
5000 4000 4.71 119.63 4.35 110.49
Busway Cutler-Hammer
C2-14 Low-Voltage Busway – Pow-R-Way III May 2001

Layout Dimensions

Elbow Flanges
Flanges can be supplied on the end of the
right or left leg as required. Minimum leg
lengths are listed in the table below. Typical
uses are for busway entrance into low-
voltage switchgear, low-voltage switch-
boards and molded case circuit breakers.
All dimensions are to the centerline of the
Pow-R-Bridge.
Upward and Downward Elbow Flanges
Forward and Rearward Elbow Flanges Ampere Rating Minimum Dimensions
Ampere Minimum Dimensions Joint Leg, (X) Flange Leg, (Y)
Rating Cu Al Up Down Up Down
Joint Leg, (X) Flange Leg, (Y)
Cu Al Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm
225 225 13.00 330.20 8.75 222.25 225 225 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
400 400 13.00 330.20 8.75 222.25 400 400 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
600 — 13.00 330.20 8.75 222.25 600 — 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
800 600 13.00 330.20 8.75 222.25 800 600 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
1000 — 13.00 330.20 8.75 222.25 1000 — 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
1200 800 13.50 342.90 9.25 235.00 1200 800 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
1350 1000 13.50 342.90 9.25 235.00 1350 1000 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
1600 1200 14.00 355.60 9.75 247.65 1600 1200 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
2000 1350 14.50 368.30 10.25 260.35 2000 1350 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
— 1600 15.00 381.00 10.75 273.05 — 1600 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
2500 2000 16.00 406.40 11.75 298.45 2500 2000 10.00 254.00 13.00 330.20 5.75 146.05 8.75 222.25
3200 — 18.50 469.90 14.00 355.60 3200 — 12.00 304.80 13.00 330.20 7.75 196.85 8.75 222.25
4000 2500 19.50 495.30 15.25 387.35 4000 2500 12.00 304.80 13.00 330.20 7.75 196.85 8.75 222.25
— 3200 20.50 520.70 16.00 406.40 — 3200 12.00 304.80 13.00 330.20 7.75 196.85 8.75 222.25
5000 4000 22.50 571.50 17.75 450.85 5000 4000 12.00 304.80 13.00 330.20 7.75 196.85 8.75 222.25

Figure 14: Elbow Flanges


Cutler-Hammer Busway
C2-15
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions

Offsets
An offset is used to avoid obstacles and
to conform to building structure. It is two
elbows fabricated into a single fitting for
use where space restrictions prohibit the
use of a standard 90° elbow. The minimum
leg lengths are listed in the tables below.
All dimensions are to the centerline of the Upward and Downward Offsets
Pow-R-Bridge.
Ampere Rating Minimum Dimensions
Forward and Rearward Offsets Cu Al Upward Downward
Ampere Rating Minimum Dimensions (Y) (Y) (Z) (Y) (Z)
Cu Al Inches mm Inches mm Inches mm Inches mm Inches mm
225 225 13.00 330.20 225 225 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
400 400 13.00 330.20 400 400 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
600 — 13.00 330.20 600 — 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
800 600 13.00 330.20 800 600 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
1000 — 13.00 330.20 1000 — 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
1200 800 13.50 342.90 1200 800 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
1350 1000 13.50 342.90 1350 1000 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
1600 1200 14.00 355.60 1600 1200 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
2000 1350 14.50 368.30 2000 1350 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
— 1600 15.00 381.00 — 1600 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
2500 2000 16.00 406.40 2500 2000 10.00 254.00 13.00 330.20 13.00 330.20 10.00 254.00
3200 — 18.50 469.90 3200 — 12.00 304.80 13.00 330.20 13.00 330.20 12.00 304.80
4000 2500 19.50 495.30 4000 2500 12.00 304.80 13.00 330.20 13.00 330.20 12.00 304.80
— 3200 20.50 520.70 — 3200 12.00 304.80 13.00 330.20 13.00 330.20 12.00 304.80
5000 4000 22.50 571.50 5000 4000 12.00 304.80 13.00 330.20 13.00 330.20 12.00 304.80

Figure 15: Offsets


Busway Cutler-Hammer
C2-16 Low-Voltage Busway – Pow-R-Way III May 2001

Layout Dimensions

Tees All dimensions are to the centerline of the Pow-R-Bridge.


A tee is a busway fitting suitable for connection in three directions.
The minimum leg lengths are shown in the following tables.

Forward and Rearward Tees Upward and Downward Tees


Ampere Rating Minimum Leg Dimensions Ampere Rating Minimum Leg Dimensions

Cu Al (X) Inches (X) mm (Y) Inches (Y) mm Cu Al (X) Inches (X) mm (Y) Inches (Y) mm
225 225 13.00 330.20 13.00 330.20 225 225 21.25 539.75 25.50 647.70
400 400 13.00 330.20 13.00 330.20 400 400 21.25 539.75 25.50 647.70
600 — 13.00 330.20 13.00 330.20 600 — 21.25 539.75 25.50 647.70
800 600 13.00 330.20 13.00 330.20 800 600 21.25 539.75 25.50 647.70
1000 — 13.00 330.20 13.00 330.20 1000 — 21.88 555.75 25.50 647.70
1200 800 13.50 342.90 13.50 342.90 1200 800 22.38 568.45 25.50 647.70
1350 1000 13.50 342.90 13.50 342.90 1350 1000 22.88 581.15 25.50 647.70
1600 1200 14.00 355.60 14.00 355.60 1600 1200 23.88 606.55 25.50 647.70
2000 1350 14.50 368.30 14.50 368.30 2000 1350 25.12 638.05 25.50 647.70
— 1600 15.00 381.00 15.00 381.00 — 1600 25.88 657.35 25.50 647.70
2500 2000 16.00 406.40 16.00 406.40 2500 2000 27.62 701.55 25.50 647.70
3200 — 27.25 692.15 26.38 670.05 3200 — 23.88 606.55 25.50 647.70
4000 2500 28.50 723.90 27.62 701.55 4000 2500 25.12 638.05 25.50 647.70
— 3200 29.25 792.95 28.38 720.85 — 3200 25.88 637.35 25.50 647.70
5000 4000 31.00 787.40 30.12 765.05 5000 4000 27.62 701.55 25.50 647.70

Figure 16: Tees


Cutler-Hammer Busway
C2-17
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions

End Cable Tap Box


End cable tap boxes are applied to feed a run
of busway with cable and conduit, or where
loads served by busway are connected with-
out the need for overcurrent protection.

Figure 17: End Cable Tap Box

Copper Dimensions Aluminum Dimensions Quantity of Mechanical Terminals, Range – One #4 to


600 kcmil or Two 1/0 to 250 kcmil Cu/Al➁
Copper➂ Aluminum➂
Ampere Rating Dimension Dimension Ampere Rating Dimension Dimension G P N G P N
(A) Inches➀ (A) mm➀ (A) Inches➀ (A) mm➀
225 12.00 304.80 225 12.00 304.80 1 2 4 1 2 4
400 12.00 304.80 400 12.00 304.80 1 2 4 1 2 4
600 12.00 304.80 12.00 304.80 1 2 4 — — —
800 12.00 304.80 600 12.00 304.80 2 3 5 1 2 4
1000 12.00 304.80 — 12.00 304.80 2 3 6 — — —
1200 12.00 304.80 800 12.00 304.80 2 4 8 2 3 5
1350 12.00 304.80 1000 12.00 304.80 2 4 8 2 3 6
1600 20.50 520.70 1200 20.50 520.70 3 5 9 2 4 8
2000 20.50 520.70 1350 20.50 520.70 3 6 12 2 4 8
— — — 1600 24.50 622.30 — — — 3 5 9
2500 24.50 622.30 2000 24.50 622.30 4 8 16 3 6 12
3200 30.50 774.50 — — — 5 9 18 — — —
4000 45.00 1143.00 2500 30.50 774.50 6 12 24 4 8 16
— — — 3200 30.50 774.50 — — — 5 9 18
5000 45.00 1143.00 4000 45.00 1143.00 7 15 30 6 12 24

➀ All dimensions shown in Figure 17 remain con-


stant regardless of system wiring configuration.
➁ Standard 600 kcmil Compression lugs are
available in the same quantities shown for the
mechanical terminals.
➂ G Denotes quantity of terminals per ground bus.
P Denotes quantity of terminals per phase and
100% neutral bus.
N Denotes quantity of terminals per 200% neutral
bus option.
Busway Cutler-Hammer
C2-18 Low-Voltage Busway – Pow-R-Way III May 2001

Layout Dimensions

Center Cable Tap Box


Center cable tap boxes are applied to center
feed a run of busway with cable and conduit,
or where loads served by the busway are
connected without the need for overcurrent
protection.

Figure 18: Center Cable Tap Box

Copper Aluminum Quantity of Mechanical Terminals,


Ampere Dimension Ampere Dimension Range – One #4 to 600 kcmil or Two
Rating Rating 1/0 to 250 kcmil Cu/Al➁
Copper➂ Aluminum➂
(A) Inches➀ (A) mm➀ (B) Inches➀ (B) mm➀ (A) Inches➀ (A) mm➀ (B) Inches➀ (B) mm➀ G P N G P N
225 16.50 419.10 40.00 1016.0 225 16.50 419.10 40.00 1016.0 1 2 4 1 2 4
400 16.50 419.10 40.00 1016.0 400 16.50 419.10 40.00 1016.0 1 2 4 1 2 4
600 16.50 419.10 40.00 1016.0 — 16.50 — 40.00 1016.0 1 2 4 — — —
800 16.50 419.10 40.00 1016.0 600 16.50 419.10 40.00 1016.0 2 3 5 1 2 4
1000 16.50 419.10 40.00 1016.0 — 16.50 — 40.00 1016.0 2 3 6 — — —
1200 16.50 419.10 40.00 1016.0 800 16.50 419.10 40.00 1016.0 2 4 8 2 3 5
1350 16.50 419.10 40.00 1016.0 1000 16.50 419.10 40.00 1016.0 2 4 8 2 3 6
1600 20.50 520.70 42.50 1079.5 1200 20.50 520.70 42.50 1079.5 3 5 9 2 4 8
2000 20.50 520.70 42.50 1079.5 1350 20.50 520.70 42.50 1079.5 3 6 12 2 4 8
— — — — — 1600 24.50 622.30 45.00 1143.0 — — — 3 5 9
2500 24.50 622.30 45.00 1143.0 2000 24.50 622.30 45.00 1143.0 4 8 16 3 6 12
3200 30.38 774.50 58.00 1473.2 — — — — — 5 9 18 — — —
4000 45.00 1143.0 60.50 1536.7 2500 30.38 771.65 58.00 1473.0 6 12 24 4 8 16
— — — — — 3200 30.38 771.65 58.00 1473.0 — — — 5 9 18
5000 45.00 1143.0 60.50 1536.7 4000 45.00 1143.0 60.50 1536.7 7 15 30 6 12 24

C Dimension
Copper Aluminum
225-1350A 1600-2000A 2500A 3200A 4000-5000A 225-1000A 1200-1350A 1600-2000A 2500-3200A 4000A
3.63 In. 4.75 In. 6.00 In. 10.75 In. 12.25 In. 3.63 In. 4.75 In. 6.00 In. 10.75 In. 12.25 In.
92.20 mm 120.65 mm 152.40 mm 273.05 mm 311.15 mm 92.20 mm 120.65 mm 152.40 mm 273.05 mm 311.15 mm

➀ All dimensions in figure 18 remain constant ➂ G Denotes quantity of terminals per ground bus.
regardless of system wiring configuration. P Denotes quantity of terminals per phase and
➁ Standard 600 kcmil compression lugs are avail- 100% neutral bus.
able in the same quantities shown for the mechan- N Denotes quantity of terminals per 200% neutral
ical terminals. bus option.
Cutler-Hammer Busway
C2-19
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions

End Closures
End closures terminate a bus run and can
be used to close either the right or left end.
Refer to page C2-2, Figure 1 for wiring con-
ductor configurations.

Ampere Rating Dimension


Cu Al (A) Inches (A) mm
225 225 5.13 130.30
400 400 5.13 130.30
600 — 5.13 130.30
800 600 5.13 130.30
1000 — 5.75 146.05 Figure 19: End Closure with Pow-R-Bridge Removed.
1200 800 6.25 158.75
1350 1000 6.75 171.45
1600 1200 7.77 197.35
2000 1350 9.02 229.10
— 1600 9.78 248.41
2500 2000 11.55 293.37
3200 — 16.52 419.60
4000 2500 19.02 482.85
— 3200 20.54 521.71
5000 4000 24.08 611.63

Dimension (B)
3WH, 3WG, 3WHG, 4WNH, 4WNG,
3WI, 4WH, 4WG, 4WNI, 4WNHG
4WHG, 4WI
Inches 5.00 5.50
mm 127.00 139.70

Note: End closure extends 0.44 inches


(11.18 mm) beyond the centerline of the
removed Pow-R-Bridge.
Busway Cutler-Hammer
C2-20 Low-Voltage Busway – Pow-R-Way III May 2001

Layout Dimensions

Horizontal Hangers Flatwise Hook Hanger


One hanger is provided for every 10 feet of
Ampere Rating Duct Width Dimension (A)
horizontally mounted busway. The type of
hanger supplied is determined by the specific Cu Al Inches mm Inches mm
mounting requirements of the busway. Types 225 225 4.75 120.65 5.12 130.04
of hook hangers and angle hangers are 400 400 4.75 120.65 5.12 130.04
shown below.
600 — 4.75 120.65 5.12 130.04
Drop rods (1/2-inch diameter) are not included 800 600 4.75 120.65 5.12 130.04
and must be furnished by the installer. Drop 1000 — 5.38 136.65 5.75 146.05
rods (3/4-inch diameter) are required for seis- 1200 800 5.88 149.35 6.25 158.75
mic applications.
1350 1000 6.38 162.05 6.75 171.45
1600 1200 7.38 187.45 7.75 196.85
2000 1350 8.64 219.45 9.03 229.36
— 1600 9.40 238.76 9.78 248.41
2500 2000 11.17 283.71 11.58 294.13

Edgewise Hook Hanger


Conductor Configuration Duct Height Duct Width (A) Inches (A) mm (B) Inches (B) mm
3WH/4WH/3WG/3WHG 4.38-4.56 In., 4.75-6.38 In., 8.40 213.36 4.81 122.17
4WG/4WHG 111-116 mm 121-162 mm
3WI/4WI 4.38-4.56 In., 7.38-11.17 In., 13.19 335.02 4.81 122.17
111-116 mm 187-284 mm
4WNH/4WNG 4.92-5.10 In., 4.75-6.38 In., 8.40 213.36 5.35 135.89
125-130 mm 121-162 mm
4WNHG/4WNI 4.92-5.10 In., 7.38-11.17 In., 13.19 335.02 5.35 135.89
125-130 mm 187-284 mm
Figure 20: Hook Hangers
Flatwise Angle Hanger
Ampere Rating Conductor Busway Width (A)
Copper Aluminum Bars Per Inches mm Inches mm
Phase
225 225 1 4.75 120.65 9.00 228.60
400 400 1 4.75 120.65 9.00 228.60
600 — 1 4.75 120.65 9.00 228.60
800 600 1 4.75 120.65 9.00 228.60
1000 — 1 5.38 136.65 9.63 244.60
1200 800 1 5.88 149.35 10.12 257.04
1350 1000 1 6.38 162.05 10.63 270.00
1600 1200 1 7.38 187.45 11.63 295.40
2000 1350 1 8.64 219.45 12.88 327.15
— 1600 1 9.40 238.76 13.62 345.94
2500 2000 1 11.17 283.71 15.44 392.17
3200 — 2 16.14 409.95 20.39 577.91
4000 2500 2 18.64 473.45 22.88 581.15
— 3200 2 20.16 512.06 24.39 619.50
5000 4000 2 23.70 601.98 28.00 711.20

Edgewise Angle Hanger


Conductor Configuration Duct Height (A) Inches (A) mm
3WH/4WH/3WG/3WHG/4WG/4WHG 4.38-4.56 In., 111-116 mm 9.00 228.60
3WI/4WI
4WNH/4WNG/4WNHG/4WNI 4.92-5.10 In., 125-130 mm 9.36 237.74

Figure 21: Angle Hangers


Cutler-Hammer Busway
C2-21
May 2001 Low-Voltage Busway – Pow-R-Way III
Layout Dimensions

Vertical Hangers This unique hanger equalizes the weight of and UL on vertical hangers is 16 feet.
When busway is to be installed vertically, a vertically mounted busway along all sup- Intermediate hangers are also required for
spring suspension type vertical hanger ports. A vertical hanger must be used on each floor heights exceeding 16 feet.
should be used. Vertical hangers are not floor and at the end of the bus run on the last
provided unless specified. floor. The maximum span permitted by CSA

Conductor Configuration Busway Height Hangers on “F” and “F” Opposite Sides
Inches mm (A) Inches (A) mm (B) Inches (B) mm Illustration Number
3WH/4WH 4.38 111.25 4.72 119.88 4.25 107.95 Figure A & B
3WG/3WHG/4WG/4WHG 4.50 114.30 4.91 124.71 4.44 112.77 Figure A & B
3WI/4WI 4.56 115.82 4.91 124.71 4.44 112.77 Figure A & B
4WHN 4.92 124.96 5.25 133.35 4.79 121.66 Figure A & B
4WNG/4WNHG 5.05 128.27 5.44 138.17 4.97 126.23 Figure A & B
4WNI 5.10 129.54 5.44 138.17 4.97 126.23 Figure A & B

Ampere Rating Busway Width Hangers on “T” and “T” Opposite Sides
Cu Al Inches mm (A) Inches (A) mm Illustration Number
225 225 4.75 120.65 4.62 117.34 Figure C
400 400 4.75 120.65 4.62 117.34 Figure C
600 — 4.75 120.65 4.62 117.34 Figure C
800 600 4.75 120.65 4.62 117.34 Figure C
1000 — 5.38 136.65 5.25 133.35 Figure D
1200 800 5.88 149.35 5.75 146.05 Figure D
1350 1000 6.38 162.05 6.25 158.75 Figure D
1600 1200 7.38 187.45 7.25 184.15 Figure D
2000 1350 8.64 219.45 8.50 215.90 Figure D
— 1600 9.40 238.76 9.25 234.95 Figure E
2500 2000 11.17 283.71 11.06 280.92 Figure E
3200 — 16.14 409.95 16.00 406.40 Figure F
4000 2500 18.64 473.45 18.50 469.90 Figure F
— 3200 20.16 512.06 20.06 510.00 Figure F
5000 4000 23.70 601.98 23.59 600.00 Figure F

Figure 22: Vertical Hangers


Busway Cutler-Hammer
C2-22 Low-Voltage Busway – Pow-R-Way III May 2001

Layout Dimensions

Dimensions – Plug-in Units

C
L

Figure 24

Plug-in Unit Max. Max. Ac Dimensions, Inches (mm) Mechanical Terminal Approx.
Amps Volts (A) (B) (C) (D) (E) (F) Wire Range Per Phase (mm2) Wghts.
Lbs. (Kgs)

Circuit Breaker Plug-in Units


P3BFD 225 600 19.26 12.36 5.43 6.25 4.00 6.05 100A – (1) #14 to 1/0 (2.5 to 50) 25
(E- & F-Frame (489) (314) (138) (159) (102) (154) 150A – (1) #4 to 4/0 ( (25 to 95) (11.33)
Breakers)
P3BJD 250 600 21.33 12.36 6.97 10.44 4.00 6.06 250A – (1) #14 to 350 kcmil (25 to 185) 47
(J-Frame Breakers) (542) (314) (177) (265) (102) (154) 225A – (1) 3 to 350 kcmil (35 to 185) (21.31)
P3BKD 400 600 32.50 13.29 7.79 12.56 4.00 6.64 350A – (1) 250 to 500 kcmil (120 to 240) 53
(K-Frame Breakers) (826) (338) (198) (319) (102) (169) 400A – (2) 3/0 to 250 kcmil (45 to 120) (24.04)
P3BLD 600 600 44.03 19.65 10.15 17.38 4.00 9.83 400A – (1) 4/0 to 600 kcmil (120 to 300) 75
(L-Frame Breakers) (1118) (499) (258) (441) (102) (250) 600A – (2) 400 to 500 kcmil (185 to 240) (34.01)
P3BMD 800 600 44.03 19.65 10.15 17.38 4.00 9.83 600A – (2) #1 to 500 kcmil (50 to 240) 136
(M-Frame Breakers) (1118) (499) (258) (441) (102) (250) 800A – (2) 500 to 750 kcmil (300 to 400) (61.68)
P3BND 800 600 44.03 19.65 10.15 17.38 4.00 9.83 700A – (2) # 1 to 500 kcmil (50 to 240) 138
(N-Fame Breakers) (1118) (499) (258) (441) (102) (250) 800A – (3) 3/0 to 400 kcmil ( (95 to 185) (62.59)
P3BLAP 400 600 44.03 19.65 10.15 13.80 4.00 9.83 225A – (1) #6 to 350 kcmil (16 to 185) 96
(Tri-Pac) (1118) (499) (258) (357) (102) (249) 400A – (1) #4 to 250 kcmil and (1) 3/0 to (43.54)
600 kcmil (25 to 120 and 95 to 300)
P3BLCL 400 600 40.00 19.65 10.15 13.80 4.00 9.83 (+)#4 to 250 kcmil (25 to 120) plus 88
(1016) (499) (258) (351) (102) (249) (r)3/0 to 600 kcmil (95 to 300) (39.91)

Fusible Plug-in Units


P3F321R and 30 240 20.85 12.36 5.43 7.88 4.00 6.06 Cu – (1) #14 to #3, (2.5 to 35) 22
P3F361R 600 (530) (314) (138) (200) (102) (154) Al – (1) #12 to #2 (3.2 to 35) (9.98)

P3F322R and 60 240 20.85 12.36 5.43 7.88 4.00 6.06 Cu – (1) #14 to #3, (2.5 to 35) 24
(530) (314) (138) (200) (102) (154) Al – (1) #12 to #2 (3.2 to 38) (10.88)
P3F362R 600 Cu – (1) #14 to 1/0 (2.5 to 50)
Al – (1) #12 to 1/0 (3.2 to 50)
P3F323R and 100 240 20.85 12.36 5.43 7.88 4.00 6.06 Cu – (1) #14 to 1/0, (2.5 to 50) 24
P3F363R (530) (314) (138) (200) (102) (154) Al – (1) #12 to 1/0 (3.2 to 50) (10.88)
600 (1) # 4 to 250 kcmil Cu/Al (25 to 120)
P3F324R and 200 240 23.52 15.57 7.19 8.20 4.00 7.63 (1) # 4 to 250 kcmil Cu/Al (25 to 120) 47
(597) (395) (183) (208) (102) (194) (21.31)
P3F364R 600 (1) #4 to 600 kcmil Cu/Al (25 to 300)
or (2) 250 kcmil (120)
P3F325R and 400 240 46.94 21.22 10.07 12.67 4.00 10.69 (2) #2 to 600 kcmil Cu/Al (35 to 300) 77
P3F365R 600 (1192) (539) (256) (322) (102) (272) (34.92)

P3F365H 400 600 23.47 21.22 21.00 12.67 4.00 10.69 (2) #2 to 600 kcmil Cu/Al (35 to 300) 81
(596) (539) (533) (322) (102) (272) (36.74)
P3F326R and 600 240 46.94 26.31 10.59 14.26 4.00 13.16 (2) #2 to 600 kcmil Cu/Al (35 to 300) 82
P3F366R 600 (1192) (669) (270) (362) (102) (334) (3) #4 to 600 kcmil Cu/Al (25 to 300) (37.19)

P3F327R and 800 240 46.94 26.31 10.59 14.26 4.00 13.16 (3) #4 to 600 kcmil Cu/Al (25 to 300) 108
P3F367R 600 (1192) (669) (270) (362) (102) (334) (48.98)
Cutler-Hammer Busway
C2-23
May 2001 Low-Voltage Busway – Pow-R-Way III
Technical Data

Plug-in Protective Devices, Circuit Breaker Selection and Interrupting Ratings Chart
Breaker Frame Ampere Rating 240 Vac 480 Vac 600 Vac
Symmetrical Symmetrical Symmetrical
Amperes Amperes Amperes
ED 100-225 65,000
EDH 100-225 100,000
EDC 100-225 200,000
EHD 15-100 18,000 14,000
FDB 15-100 18,000 14,000 14,000
FD 15-225 65,000 25,000 18,000
HFD 15-225 100,000 65,000 25,000
FDC 15-225 200,000 100,000 35,000
JDB, JD 70-250 65,000 25,000 18,000
HJD 70-250 100,000 65,000 25,000
JDC 70-250 200,000 100,000 35,000
DK 250-400 65,000
KDB 250-400 65,000 35,000 25,000
KD, CKD➀ 250-400 65,000 35,000 25,000
HKD, CHKD➀ 250-400 100,000 65,000 35,000
KDC 250-400 200,000 100,000 50,000
LDB 300-600 65,000 35,000 25,000
LD, CLD➀ 300-600 65,000 35,000 25,000
HLD, CHLD➀ 300-600 100,000 65,000 35,000
LDC, CLDC➀ 300-600 200,000 100,000 50,000
MD 400-800 42,000 35,000 22,000
MDS 400-800 42,000 35,000 22,000
MDSC➁ 400-800 42,000 35,000 22,000
ND➂ 600-1200 65,000 50,000 25,000
HND➂ 600-1200 100,000 65,000 35,000
NDC➂ 600-1200 200,000 100,000 50,000
Current Limiting Breakers
LA Tri-Pac 70-400 200,000 200,000 200,000

Fusible Switch Horsepower and Short Circuit Ratings (based on fuse class)
Ampere 240 Volts 480 Volts 600 Volts
Rating NEC Standard Maximum Max. Sym. NEC Standard Maximum Max. Sym. NEC Standard Maximum Max. Sym.
RMS @ Fuse RMS @ Fuse RMS @ Fuse
Class Class Class
30 3 7.5 200kA - R 5 15 200kA - R 7.5 20 200kA - R
60 7.5 15 200kA - R 15 30 200kA - R 15 50 200kA - R
100 15 30 200kA - R 25 60 200kA - R 30 75 200kA - R
200 25 60 200kA - R 50 125 200kA - R 60 150 200kA - R
400 50 125 200kA - R 100 250 200kA - R 125 350 200kA - J
600 75 200 200kA - R 150 400 200kA - J 200 500 200kA - J
800 100 250 200kA - L 200 500 200kA - L 250 500 200kA - L

➀ Indicates 100% rated breaker. Contact the Product ➂ Plug-in units available up to 800 amperes. Above
Line for application Information. 800 amperes only available in built-in or bridge
➁ Indicates 100% rated breaker available for built-in joint power take-off or bolt-on unit.
or bridge joint Power Take-off/Bolt-on units only,
from 800 amperes and above. Contact the
Product Line for application Information.
Busway Cutler-Hammer
C2-24 Low-Voltage Busway – Pow-R-Way III May 2001

Technical Data

Short Circuit Rating

Aluminum
Ampere 6-Cycle RMS Symmetrical IEC 439 Short Circuit Maximum Class L Fuse to Achieve
Rating Short Circuit Rating Rating 6-Cycle RMS Series Rating
Plug-in Feeder 1 Second (60 cycles)
Plug-in and Feeder 100 kA 200 kA
225 85,000 85,000 30,000 2000A 1200A
400 85,000 85,000 30,000 2000A 1200A
600 85,000 85,000 30,000 2000A 1200A
800 100,000 100,000 43,000 — 2500A
1000 100,000 100,000 52,000 — 2500A
1200 125,000 125,000 61,000 — 2500A
1350 150,000 150,000 87,000 — 4000A
1600 150,000 150,000 95,000 — 4000A
2000 150,000 150,000 121,000 — 4000A
2500 200,000 200,000 130,000 — —
3200 200,000 200,000 173,000 — —
4000 200,000 200,000 200,000 — —

Copper
Ampere 6-Cycle RMS Symmetrical IEC 439 Short Circuit Class L Fuse Needed to Achieve
Rating Short Circuit Rating Rating 6-Cycle RMS Series Rating
Plug-in Feeder 1 Second (60 cycles)
Plug-in and Feeder 100 kA 200 kA
225 85,000 85,000 43,000 2000 1600
400 85,000 85,000 43,000 2000 1600
600 85,000 85,000 43,000 2000 1600
800 85,000 85,000 43,000 2000 1600
1000 100,000 100,000 55,000 — 3000
1200 100,000 100,000 68,000 — 3000
1350 100,000 100,000 80,000 — 3000
1600 125,000 125,000 97,000 — 3000
2000 150,000 150,000 130,000 — 4000
2500 150,000 150,000 173,000 — 4000
3200 200,000 200,000 182,000 — —
4000 200,000 200,000 200,000 — —
5000 200,000 200,000 200,000 — —

Resistance Values for Integral Housing Ground


(Only) (Milliohms per 100 Feet or 30.5 Meters)
Ampere Aluminum Phase Copper Phase
Rating Conductors Conductors
225 1.04 1.04
400 1.04 1.04
600 1.04 1.04
800 .95 1.04
1000 .92 .99
1200 .85 .95
1350 .72 .92
1600 .68 .85
2000 .61 .72
2500 .36 .61
3200 .34 .43
4000 .30 .36
5000 — .30
Cutler-Hammer Busway
C2-25
May 2001 Low-Voltage Busway – Pow-R-Way III
Technical Data

Line-to-Line Voltage Drop


The tables below give average 3-phase voltage drop per 100 feet (30.48 meters) at rated current and varying power factor. Line-to-neutral
voltage drop is obtained by multiplying the line value by .577.

Copper
Ampere Rating Percent Power Factor
0 10 20 30 40 50 60 70 80 90 100
225 Plug-in .235 .275 .31 .34 .375 .4 .425 .445 .455 .46 .40
Feeder .47 .55 .62 .68 .75 .80 .85 .89 .91 .92 .80
400 Plug-in .415 .485 .55 .615 .67 .72 .765 .80 .825 .825 .725
Feeder .83 .97 1.10 1.23 1.34 1.44 1.53 1.60 1.65 1.65 1.45
600 Plug-in .625 .735 .835 .935 1.025 1.105 1.175 1.235 1.27 1.28 1.13
Feeder 1.25 1.47 1.67 1.87 2.05 2.21 2.35 2.47 2.54 2.56 2.26
800 Plug-in .83 .99 1.13 1.27 1.40 1.52 1.62 1.70 1.76 1.79 1.59
Feeder 1.66 1.97 2.26 2.53 2.79 3.03 3.24 3.40 3.52 3.57 3.18
1000 Plug-in .82 .97 1.10 1.22 1.33 1.44 1.53 1.60 1.65 1.66 1.45
Feeder 1.64 1.93 2.19 2.43 2.66 2.88 3.06 3.19 3.29 3.31 2.90
1200 Plug-in .81 .95 1.08 1.21 1.32 1.43 1.52 1.59 1.64 1.65 1.45
Feeder 1.61 1.90 2.16 2.41 2.64 2.85 3.03 3.17 3.27 3.29 2.90
1350 Plug-in .77 .91 1.04 1.16 1.27 1.37 1.46 1.53 1.58 1.59 1.41
Feeder 1.54 1.81 2.07 2.31 2.53 2.74 2.92 3.06 3.16 3.18 2.81
1600 Plug-in .70 .83 .95 1.06 1.16 1.26 1.34 1.41 1.46 1.48 1.31
Feeder 1.39 1.65 1.89 2.11 2.32 2.52 2.68 2.82 2.91 2.95 2.62
2000 Plug-in .67 .80 .92 1.04 1.14 1.24 1.33 1.40 1.45 1.47 1.31
Feeder 1.34 1.60 1.84 2.07 2.28 2.48 2.65 2.79 2.89 2.93 2.62
2500 Plug-in .58 .70 .81 .91 1.01 1.10 1.18 1.25 1.30 1.32 1.20
Feeder 1.15 1.39 1.61 1.82 2.01 2.20 2.36 2.49 2.59 2.64 2.39
3200 Plug-in .81 .93 1.04 1.14 1.23 1.32 1.38 1.43 1.46 1.45 1.23
Feeder 1.61 1.85 2.07 2.27 2.46 2.63 2.76 2.86 2.92 2.89 2.46
4000 Plug-in .84 .96 1.08 1.19 1.29 1.38 1.46 1.51 1.54 1.54 1.31
Feeder 1.67 1.92 2.16 2.38 2.58 2.76 2.91 3.02 3.08 3.07 2.62
5000 Plug-in .72 .83 .94 1.04 1.14 1.22 1.29 1.35 1.38 1.38 1.20
Feeder 1.43 1.66 1.88 2.08 2.27 2.44 2.58 2.69 2.76 2.76 2.39

Aluminum
Ampere Rating Percent Power Factor
0 10 20 30 40 50 60 70 80 90 100
225 Plug-in .23 .305 .38 .45 .515 .585 .645 .70 .75 .79 .77
Feeder .46 .61 .76 .90 1.03 1.17 1.29 1.40 1.50 1.58 1.54
400 Plug-in .405 .545 .68 .81 .935 1.055 1.17 1.275 1.37 1.44 1.41
Feeder .81 1.09 1.36 1.62 1.87 2.11 2.34 2.55 2.74 2.88 2.81
600 Plug-in .61 .83 1.05 1.26 1.47 1.67 1.85 2.02 2.18 2.31 2.28
Feeder 1.21 1.66 2.10 2.52 2.93 3.33 3.70 4.04 4.35 4.61 4.55
800 Plug-in .69 .87 1.04 1.21 1.37 1.52 1.66 1.78 1.88 1.95 1.85
Feeder 1.37 1.73 2.08 2.41 2.73 3.03 3.31 3.55 3.76 3.90 3.69
1000 Plug-in .73 .92 1.11 1.29 1.46 1.62 1.77 1.90 2.02 2.09 1.99
Feeder 1.45 1.84 2.21 2.57 2.91 3.24 3.54 3.80 4.03 4.18 3.97
1200 Plug-in .67 .85 1.02 1.18 1.84 1.49 1.63 1.75 1.85 1.93 1.83
Feeder 1.33 1.69 2.03 2.36 9.68 2.98 3.25 3.50 3.70 3.85 3.65
1350 Plug-in .58 .74 .89 1.04 1.18 1.31 1.44 1.55 1.64 1.71 1.63
Feeder 1.15 1.47 1.78 2.07 2.36 2.62 2.87 3.09 3.28 3.41 3.25
1600 Plug-in .60 .78 .94 1.10 1.25 1.39 1.52 1.64 1.74 1.82 1.73
Feeder 1.20 1.55 1.87 2.19 2.49 2.78 3.04 3.28 3.48 3.63 3.46
2000 Plug-in .59 .63 .93 1.09 1.24 1.39 1.53 1.65 1.76 1.83 1.76
Feeder 1.18 1.25 1.86 2.18 2.48 2.78 3.05 3.29 3.51 3.66 3.51
2500 Plug-in .60 .75 .89 1.03 1.16 1.29 1.40 1.50 1.58 1.64 1.54
Feeder 1.19 1.49 1.78 2.05 2.32 2.57 2.80 2.99 3.16 3.27 3.07
3200 Plug-in .63 .79 .94 1.09 1.23 1.36 1.48 1.58 1.67 1.73 1.63
Feeder 1.26 1.58 1.88 2.17 2.45 2.71 2.96 3.16 3.34 3.46 3.25
4000 Plug-in .66 .83 1.00 1.15 1.31 1.45 1.58 1.70 1.80 1.86 1.76
Feeder 1.31 1.66 1.99 2.30 2.61 2.89 3.16 3.39 3.59 3.72 3.52
Busway Cutler-Hammer
C2-26 Low-Voltage Busway – Pow-R-Way III May 2001

Technical Data

Resistance, Reactance and Impedance Derating Chart for Higher Ambient


Aluminum Bars Temperatures
Pow-R-Way III busway may be operated
Milliohms per 100 ft. (30.48 Meters) Line-to-Neutral Aluminum Plug-in and Feeder Busway continuously at its assigned ratings without
Ampere Rating Resistance Reactance Impedance exceeding the maximum hot spot tempera-
225 4.38 1.17 4.54 ture rise of 55° C, provided the ambient tem-
perature does not exceed 40° C. For higher
400 4.38 1.17 4.54
ambient temperatures, the ratings should be
600 4.38 1.17 4.54 reduced by applying the appropriate multi-
800 2.67 1.05 2.84 plier shown in the following chart.
1000 2.29 .84 2.44
Ambient Temp. °C Multiplier
1200 1.76 .64 1.87
40 1.00
1350 1.39 .49 1.47
45 .95
1600 1.25 .43 1.32
50 .90
2000 1.01 .34 1.07
55 .85
2500 .71 .27 .76
60 .80
3200 .62 .24 .67
65 .74
4000 .50 .19 .54
70 .67
Copper Bars
Milliohms per 100 ft. (30.48 Meters) Line-to-Neutral Copper Plug-in and Feeder Busway
Ampere Rating Resistance Reactance Impedance
225 2.30 1.20 2.59
400 2.30 1.20 2.59
600 2.30 1.20 2.59
800 2.30 1.20 2.59
1000 1.67 .95 1.93
1200 1.39 .78 1.60
1350 1.20 .66 1.37
1600 .94 .50 1.07
2000 .76 .39 .85
2500 .55 .26 .61
3200 .47 .31 .51
4000 .38 .24 .45
5000 .27 .16 .32

Weight (Pounds/Ft.) and Current Density (Amperes Per Square Inch)


Ampere Rating Current Density Weight – Including Integral Housing Ground (Pounds/Ft.)
Amperes Per Square
3-Wire 4-Wire 100% Neutral 4-Wire 200% Neutral Add for Internal Ground
Inch
Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
225 225 554 554 8 5 10 6 11 7 .78 .23
400 400 985 985 8 5 10 6 11 7 .78 .23
600 — 1477 — 8 — 10 — 11 — .78 —
800 600 1969 1477 8 5 10 6 11 7 .78 .23
1000 — 1778 — 10 — 12 — 14 — 1.08 —
1200 800 1745 1164 12 6 15 7 17 8 1.33 .40
1350 1000 1662 1231 14 7 17 8 20 9 1.57 .47
1600 1200 1506 1129 17 8 21 10 25 11 2.05 .62
2000 1350 1455 982 23 11 28 12 33 13 2.66 .80
— 1600 — 1024 — 12 — 13 — 15 — .91
2500 2000 1250 1000 29 14 36 16 42 18 3.87 1.17
3200 — 1505 — 45 — 56 — 66 — 4.11 —
4000 2500 1455 909 34 21 42 24 49 27 5.32 1.61
— 3200 — 960 — 23 — 26 — 29 — 1.83
5000 4000 1250 1000 63 28 72 32 85 36 7.74 2.35
Cutler-Hammer Busway
C2-27
May 2001 Low-Voltage Busway – Pow-R-Way III
Technical Data

Metric Weight (Kg/M) and Current Density (Amperes Per cm2)


Ampere Rating Current Density Weight – Including Integral Housing Ground (kg/M)
Amps/cm2 3-Wire 4-Wire 100% Neutral 4-Wire 200% Neutral Add for Internal Ground
Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
225 225 86 86 12 7 15 9 17 11 1.17 .35
400 400 153 153 12 7 15 9 17 11 1.17 .35
600 — 229 — 12 — 15 — 17 — 1.17 —
800 600 305 229 12 7 15 9 17 11 1.17 .35
1000 — 276 — 15 — 18 — 21 — 1.62 —
1200 800 270 180 18 9 22 11 26 12 1.98 .60
1350 1000 258 191 21 11 25 12 30 14 2.34 .71
1600 1200 233 175 25 12 32 15 37 16 3.06 .92
2000 1350 226 152 34 16 42 18 49 20 3.96 1.20
— 1600 — 159 — 18 — 20 — 22 — 1.36
2500 2000 194 155 43 21 54 24 63 27 5.76 1.75
3200 — 233 — 67 — 83 — 98 — 6.12 —
4000 2500 226 140 51 32 63 36 73 40 7.92 2.40
— 3200 — 149 — 34 — 39 — 43 — 2.73
5000 4000 194 155 94 42 108 48 126 54 11.53 3.50

TVSS Bus Plugs, Clipper Power Systems Selection Chart


Catalog Number P3F-CPS-M P3F-CPS-H P3F-CPS-S2 P3F-CPS-S P3F-CPS-B
Surge Current Per Phase 400 kA 250 kA 160 kA 120 kA 100 kA
Surge Current Mode
Line-Neutral 200 kA 125 kA 60 kA 60 kA 50 kA
Line-Ground 200 kA 125 kA 60 kA 60 kA 50 kA
Neutral-Ground 200 kA 125 kA 60 kA 60 kA 50 kA
Line-Line (Delta and ungrounded applications only) 200 kA 125 kA 60 kA 60 kA 50 kA
Protection Modes
3-Phase Wye Systems 7 7 7 7 7
3-Phase Delta Systems 6 6 6 6 6
Filter Attenuation 55dB 55dB 55dB 55dB 40dB
(Based on MIL-STD-220A) at 100kHz
IEEE Category B3 Ringwave Suppression <150V <150V <150V <150V <350V
(L-N Mode; 6000V, 500A)
Surge Withstand Capabilities >4000 >3500 >2500 >2500 >1500
IEEE C3 Wave (10 kA)
TVSS TRI-Monitor System
1. Overcurrent Protection Yes Yes Yes Yes Yes
2. Infrared Detection Yes Yes Yes Yes Optional
3. Thermal Detection Yes Yes Yes Yes Optional
Busway Cutler-Hammer
C2-28 Low-Voltage Busway – Pow-R-Way III May 2001

Typical Specifications

1. Ratings B. Bus bars shall be insulated over their entire plug-in units shall be provided at each
length, except at joints and contact surfaces, plug-in opening to facilitate unit alignment
A. The busway shall be Cutler-Hammer type
with a CSA and UL listed insulating material and prevent improper installation.
Pow-R-Way III:
consisting of epoxy applied by fluidized bed
B. Where required, plug-in units of the types
[3-phase, 3-wire with 50% housing ground process. Tape or heat-shrink sleeve insula-
and ratings indicated on the plans and
and optional 50% internal ground] tion, or any other method of insulation
specifications shall be supplied. Plug-in
which can allow air-gaps or insulation
[3-phase, 3-wire with 50% housing ground units shall be mechanically interlocked
breakdown, shall not be acceptable.
and optional 50% isolated ground] with the busway housing to prevent their
C. The busway shall be capable of carrying installation or removal while the switch is
[3-phase, 4-wire with 100% neutral, rated current continuously without exceed- in the ON position. The enclosure of any
50% housing and optional 50% internal ing a temperature rise of 55 degrees C plug-in unit shall make positive ground
ground] based on a 40 degrees C ambient. connection to the duct housing before the
stabs make contact with the bus bars. All
[3-phase, 4-wire with 100% neutral, 4. Bus Joints
plug-in units shall be equipped with a
50% housing and optional 50% isolated A. Each busway section shall be furnished defeatable interlock to prevent the cover
ground] complete with joint hardware and covers. from being opened while the switch is in
[3-phase, 4-wire with 200% neutral] The busway joints shall be a single-bolt, the ON position and to prevent accidental
non-rotating, removable bridge design. All closing of the switch while the cover is
[3-phase, 4-wire with 200% neutral, bridge joints shall be furnished with open. The plugs shall be provided with a
50% housing ground and optional torque-indicating double head joint bolts means for padlocking the cover closed and
and Belleville washers. The bridge joint padlocking the disconnect device in the
50% internal ground] shall utilize a captive nut retainer on the OFF position. The operating handle and
[3-phase, 4-wire with 200% neutral, opposite side of the torque indicating bolt. mechanism shall remain in control of the
50% housing ground and optional The bridge joint design shall ensure disconnect device at all times, permitting
50% isolated ground] proper installation without the use of a its easy operation from the floor by means
torque wrench, and provide visual indica- of a hookstick or chain. Plug-in units shall
with voltage and current ratings as tion that the joint is properly torqued. Each be equipped with a means for direct posi-
indicated on the contract drawings. busway joint shall allow for a minimum tioning or hanging, so that the weight is
B. The busway shall, have a minimum of length adjustment of +/- 0.5 inches. De- borne by the duct before the stabs make
6-cycle short-circuit rating of 85 kA RMS energization of busway shall not be contact with the bus bars. For safety rea-
symmetrical for ratings through 800A, 100 required for safe testing of joint tightness. sons, no projections shall extend into the
kA RMS symmetrical for ratings through 5. Housing busway housing other than the plug-in
1350A, 125 kA RMS symmetrical for rat- stabs. All plug-in units shall be inter-
ings through 1600A, 150 kA RMS symmet- A. The busway housing shall be a 2-piece changeable without alteration or modifica-
rical ratings through 2500A, and 200 kA design fabricated from extruded aluminum. tion of plug-in duct.
RMS symmetrical for ratings through The 2-piece housing shall be bolted
together along the bottom flange using C. Fusible-type plugs shall have a quick-
5000A. make/quick-break disconnect switch and
grade 5, 1/4x20 zinc-plated fasteners on
2. Construction 3-inch centers for maximum mechanical positive pressure fuse clips
A. The busway and associated fittings shall strength. The busway enclosure finish shall – OR –
consist of [aluminum] [copper] conductors be ANSI 61 gray baked epoxy powder paint
C. Circuit breaker-type plugs shall have an
totally enclosed in a 2-piece extruded alumi- applied by an electrostatic process.
interrupting rating of not less than ____
num housing. Outdoor feeder, indoor feeder B. Outdoor feeder busway housing shall be symmetrical RMS amperes or be series-
and indoor plug-in busway shall be inter- identical to indoor feeder busway hous- rated as otherwise shown in the contract
changeable at the same rating without the ings, and shall be UL listed for outdoor document and shall meet all requirements
use of adapters or special splice plates. use. Busway shall be completely weather- of UL Standard 489. It shall be possible to
Where indicated on the drawings, provide ized at the factory, and designed such that increase the interrupting rating of a
indoor, sprinkler-proof plug-in busway. Out- only protective joint covers are required breaker plug-in device having ampere rat-
door designs requiring addition of caulking for outdoor application. ings through 400A up to 100 kAIC at 480
or gasketing in the field are not acceptable. Vac and 200 kAIC at 240 Vac by changing
Fittings such as – elbows, tees, flanges, etc. – 6. Plug-in Busway
out the circuit breaker only and leaving the
shall be identical for use with both the plug- A. Where required, busway shall be of the enclosure intact. All breaker plug-in
in and feeder types of busway. The busway plug-in type. Plug-in busway shall be avail- devices shall be Cutler-Hammer type
shall be capable of being mounted flatwise, able in standard 2-, 4-, 6-, 8-, and Series C.
edgewise, or vertically without derating. The 10-foot lengths, with plug-in openings pro-
busway shall consist of standard 10-foot sec- vided on both sides of the busway sec- D. Current-limiting circuit breaker-type plug-
tions with special sections and fittings pro- tions on 24-inch centers. Plug-in in devices shall be units which provide
vided to suit the installation. Horizontal runs covers shall prohibit dirt and debris from integral time delay/thermal trip protection
shall be suitable for hanging on 10-foot max- entering contact plug-in openings in the and current-limiting protection in one
imum centers. Vertical runs shall be suitable busway. The design shall allow for ten (10) assembly. These breakers shall be UL
for mounting on 16-foot maximum centers. hinged cover outlets per ten (10) feet of rated at 200 kAIC at 240 Vac, and 150 kAIC
Provide one (1) hanger for every ten (10) feet plug-in length, and covers shall be field- at 480 Vac, and shall be series-rated to pro-
of horizontally mounted duct. On vertical convertible to hinge on either side. Covers tect all molded case breakers downstream
runs provide one adjustable hanger per for plug-in openings shall have a positive as shown on the drawings.
floor. screw close feature and provisions for 7. Transient Voltage Surge Suppression
3. Bus installation of power company seals. The
A. Provide transient voltage surge sup-
contact surfaces for bus plug stabs shall
A. Bus bars shall be fabricated from high pression.
be silver-plated of the same material, thick-
strength, [55% conductivity aluminum] ness, and rating as the phase bars. The B. Refer to the TVSS Bus Plug, Clipper
[98% conductivity copper] and suitably tabs shall be welded to the busbars. A Power Systems Selection Chart page C2-
plated at all electrical contact surfaces. standard silver-plated housing ground 27 and select the TVSS as required.
connection shall be supplied in each plug-
in opening. Positive mechanical guides for

You might also like