Professional Documents
Culture Documents
CONTENTS
Section Page
SCOPE ............................................................................................................................................................ 4
REFERENCES ................................................................................................................................................ 4
DESIGN PRACTICES............................................................................................................................. 4
INTERNATIONAL PRACTICES.............................................................................................................. 4
OTHER LITERATURE ............................................................................................................................ 4
BACKGROUND .............................................................................................................................................. 4
CONVECTION SECTION ....................................................................................................................... 4
STACK .................................................................................................................................................... 4
DEFINITIONS.................................................................................................................................................. 5
CONTENTS (Cont)
Section Page
NOMENCLATURE ........................................................................................................................................ 57
CONTENTS (Cont)
Section Page
FIGURES
Figure 1A Cylindrical Stud Extended Surface ..................................................................................... 62
Figure 1B Helical Fin Extended Surface ............................................................................................. 62
Figure 2 Arrangement of Convection Section Tubes ........................................................................ 63
Figure 3 Temperature Factor F1 ....................................................................................................... 64
Figure 4 Partial Pressure of CO2 + H2O in Flue Gas ....................................................................... 65
Figure 5 Convection Section Characteristic Factor, F ............................................................................................. 66
Figure 6 Stud Efficiency Factors E, E′, E′′ ........................................................................................ 67
Figure 7A Stud Efficiency Factors E, E′ for 1/2 in. (12.7 mm) Diameter Carbon Steel Studs.............. 68
Figure 7B Stud Tip Temperatures Factors E′′ for 1/2 in. (12.7 mm) Diameter Carbon Steel Studs .... 69
Figure 8 Fin Efficiency factors E, E′ .................................................................................................. 70
Figure 9 Fin Tip Temperature Factor E′′ ........................................................................................... 71
Figure 10 Flue Gas Pressure Gains And Losses................................................................................ 72
Figure 11 Pressure Losses in Bends .................................................................................................. 73
Figure 12 Ducting Arrangements ........................................................................................................ 74
Figure 13 Convection Section Friction Factor ..................................................................................... 75
Figure 13A Convection Section Friction Factor (Equilateral Pitch)........................................................ 76
Figure 14 Approximate Stack Temperature Losses for Steel Stacks.................................................. 77
Figure 15 Approximate Stack Exit Temperatures for Concrete Stacks ............................................... 78
Figure 16 Stack Effect ........................................................................................................................ 79
Revision Memo
12/99 The highlights of these revisions are:
1. Page 4 Updated Reference List
2. Page 4 Updated Background information on Stacks
3. Page 5 Updated Extended Surfaces information
4. Page 6 Updated table to include stud spacing
5. Page 13 Updated equations for Shield Tube Heat Density
6. Page 16 Added table for equivalent lengths between studs and thick fins
7. Page 16 Replaced equations for inside heat transfer coefficients with the
Dittus Boelter equation
8. Pages 20-23 Corrected tube metal temperature calculations
9. Page 23 Corrected equation for equivalent tube conductivity
10. Page 24 Updated information in Stack Linings section
11. Page 25 Updated density equations to reflect effect of molecular weight
12. Page 26 Added section on Flue Gas Pressure Variation and added
graph for draft in a furnace
13. Page 41 Updated frictional pressure drop formula to reflect changes in
DP XIV, Fluid Flow
14. Pages 32-59 Updated examples to reflect changes in equations
15. Page 57-60 Updated units in Nomenclature
16. Page 61 Added Computational Fluid Dynamics to Computer Programs
listing
17. Relocated TMT calculation from Appendix to Convection
Section Design
18. Deleted Figures 3A and 3B - Heat transfer coefficients for
fluids in tubes
19. Deleted Figure 4 - Inside film coefficients for fluids containing
hydrogen (Colburn correlation)
20. Page 77 Corrected Metric axes in Figure 14
SCOPE
This section contains calculation procedures to be used for designing convection sections and stacks for aIl fired heaters. Where
specialized procedures are required for the convection section design, they are noted.
The procedures outlined below are based on conventional single service convection section arrangements, with countercurrent
flow of flue gas and process fluid. Flue gas flow is upward, and the process fluid flows downward from the top of the convection
section to the bottom (see SHIELD SECTION). Although the basic equations are unchanged, other arrangements, as well as
auxiliary services such as steam superheaters, will require modifications to these procedures.
➧ REFERENCES
DESIGN PRACTICES
Other sections of Section VIII, Fired Heaters
Section XIV Fluid Flow
INTERNATIONAL PRACTICES
IP 7-1-1, Fired Heaters
OTHER LITERATURE
ASHRAE Guide and Data Book, 1969.
General Electric Company, Heat Transfer and Fluid Flow (1970).
Grimison, E. D., Cross Flow of Gases Over Tube Banks, ASME Transactions PRO-59-8 (1937).
Tenner, A. R. and Golan, L. P., Graphic Procedure for Calculating Heat Transfer Coefficient and Flow Regimes for Single and
Two Phase Flow in Tubes, ER&E Report No. EE.6ER.71 (March 1971).
BACKGROUND
CONVECTION SECTION
Flue gases leave the fired heater radiant section and pass through the convection section before entering the stack. At flue gas
temperatures below 1500 to 1800°F (815 to 980°C), radiant heat transfer becomes relatively uneconomical, and if further heat
recovery from the flue gas is desired, this is more economically accomplished by convective heat transfer. Typically, 35 to 40%
of the total fired heater duty is obtained in modern extended surface convection sections. The convection section must be
designed to transfer heat economically to the process fluid, and at the same time not to impede unduly the flue gas leaving the
fired heater. Since the flue gas heat transfer coefficient on the outside tube surface is relatively poor, extended surface is usually
used to increase heat transfer.
➧ STACK
The purpose of the stack is to create the necessary draft for flue gases to flow properly through the fired heater system and to
dispose of the flue gases. This must be done without imposing a positive pressure on any part of the fired heater box, since the
construction box is not pressure-tight and flue gases leaking out can cause severe damage to the fired heater casing and
structure. Also, flue gas leakage could seriously injure nearby personnel. Adequate draft is also necessary for natural draft
burners, to inspirate the required combustion air. The hot stack gases must also be discharged at a safe height with respect to
surrounding equipment (towers and other structures).
Since flue gases contain pollutants such as SOx, NOx, and particulates, the stack must be designed to discharge these gases in
a manner that avoids causing a local pollution problem. Stack height and flue gas exit velocity are important design variables
that allow the stack to discharge and disperse pollutants for the purpose of meeting regulatory emission requirements. Turndown
conditions (as well as design conditions) must be considered, since ground-level concentrations of pollutants from the flue gases
are affected by the flue gas exit velocity.
DEFINITIONS
See Section VIII-A.
SHIELD SECTION
The first two rows of the convection section are exposed to radiation from the radiant section and are known as “shield tubes."
The radiant heat transfer to these two rows is included in the total fired heater radiant duty (see Section VIII-B). Since the shield
tubes also pick up some heat by convection, the total shield duty is the sum of these radiant and convection heat duties.
Extended surface must not be used on the shield tubes, since the resulting heat pickup and heat densities would be excessive,
causing high tube metal temperatures and/or vapor blanketing.
IP 7-1-1 requires the shield tubes to be of the same material as the radiant tubes. An exception can be made where the shield
service is different from the radiant service, such as a steam generator coil in a process fired heater.
EXTENDED SURFACES
➧ Selection of Extended Surface Type - The type of extended surface to be used is based on the fuel to be fired in the fired
heater.
1. Stud type and thick-fin type extended surfaces are the only types that may be used if heavy liquid fuels [containing greater
than 0.01% ash and 25° API or lower, ρ = 56.4 lb/ft3 (904 kg/m3) or greater] are to be fired. Figure 1A shows a studded
tube.
2. Thin-fin type extended surface should be used only when fuel gas or light liquid fuels [containing less than 0.01% ash and
above 25° API, ρ less than 56.4 lb/ft3 (904 kg/m3)] are to be fired. Figure 1B shows a finned tube.
In fired heaters where a number of fuels are to be fired, the heaviest fuel governs the selection of extended surface type. Note
that in fired heaters where heavy liquid fuels are to be fired at any time in the future, studded or thick-finned tubes should be
used. Conversion of a fired heater originally designed for only gas firing to permit heavy liquid fuel firing would require major
revamping of the fired heater. The criteria for selecting thick-fins versus studs is usually based on cost and availability.
Studded Tubes
1. Application - Cylindrical studs are resistance welded to the tube in circular or helical rows. Carbon steel studs, 1/2-in.
(12.7 mm) diameter, and spaced on rows 5/8 in. (15.9 mm) apart (19.2 rows per ft of tube or 63.0 rows per m of tube) are
standard and should be so specified. Other types of studded surface, including 1/4 and 3/8 in. (6.4 and 9.5 mm) diameters
and elliptical shaped studs, are available. However, these should not be used because of their disadvantages, such as
reduced mechanical strength and poorer cleanability.
2. Temperature - Carbon steel studs should be limited to about 1050°F (565°C) maximum tip temperature, based on stud
oxidation considerations. CS studs can be applied to any tube material. Stress relieving is not required. It is generally not
economical to use alloy studs.
➧ 3. Stud Arrangement - Studs can be applied on the entire tube diameter, or on just the bottom half of the tube (the side facing
the flow of flue gas). Half-studded tubes (studded along the bottom half of the tube) were used in the past but should no
longer be used. Fully studded tubes are recommended.
4. Stud Length - Studs are available in length increments of 1/16 in. (1.6 mm), starting at 3/4 in. (19.1 mm) long (5/8 in. or
15.9 mm studs can also be obtained, but they must be cut to length by hand and should therefore not normally be used.)
The maximum possible stud length is based on manufacturing capabilities, and depends on tube size, since the outside
diameter of the tube and studs is limited to 11 1/8 in. (282.6 mm). Maximum stud lengths should usually be limited to about
2 in. (50 mm) because stud efficiency drops sharply with increasing length.
Selection of stud lengths depends upon convection section geometry and flue gas mass velocity, as discussed below. Short
studs should be used as soon as possible in the lower convection section, as limited by stud tip, tube and film temperatures;
and stud length should be increased as flue gas temperature decreases through the convection section.
mm 63.5 76.2 88.9 101.6 114.3 127.0 141.3 152.4 168.3 219.1
Studs per circumferential row 8 10 12 12 14 16 18 20 22 28
BASED ON ROWS SPACED AT 5/8 in. (15.9 mm)
Studs per foot 153.6 192.0 230.4 230.4 268.8 307.2 345.6 384.0 422.4 537.6
Studs per meter 504.0 630.0 756.0 756.0 882.0 1008.0 1134.0 1260.0 1386.0 1764.0
Finned Tubes
1. Application - Thin-fins are continuously wound around the tube in a spiral, with up to about 5 turns per in. (2 turns per cm).
Thick-fins are also continuously wound in a spiral, with up to about 3 turns per in. (1.2 turns per cm). The fins should be
continuously welded to the tube by a fillet or resistance weld. These welds are generally required over intermittent spot-
welding attachments, because of their better heat transfer capabilities and their stronger bond to the tube (see IP 7-5-1).
➧ 2. Fin Type - Continuous solid fins (Figure 1B) are made by stretching a continuous strip of metal around the tube. As
covered by IP 7-5-1, solid fins are preferred over serrated fins, which are formed by partially splitting the metal strip before
winding it around the tube. Solid fins have superior mechanical rigidity. Calculation procedures given in this section are
based on solid fins. It may not be possible to obtain solid fins for all combinations of tube diameter, fin height, and fin
material due to mechanical constraints imposed by the manufacturing process.
3a. Availability of Thin-Fins - A variety of fins are available, as follows:
Fin height from 1/4 to 1-1/2 in. (from 6.4 to 38.1 mm).
Fin thicknesses from 0.02 to 0.06 in. (from 0.5 to 1.5 mm).
Fin spacing of up to10 fins per in. of tube length (fins as close as 2.5 mm).
Not all combinations of these variables are available. For economical design, fins should be based on the following:
Fin height of 1/2, 3/4 or 1 in. (12.7, 19.1 or 25.4 mm).
Fin thickness of 0.05 in. (1.3 mm).
Spacing of 4 to 5 fins per in. (5.1 to 6.4 mm).
3b. Availability of Thick-Fins
Fin height from 1/2 to 1-1/4 in. (12.7 to 30.6 mm).
Fin thicknesses of 0.105 in. (2.7 mm).
Fin spacing of 1 to 4 fins per in. (6.4 to 25.4 mm).
To minimize fouling potential, it is recommended that a maximum height of 3/4 in. (19 mm) and a spacing of 3 fins per in.
(8.5 mm) be used.
4. Material - Almost any fin material can be attached to any tube material. Since fins are much thinner than studs, fin materials
should be selected for zero oxidation at the maximum tip temperature. The higher the tip temperature, the better grade fin is
required. The following fin materials are commonly used:
Convection Section Cleaning - The requirement for sootblowers and attendant erosion protection of convection section
refractory walls (see Section VIII-H) has a significant effect on fired heater investment. The convection section layout should
take into consideration the optimum arrangement of sootblowers, tubesheets and tubes.
Consideration should be given to widening the convection section as a means of minimizing the number of sootblower rows
required. The wider convection section permits the use of more tube surface per row, resulting in fewer vertical rows to be
covered by sootblowers. Even though the total number of tubes is increased (lower flue gas mass velocity and heat transfer
coefficient), the reduction in sootblower investment would more than compensate for the increased number of tubes. However,
reducing the number of sootblowers by this means is often not possible. Conventional flue gas mass velocities should then be
used.
Calculation Procedure
Wf
Gc = Eq. (1)
Af
where: Gc = Flue gas mass velocity through convection section (for heat transfer calculations),
Ib/sec ft2 (kg/s m2)
Wf = Flue gas rate, lb/sec (kg/s)
Af = Free cross-sectional area for flue gas flow, ft2 (m2)
Fg FG
Wf = (Customary) Eq. (2)
3600
Af = L c Wc − R Eq. (3)
R sh =
Do
1000
(L c Nt ) (Metric) Eq. (4a)M
Although not accounted for in this calculation, corbelling should be specified for the second shield
row.
2. Bare Tube Section Restriction Rb
R b = R sh +
C
12
Lc ( ) (Customary) Eq. (4b)
C
R b = R sh + (L c ) (Metric) Eq. (4b)M
1000
where: Rb = Restriction in bare section (from tubes and corbelling), ft2 (m2)
C = Corbelling width, in. (mm)
hs
Rs = Rb + (L c N t ) (Metric) Eq. (4c)M
1250
h d
Rs = Rb + s s (Lc Nt ) (Customary) Eq. (4c1)
12 ps
h d
Rs = R b + s s (L c N t ) (Metric) Eq. (4c1)M
1000 p s
Rf = Rb +
hf
6
(
t f nf Lc Nt ) (Customary) Eq. (4d)
(
hf hf Lc Nt )
R f = Rb + (Metric) Eq. (4d)M
500 nf
CALCULATION PROCEDURE
The procedure outlined below is used to calculate the required convection section surface. This procedure consists of a series of
trial and error solutions. The Fired Heater Simulation Program 3558 may be used for these calculations.
The necessary equations for design of the convection section are presented following this calculation procedure.
Step 1 - Divide the convection section into smaller increments of several tube rows each. Start calculations at the shield section
and work upward to coil inlet.
Step 2 - By a heat balance around the radiant section, the crossover temperature (oil side temperature out of shield section) can
be determined. The shield radiant duty must be calculated and separated from the radiant section duty. The flue gas
temperature into the shield section will be the bridgewall temperature previously determined.
Step 3 - For each new section being designed, calculate the maximum oil film temperature, tube metal temperature, and stud/fin
tip temperature to insure they are not excessive. This should be done for the first row of each new material, extended surface,
etc. used. These calculations should all be based on entering flue gas and leaving oil temperatures for that row.
where: Qtr = Total fired heater radiant duty, Btu/hr (W) (Note that bridgewall temperature (Tbw) is
based on Qtr)
3. Total Convection Section Duty
where: Qtc = Total convection section heat duty, Btu/hr (W). (Note that Qtc is the basis of the crossover
temperature from the convection section to the radiant section.) Also note that Qtr and
Qtc overlap, since both include the shield radiant duty, Qsr.
2. Shield Section Radiant Duty Qsr - The shield tubes are directly exposed to the radiant section and absorb a portion of the
total radiant duty. This duty is included in the heat absorbed in cooling the flue gases down to the bridgewall temperature.
where: φ1 side = Average radiant section heat density based on one-side firing, Btu/hr ft2 (W/m2)
(T + 460 ) 4 − T
φs =
bw (
mas + 460 )
4
φ la FBL (Customary) Eq. (10a)
(Tbw + 655 ) 4 − (Tma + 460 ) 4
φs =
(
T + 273 4 − T
bw ) (
mas + 273
4
)
φ la FBL (Metric) Eq. (10a)M
(
(Tbw + 381) 4 − T ma + 273 4
)
where: Tbw = Bridgewall temperature, °F (°C)
Tma = Length average radiant tube metal temperature, °F (°C)
For steam reforming fired heaters, refer to Section VIII-E for Tma. For process fired
heaters, Tma should be calculated on the basis of φr and the average bulk fluid
temperature in the radiant section (uncoked), and assuming no maldistribution of heat
input (C1 • C2 • C3 = 1.0)
Tmas= Length average shield tube metal temperature (on front 180 of all shield tubes), °F (°C)
= 0.866 Tms – 0.266 Tb1 + 0.4 Tb2 Eq. (55)
Tms = Maximum shield tube metal temperature, °F (°C) (see below)
Tb1 = Process fluid temperature leaving the shield section, °F (°C) (crossover temperature)
Tb2 = Process fluid temperature entering the shield section, °F (°C)
φla = Radiant section front face length average heat density, Btu/hr ft2 (W/m2)
= C1 φr
φr = Radiant section average heat density, Btu/hr ft2 (W/m2)
C1 = Peripheral maldistribution of heat around tube. See Section VIII-B.
C2 = Vertical maldistribution of heat around tube. See Section VIII-B.
C3 = Luminosity factor. See Section VIII-B.
FBL = Mean beam length correction factor (Use 1.5)
LMTD =
(Tg1 − Tb1) − (Tg2 − Tb2 ) Eq. (12)
Tg1 − Tb1
In
Tg2 − Tb2
where: Tg1 = Flue gas temperature entering the section, °F (°C) (see Figure 2a)
Tb1 = Process fluid temperature leaving the section, °F (°C)
Tg2 = Flue gas temperature leaving the section, °F (°C)
Tb2 = Process fluid temperature entering the section, °F (°C)
1 1 A 1 A ta
= + o + o
h A
k
(Customary) Eq. (13)
U ho Ai i m m
1 1 A 1 Ao ta −3
= + o + x 10 (Metric) Eq. (13)M
U ho Ai hi Am km
Btu / hr ft 2
km = Thermal conductivity of tube wall, o
(W/m °C)
F / in.
(see Section VIII-B)
Do = Tube outside diameter, in. (mm)
AREA CALCULATIONS
Ao = A e + Ab Eq. (15)
−3 −3
A e = 2.51 x 10 h s n s + 7.98 x 10 ns (Metric) Eq. (16)M
−3
A b = 3.14 x 10 D o − 7.98 x 10 −3 n s (Metric) Eq. (17)M
d d2s
A e = 0.262 s hs ns + 0.0654 ns (Customary) Eq. (16a)
ps ps
d d 2s
Ae = 3.14 x 10 −3 s h n + 7.85 x 10 −4 n (Metric) Eq. (16a)M
p s s ps s
s
d2
A b = 0.262 Do − 0.0654 s ns (Customary) Eq. (17a)
ps
d s2
A b = 3.14 x 10 −3
D o − 7.85 x 10 −4 n (Metric) Eq. (17a)M
ps s
Ae = 0.131 nf (D 2
f − Do2 + 2 Df t f ) (Customary) Eq. (18)
A e = 1.57 x 10
−3
(
/ n f • D 2f − D o2 + 2 D f t f ) (Metric) Eq. (18)M
A b = 3.14 x 10 −3
D o (1 − t f / n f ) (Metric) Eq. (19)M
0.8 0.4 k
hi = 0.023 Re D Pr Eq. (21)
D
hi = φ1 φ 2 Eq. (21a)
0.8
G
φ1 = 23.0 0.2
Eq. (21b)M
D
0.4
Cp
φ 2 = k 0.6
Eq. (21c)
µ
3. Two-Phase
For two-phase flow, the heat transfer coefficients are found by taking the mass average of the single phase coefficients.
a. Determine the all-liquid coefficient, assuming that the total bulk fluid is liquid. Use the single-phase equation using the
liquid properties of the process fluid.
b. Determine the all-vapor coefficient, assuming that the total bulk fluid is vapor. Use the single-phase equation using the
vapor properties of the process fluid.
c. Calculate the two-phase coefficient, as a weighted average of (a) and (b), using weight fractions of vapor and liquid:
where: htp = Two-phase inside heat transfer coefficient, Btu/hr ft2 °F (W/m2 °C)
X = Weight fraction of vapor in the fluid
hl = Liquid film coefficient, based on no vaporization at bulk temperature, Btu/hr ft2 °F (W/m2 °C)
hv = Vapor film coefficient, based on 100% vaporization at bulk temperature, Btu/hr ft2 °F (W/m2 °C)
Note: This method is recommended for calculating design coefficients for two-phase flow. Assuming
satisfactory fluid flow patterns, the actual coefficient at any given point may be significantly higher
than either the all-liquid or all-vapor coefficient. However, it is not practical to use these anticipated
higher coefficients for design. For special cases requiring better definition of coefficients, consult
Report No. EE.6ER.71 or the Heat Transfer Equipment Section of EETD.
ho = hc + hr Eq. (22)
0.40
G 0.067 Tg + 273
h c = 30.7 c (Metric) Eq. (23)M
0.33 55.6
D o
hr = 0 Eq. (24a)
hr = F1 F2 Eq. (24b)
where: F1 = Temperature Factor, based on average flue gas and tube metal temperatures in the
bank. (Assume average tube metal temperature is 50°F (28 °C) hotter than fluid
temperature.) See Figure 3.
F2 = Convection Section Characteristic Factor, a function of tube geometry and flue gas
( )
properties (Lb) PCO2 +H2O . See Figures 4 and 5.
PCO 2 +H2O = Partial pressure of CO2 + H2O in the flue gas Eq. (25)
S S S S2 − (ST / 2) 2
Lb = 0.0903 R T − 0.0708 Do = 0.0903 T L − 0.0708 Do (Customary) Eq. (26)
Do Do
−3 SR S T −4 −3
S T S L2 − (S T / 2 ) 2
L b = 1.08 x 10 − 8.50 x 10 D o = 1.08 x 10 − 0.0708 D o (Metric) Eq. (26)M
D Do
o
Do SL = ST Lb
in. mm in. mm ft m
4.5 114.3 8 203 0.79 0.241
5.563 141.3 10 254 0.96 0.293
6.625 168.3 12 305 1.16 0.354
8.625 219.1 16 406 1.62 0.494
0.40
G 0.67 Tg + 273
h c = 2 4.4 c (Metric) Eq. (23a)M
D o 0.33 55.6
S S
Lb = 0.108 R T − 0.085 Do
(Customary) Eq. (26a)
Do
S S
Lb = 1.30 x 10 −3 R T − 1.02 x 10 −3 Do
(Metric) Eq. (26a)M
Do
EA + Ab
ho = he e Eq. (27)
Ao
where: ho = Outside film coefficient for tube plus its extended surface, Btu/hr ft2 °F (W/m2 °C)
he = Film coefficient for extended surface [see Eqs. (28a), (28b), and (28c)], Btu/hr ft2 °F
(W/m2 °C)
E = Extended surface efficiency factor. See Figure 6 or 7a for studded tubes, or Figure 8 for
finned tubes.
For fully-studded tubes,
0.48
G 0.55 Tg + 460
he = 7 c (Customary) Eq. (28a)
D o 0.45 100
0.48
G 0.55 Tg + 273
h e = 71.3 c (Metric) Eq. (28a)M
D o 045 55.6
Ao 1
∆T f = [U′ (Tbw − Tb1 ) + φ s ] Eq. (30)
A i hi
Ao ta
∆Tm = [ U′ (Tbw − Tb1) + φs ] (Customary) Eq. (31)
Am km
−3
Ao t a x 10
∆Tm = [U′ (Tbw − Tb1 ) + φ s ] (Metric) Eq. (31)M
Am km
1 1 A 1 A ta
= + o + o + fe (Customary) Eq. (31a)
U′ 1.5 hc Ai h i Am km
t x 10 −
3
1 1 Ao 1 A
= + + o a + fe (Metric) Eq. (31a)M
U′ 1.5 hc Ai h i Am km
Ao 1
∆Tf = U′ (Tg1 − Tb1 ) Eq. (32)
Ai h i
Ao ta
∆Tm = U′ (Tg1 − Tb1 ) (Customary) Eq. (33)
Am km
(
∆Tm = U′ Tg1 − Tb1 ) Ao ta
Am k m
x 10 −3 (Metric) Eq. (33)M
Ao 1
∆Tf = U′ (Tg1 − Tb1 ) Eq. (34)
Ai h i
Ao ta
∆Tm = U′ (Tg1 − Tb1 ) (Customary) Eq. (35)
Am km
(
∆Tm = U′ Tg1 − Tb1 ) Ao ta
Am km
x 10 −3 (Metric) Eq. (35)M
1 1 A 1 A ta
= + o + o (Customary) Eq. (36)
U′ h ′ A i hi Am km
o
1 1 A 1 Ao ta
= + o + x 10 −3 (Metric) Eq. (36)M
U′ h ′ A i hi Am km
o
where: ho′ = Local extended surface coefficient, Btu/hr ft2 °F (W/m2 °C)
E′ A e + A b
h o′ = h e′ Eq. (37)
Ao
h e ′ = fm h e Eq. (38)
(
Tt = Tg1 − E ′′ Tg1 − Tm ) Eq. (39)
1 1 A 1 A t x 10 −3 A t
= + o + o c + o a x 10 −3 + fe (Metric) Eq. (40)M
Uc ho Ai ′ h i A c k c A m km
where: Uc = Overall coefficient in coked and/or fouled condition, Btu/hr ft2 °F (W/m2 °C)
Ai′ = Area at inside diameter of coke layer, ft2/ft (m2/m)
= 3.14 x 10 −3
(D i − tc )
(Metric) Eq. (41b)M
1 A m′ t c 1 A ′ t 1
➧ = + m a Eq. (41c)
k m′ Ac t kc
a
′ ′
Am t km
a
Btu / hr ft 2
where: km′ = “Equivalent” tube conductivity, (W/m °C)
o
F / in.
t a′ = t a + tC Eq. (41d)
STACK DIAMETER
The diameter is usually a function of the quantity of flue gas flowing. Stacks should usually be designed for a velocity of 25 ft/sec
(7.6 m/s). Unless details of the stack are known, for design purposes the diameter should be considered uniform for the entire
length. The design specification should state the inside diameter required at the stack exit. The following considerations may
also affect the stack diameter:
Fired Heater Supported Stacks - Where flue gases pass directly into the stack, the diameter should be no greater than the
outside width (about 12 in. or 300 mm greater than the inside width) of the convection section. Where flue gases enter the stack
from ducts (Figure 12A) the stack may have a diameter somewhat greater than the outside width of the convection section.
Pollution Control Requirements - When relatively high stacks are required by pollution control considerations or by local
regulations, stack gas velocities higher than 25 ft/sec (7.6 m/s) may be economical, because the extra draft to compensate for
the extra pressure drop is available anyway. High velocities (instead of or in addition to tall stacks) may also be required on
occasion for pollution control considerations. When a restricted stack exit (choke cone) is used to obtain this increased velocity,
the pressure drop through the choke cone may place the top portion of the stack under positive internal pressure, if the exit
velocity is much above 25 ft/sec (7.6 m/s). This can cause damage to concrete or brick stacks, and a steel liner would then
probably be required. When the exit velocity is a nominal 25 ft/sec (7.6 m/s) or less, the exit loss is relatively small, and the effect
of a choke cone on the stack can be ignored.
Minimum Stack Gas Velocity - At very low flue gas velocities in the stack, much lower than 10 ft/sec (3 m/s), inversion can
occur, with cold air spilling into the stack and running down one side. This recirculation could possibly reduce the available draft
and should be avoided. Where extended operations of the fired heater at extremely low throughputs are expected, the following
measures should be considered:
1. Operate at Higher Excess Air Rate - During operation at low throughput, the percent excess air can be increased as
necessary, to avoid recirculation if this actually becomes a problem. This solution is usually preferable to increasing the
design stack gas velocity, and is particularly recommended for cases where stack height is based on draft requirements. In
such cases, increasing the design stack gas velocity would require increasing the stack height. Another reason for accepting
higher than design percent excess air during operation at low throughput is that, due to control difficulties and air leakage
into the fired heater, it is probably not practical to operate at low excess air rates under these conditions.
2. Removable Choke Plate - A removable choke cone on the stack can be considered, as a means of increasing stack exit
gas velocity during initial operation at low throughput. The cone would be removed when the fired heater throughput is
increased.
➧ STACK LININGS
Refractory linings are not required in a stack when the flue gas contains less than 5 vppm of SO3 or if the fuel contains less than
0.25% by weight of sulfur. In these circumstances, a bare steel stack could be constructed even if its metal temperature is
expected to be below the acid dewpoint of the flue gas. Its metal temperature must, however, be above the water dewpoint. In
cold climates, ambient temperatures may cause the metal temperature to drop below the water dewpoint. The formation of
carbonic acid and rust could damage the steel shell. For this reason, bare steel stacks are usually found in refineries having
warmer climates.
When the flue gas contains more than 5 vppm of SO3, carbon steel stacks and steel liners in concrete chimneys may be at risk
from acid corrosion. Corrosion will occur if the temperature of the metal in contact with the flue gases falls below the acid
dewpoint of the flue gas. As a rule-of-thumb, the metal temperature of a steel stack (uninsulated and with no lining) is midway
between the flue gas temperature and the ambient temperature. All carbon steel stacks require linings as required to maintain
the shell temperature below 900°F (480°C). A layer of 3-inch (76.2 mm) medium weight castable refractory is common.
External insulation could also be used to keep metal temperatures above the acid dewpoint. It is generally not used because of
the increased thermal stresses/growth in the steel shell, potential problems with insulation maintenance, and under-insulation
corrosion. Furthermore, external insulation does not provide any protection from an internal fire.
Special consideration should be taken when designing stacks that will operate under steam-air decoking conditions, where the
flue gas into the stack is approximately 1000°F (538°C). As the metal temperature increases, there is a reduction of strength in
the stack material (typically carbon steel) and a thicker wall may be required. So it may be preferable to internally line the stack
with refractory, which will reduce the metal temperature and the required wall thickness.
To protect nearby personnel, furnace-supported bare stacks should be lined internally, up to the elevation where personnel
access instrumentation (stack damper elevation). Bare stacks may also have a protective screen that prevents personnel from
coming into contact with the potentially hot wall.
39.5 Mg
➧ ρ = (Customary) Eq. (42)
Tg + 460 M a
351 Mg
➧ ρ = (Metric) Eq. (42)M
Tg + 273 M a
If the altitude is greater than 1000 ft (300 m), see Section VIII-G for altitude corrections to air density.
Temperature Loss in the Stack - Assume the following temperature drops from the fired heater exit to the stack exit:
1. Steel Stacks - See Figure 14.
2. Concrete Stacks - See Figure 15. (Infiltration of cold air through the concrete stack is accounted for in this figure.)
200
(61)
Atmospheric
Pressure
Height, ft (m)
100
Damper
(30.5)
Radiant Floor
0
14.6 14.7
2.8 inches of Water
DP8Cfh
Absolute Pressure (psia)
V12
∆P1 = 0.1186 K (Customary) Eq. (43)
Tg + 460
V12
∆P1 = 0.176 K (Metric) Eq. (43)M
Tg + 273
➧ Note: In determining the Fanning friction factor f, for use in the pressure drop equation, use a roughness
factor of 0.055 in. for internally insulated stacks (from the suggested range of 0.015 to 0.15 in.). For
bare steel use 0.002 in.
For calculating pressure drop in a duct of rectangular cross-section, using equations intended for
conduits with circular cross-section, it is necessary to use an equivalent (“hydraulic") diameter:
2 xy
dc = Eq. (45)
x+y
where: dc = Equivalent diameter (for a circular duct with the same friction loss), ft (m)
x = Depth of duct, ft (m)
y = Width of duct, ft (m)
3. Friction Loss Across Damper - With the damper wide open:
4. Additional Losses - These pressure drops depend on the ducting and stack arrangement. They include sudden
expansions and contractions, bends, and intersections of flue gas streams. The sum of these additional losses is designated
∆P4.
a. Sudden Expansion
∆Pe = 0.1186
(V1− V2 )
2
(Customary) Eq. (47)
Tg + 460
∆Pe = 0.176
(V1 −V2 )
2
(Metric) Eq. (47)M
Tg + 273
where: ∆Pe = Pressure loss due to sudden expansion, in. of water (kPa)
V1 = Flue gas velocity upstream of sudden expansion, ft/sec (kPa)
V2 = Flue gas velocity downstream of sudden expansion, ft/sec (kPa)
V22
∆Pc = 0.1186 K (Customary) Eq. (48)
Tg + 460
V22
∆Pc = 0.176 K (Metric) Eq. (48)M
Tg + 273
where: ∆Pc = Pressure loss due to sudden contraction, in. of water (kPa)
K = Coefficient for contraction loss (Section XIV); use a value from the table below:
c. Bends - Bend losses are detailed in Figure 11. For systems where stack height is determined by fired heater draft
requirements, assume that miter bends with turning vanes are to be used. Typical turning vanes should be included in
the design specification. For systems where the stack height is set by local (e.g., pollution control) requirements, i.e.,
the available draft exceeds the required draft, assume the use of rounded bends with Rt / x = 0.5 and no turning vanes.
d. Intersections - Typical intersections of flue gas streams are shown in Figure 12. Note that these losses are in addition
to normal bend and expansion or contraction losses.
5. Stack Entrance Loss - A full velocity head loss is taken at the stack (or duct) entrance from the breeching to account for a
sudden contraction plus a change in direction:
V22
∆P5 = 0.1186 (Customary) Eq. (49)
Tg + 460
V22
∆P5 = 0.176 (Metric) Eq. (49)M
Tg + 273
6. Flue Gas Pressure Drop through Convection Section - This pressure drop is calculated for each of the different zones
(bare tubes, extended surface tubes) in the convection section.
2
Nc Gcp fc
∆P6 = 0.01195 (Customary) Eq. (50)
ρ
2
Nc Gcp fc
∆P6 = 0.002 (Metric) Eq. (50)M
ρ
PRESSURE GAINS
The following pressure gains are found in the fired heater. They are caused by the difference between the density of the hot
gases inside the fired heater and that of the ambient air outside the fired heater. The theoretical draft per ft/m of height (stack
effect, SE) may be found from Figure 16. Be sure to use the Summer Design Air Temperature in determining available draft.
1. Radiant Section
∆PR = Stack effect caused by the radiant section.
= SE at the bridgewall temperature times the difference in height between the burner level and the top of the
radiant section.
2. Convection Section
∆PC = Stack effect caused by the convection section.
= SE at average convection section flue gas temperature times height of convection section.
3. Stack
∆PS = Stack effect in the stack.
= SE at average stack temperature times height of stack above top of convection section.
STACK HEIGHT
1. Calculations - Balances of pressure gains and losses must be made for natural draft burners and for the stack. In the
design of forced-draft systems, the fan is sized to cover the pressure drop through the burners. It is customary not to
consider the actual draft available at the burner level when sizing the fan.
a. Burners
Draft available at the burner level = ∆P7 + ∆PR Eq. (51)
The actual draft available usually equals or exceeds the requirements of the particular natural draft burner selected
(∆P8). However, if ∆P8 > ∆P7 + ∆PR, consideration should be given to revising the burner selection to one requiring less
draft. Otherwise, additional stack height must be added to cover this deficiency.
b. Stack - The calculated minimum stack height is based on maintaining a negative pressure at the top of the radiant
section (∆P7 = 0.10 in. H2O or 0.025 kPa). As discussed above, additional height must be added if necessary to provide
the required draft at the burner.
∆PS = [ ∆P1 + ∆P2 + ∆P3 + ∆P4 + ∆P5 + ∆P6 + ∆P7 ] − ∆PC Eq. (52)
∆PS
Hm = Eq. (53)
SE at average stack temp.
C = 6 in.
Intermediate process fluid temperatures and flue gas temperatures can be calculated from the specific heat of the process fluid
and the charts showing heat available in flue gas. However, for convenience in determining these temperatures, it is helpful to
develop temperature - heat duty (T-Q) curves for the process fluid and flue gas. (See the example below).
1700 620
Qsr
1600 600
1500 580
Flue Gas
1200 520
1100 500
1000 480
Process
Fluid
900 460
800 440
700 420
600 400
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Heat Absorbed In Convection Section, MBtu/hr
Recalculate parameters based on Tg1, Tb1, and ∆T1 and use with results obtained above.
0.40
Tg1 + 460
= 3.32
100
hc = 1.415 x 3.32 = 4.65 Btu/hr ft2 °F
F1 = 1.32 (Based Tg1 & Tm = 600°F) see Figure 3
F2 = 2.54
hr = 1.32 x 2.54 = 3.35 Btu/hr ft2 °F
ho = 4.65 + 3.35 = 8.00 Btu/hr ft2 °F
1 1
= = 0.08333 + 0.00364 + 0.00095 = 0.08792
U 1.5 x 8.00
U = 11.37 Btu/hr ft2 °F
from Eq. (32)
∆Tf = 11.37 x 953 x 0.00364 = 40o F
144244 3
116.5
G c , lb / sec − ft 2 = 0.498 0.394 from Eq. (1)
Af
0.55
Gc = 0.681 0.600
0.45
Do = 6.625 in., Do = 2.34 Same
0.48
Tg1 + 460
3.96 Same
100
0.55
Gc 0.55 8.07 7.11 from Eq. (28a)
he = 7 x x 4.05 = 12.21 x Gc =
2.34
he′, Btu/hr ft2 °F = 6 he = 48.4 42.6 from Eq. (38a)
Studded Tube Areas
ns = 22 studs/row see Page 6
0.1058 0.1067
U, Btu/hr ft2 °F = 9.45 9.37
Nc Gcp 2 fc
∆P6 , in. H2O = 0.01195 = 0.014 0.015 0.025 0.297 from Eq. (50)
ρ
Σ∆P6 = 0.351 in. H2O
Draft at Top of Radiant Section ∆P7
∆P7 = 0.10 in. H2O
Pressure Gain in Convection Section ∆Pc
1625 + 600 from Eq. (53)
Tg = = 1112 o F
2
Stack Effect SE = 0.009 in H2O/ft
Hc = 11 ft (approximate)
∆Pc = 0.009 x 11 = 0.099 in. H2O
Stack Height Hs
[ ]
∆Ps = 0.071 + 0.013 + 0.10 + 0 + 0.070 + 0.351 + 0.10 − 0.099 = 0.606 in. H 2 O
from Eq. (52)
3
2
1
DP8CFb
3130 ft 3 / sec
Stack Area = = 125 ft 2
25 ft / sec
= 3 x 0.1186
(25) 2 = 0.21 in. H20
600 + 460
∆Ps = [0.081 + 0.025 + 0.10 +0.21 + 0.070 + 0.351 + 0.10] – 0.099 = 0.838 in. H2O from Eq. (52)
600 + 460
Average Ts = = 530 o F
2
Stack Effect SE = 0.0061 in. H2O/ft see Figure 16
0.838 from Eq. (53)
Hm = = 137 ft
0.0061
Hs = 1.05 x 137 = 144 ft from Eq. (54)
Use Hs = 144 ft above convection section
(vs. Hs = 96 ft for furnace mounted stacks)
Qsr 310
800 Fl 300
ue
Ga Note: For actual design, a
s larger scale should be used. 290
700 280
270
600 260
250
Pro
500 ces 240
sF
luid
230
400 220
210
300 200
0 5 10 15 20 25 30 35 40
Ao 1 A 0.00406 0.00192
+ x = o =
0.484 1700 823
Ao 7.1 x 10 −3 Ao
+ x = = 0.00171 0.00081
0.506 27.4 1953
1 0.0108 0.0059
=
U′
U′, W/m2 °C = 92.4 169.5
Stud and Tube Metal Temperatures
Ao 1 161 139 from Eq. (34)
∆Tf , o C = U′ x 430 x x =
0.484 1700
71 62 from Eq. (35)M
7.1 x 10 −
3
Ao
∆Tm , o C = U′ x 430 x x =
0.506 27.4
Tb1, °C = 274 274
Tm, °C = Tb1 + ∆Tf + ∆Tm 507 493 from Eq. (29)
(km should be revised based on actual Tm, but the change is negligible for 5% Cr)
′′
E = 0.24 0.75 see Figure 7B
Tt, °C = 754 – E′′ (754 – Tm) 657 533 from Eq. (39)
(too high, try (OK)
shorter stud)
3
2
1
DP8CFb
88.27 m 3 / s
Stack Area = = 11.6 m 2
7 .6 m / s
1/ 2
4
Stack Diameter D s = A = 3.84 m
π
Estimate Stack Exit Temperature = 238°C see Figure 15
Pressure Drops ∆P3, ∆P5, ∆P6, ∆P7 will be the same as in Problem 6
Stack Exit Loss ∆P1
from Eq. (43)M
0.176 x 7.6 2
∆P1 = = 0.0199 kPa
238 + 273
Friction Loss ∆P2 is very small. Assume this is doubled to account for ducting and extra stack height
∆P2 = 2 x 0.0031 0.0062 kPa
Additional Losses ∆P4
At Location 1: Assume miter bend with turning vanes see Figure 11
∆P = 0.75 VH
At Location 2: Assume miter bend with turning vanes and baffle plate see Figure 12c
∆Pa = 0
∆P = 0.75 VH see Figure 11
At Location 3: Assume miter bend with no turning vanes see Figure 12e
V'1 = 0 (no other furnace using stack)
∆Pa = 0 see Figure 11
∆P = 1.5 VH
Σ∆P4 = (0.75 + 0.75 + 1.5) VH = 3.0 VH
7. 6 2
= 3 x 0.176 = 0.05187
315 + 273
∆P s = [0.0199 + 0.0062 + 0.0250 + 0.0518 + 0.0173 + 0.0873 + 0.025] − 0.0257 = 0.2068 kPa from Eq. (52)
315 + 238
Average T s = = 277o C
2
Stack Effect SE = 0.0051 kPa/m see Figure 16
0.2068 from Eq. (53)
Hm = = 40.5 m
0.0051
Hs = 1.05 x 40.5 = 42.5 m from Eq. (54)
Use Hs = 42.5 m above convection section
(vs Hs = 29.1 m for furnace mounted stacks)
NOMENCLATURE
A = Total outside surface area for section being designed, ft2 (m2)
Ab = Area of exposed bare tube surface, ft2/ft (m2/m)
Ac = Area at mean diameter of coke layer, ft2/ft (m2/m)
Ae = Area of extended surface on tube, ft2/ft (m2/m)
Af = Free cross-sectional area for flue gas flow, ft2 (m2)
Ai = Inside tube surface area, ft2/ft (m2/m)
Ai′ = Area at inside diameter of coke layer, ft2/ft (m2/m)
Am = Area at mean tube diameter, ft2/ft (m2/m)
Ao = Total outside surface area, ft2/ft (m2/m)
A1 = Upstream cross-sectional flow area, ft2 (m2)
A2 = Downstream cross-sectional flow area, ft2 (m2)
C = Corbelling width, in. (mm)
C1 = Peripheral maldistribution of heat transfer around radiant tube
Cvs = Stack flue gas velocity correction factor
Cvw = Stack wind velocity correction factor
Dcp = Tube diameter for convection section pressure drop calculations, in. (mm)
Df = Fin outside diameter, in. (mm)
Di = Inside tube diameter, based on average wall thickness, in. (mm)
Di′ = Inside diameter of coke layer, in. (mm)
Do = Tube outside diameter, in. (mm)
Ds = Stack diameter, ft (m)
d = Duct diameter ft (m)
dc = Equivalent diameter of a rectangular duct (for a circular duct with the same friction loss), ft (m)
ds = Stud diameter, in. (mm)
E = Extended surface efficiency factor
E′ = Local extended surface efficiency factor
E′′ = Local extended surface temperature factor
e = Turning vane spacing, ft (m)
fe = External fouling factor, hr ft2 °F/Btu (m2 °C/W)
fm = External surface maldistribution factor
FBL = Mean beam length correction factor
Fg = Gross fuel required, Ib/hr (kg/s)
Fn = Net fuel required, lb/hr (kg/s)
F1 = Temperature factor for determining hr
F2 = Convection section characteristic factor for determining hr
FG = Lb flue gas/lb fuel (kg flue gas/kg fuel)
fc = Friction factor for flue gas pressure drop, dimensionless
G = Fluid mass velocity through the coil, Ib/sec ft2 (kg/s m2)
Gc = Flue gas mass velocity through convection section (for heat transfer calculations), lb/sec ft2 (kg/s m2)
Gcp = Flue gas mass velocity through convection section (for pressure drop calculations), lb/sec ft2 (kg/s m2)
Hm = Calculated minimum stack height, ft (m)
Hs = Design stack height, ft (m)
HA = Heat Available from fuel, Btu/lb (kJ/kg)
NOMENCLATURE (Cont)
HAbw = Heat Available at bridgewall temperature, Btu/lb (kJ/kg)
HAs = Heat available at stack temperature, Btu/lb (kJ/kg)
hc = Heat transfer coefficient due to convection, Btu/hr ft2 °F (W/m2 °C)
he = Extended surface film coefficient, Btu/hr ft2 °F (W/m2 °C)
he′ = Local extended surface film coefficient, Btu/hr ft2 °F (W/m2 °C)
hf = Fin height (or length), in. (mm)
hi = Inside film coefficient, Btu/hr ft2 °F (W/m2 °C)
hl = Liquid inside film coefficient, Btu/hr ft2 °F (W/m2 °C)
ho = Outside film coefficient, Btu/hr ft2 °F (W/m2 °C)
ho′ = Local extended surface coefficient, Btu/hr ft2 °F (W/m2 °C)
hr = Heat transfer coefficient due to radiation, Btu/hr ft2 °F (W/m2 °C)
hs = Stud height (or length), in. (mm)
htp = Two phase inside film coefficient, Btu/hr ft2 °F (W/m2 °C)
hv = Vapor inside film coefficient, Btu/hr ft2 °F (W/m2 °C)
K = Pressure loss coefficient
Btu / hr ft 2
kc = Thermal conductivity of coke, (W/m °C)
°F / in.
Btu / hr ft 2
km = Thermal conductivity of tube wall, (W/m °C)
°
F / in.
Lb = Mean beam length for radiation in convection bank, ft (m)
Lc = Convection section inside length, ft (m)
LMTD = Logarithmic mean temperature difference between flue gas and process fluid, °F (°C)
lv = Length of turning vane straight section, ft (m)
Ma = Molecular weight of air = 28.84, lb/lb mol (kg/kg mol)
Mg = Molecular weight of flue gas, lb/lb mol (kg/kg mol)
Nc = Number of tube rows in convection section (in direction of flue gas flow)
Nt = Number of tubes per convection section row
nf = Number of fins per in. (fin spacing, mm)
ns = Number of studs per circular row
nv = Number of turning vanes
Pa = Air pressure, psia (kPa absolute)
Pg = Flue gas pressure, psia (kPa absolute)
pCO2 +H2O = Partial pressure of CO2 plus H2O in the flue gas, atmospheres (kPa)
ps = Stud row pitch, in. (mm)
∆P = Flue gas pressure drop, in. of water (kPa)
∆PC = Stack effect caused by the convection section, in. of water (kPa)
∆PR = Stack effect caused by the radiant section, in. of water (kPa)
∆PS = Stack effect in the stack, in. of water (kPa)
∆Pc = Flue gas pressure drop due to sudden contraction, in. of water (kPa)
∆Pe = Flue gas pressure drop due to sudden expansion, in. of water (kPa)
Qa = Total fired heater heat duty, MBtu/hr (MW)
Qc = Total heat absorbed in convection section, excluding shield section radiant duty, MBtu/hr (MW)
NOMENCLATURE (Cont)
Qf = Heat fired, MBtu/hr (MW)
Qr = Heat absorbed by radiant section surface, MBtu/hr (MW)
Qs = Total shield section heat duty, MBtu/hr (MW)
Qsc = Heat transferred in shield detection by convection, MBtu/hr (MW)
Qsr = Shield section radiant heat duty, MBtu/hr (MW)
Qtc = Total convection section heat duty, MBtu/hr (MW)
Qtr = Total fired heater radiant heat duty, MBtu/hr (MW)
qc = Heat absorbed in section being designed, MBtu/hr (MW)
R = Restriction to flow of flue gas through convection section, ft2 (m2)
Rb = Restriction from bare tube section, ft2 (m2)
Re = Reynolds number, dimensionless
Rf = Restriction from finned tube section, ft2 (m2)
Rs = Restriction from studded tube section, ft2 (m2)
Rsh = Restriction from shield section tubes, ft2 (m2)
Rt = Radius of ducting turns, ft (m)
rv = Radius of turning vanes, ft (m)
SL = Distance between tube centers in adjacent rows of convection section, in. (mm)
SR = Distance between centers of convection section tube rows, in. (mm)
ST = Distance between tube centers in horizontal row of convection section, in. (mm)
SE = Stack effect, in. of water per ft of height (kPa per m of height)
Ta = Ambient temperature, °F (°C)
Tb = Bulk fluid temperature, °F (°C)
Tb1 = Process fluid temperature leaving the section, °F (°C)
Tb2 = Process fluid temperature entering the section, °F (°C)
Tbw = Bridgewall temperature, °F (°C)
Tg = Flue gas temperature, °F (°C)
Tg1 = Flue gas temperature entering the section, °F (°C)
Tg2 = Flue gas temperature leaving the section, °F (°C)
Tm = Maximum tube metal temperature, °F (°C)
Tma = Length average radiant tube metal temperature, °F (°C)
Tmas = Length average shield tube metal temperature (on front 180° of all shield tubes), °F (°C)
Tms = Maximum shield tube metal temperature, °F (°C)
Ts = Stack temperature, °F (°C)
Tt = Maximum stud or fin tip temperature, °F (°C)
ta = Average thickness of tube wall, in. (mm)
tc = Design coke thickness, in. (mm)
tf = Fin thickness, in. (mm)
∆Tc = Temperature rise across coke layer, °F (°C)
∆Tf = Temperature rise across inside oil film, °F (°C)
∆Tm = Temperature rise across tube wall, °F (°C)
∆Ts = Estimated temperature loss in stack, °F (°C)
∆Tu = Uncorrected temperature loss in stack, °F (°C)
U = Overall heat transfer coefficient, Btu/hr ft2 °F (W/m2 °C)
U′ = Local overall heat transfer coefficient, Btu/hr ft2 °F (W/m2 °C)
Uc = Overall heat transfer coefficient in coked condition, Btu/hr ft2 °F (W/m2 °C)
NOMENCLATURE (Cont)
V = Velocity, ft/sec (m/s)
V1 = Upstream velocity, ft/sec (m/s)
V2 = Downstream velocity, ft/sec (m/s)
VH = Velocity head, in. of water (kPa)
Wc = Convection section inside width, ft (m)
Wf = Flue gas rate, Ib/sec (kg/s)
X = Weight fraction of vapor in the fluid
x = Depth of duct, ft (m)
y = Width of duct, ft (m)
α = Angle of bend in ducting, degrees
ε = Emissivity of tube surface, dimensionless
µ = Absolute viscosity, centipoises (Pa•s)
ρ = Density, Ib/cu ft (kg/m3)
φla = Radiant section front face length average heat density, Btu/hr ft2 (W/m2)
φr = Radiant section average heat density, Btu/hr ft2 (W/m2)
φs = Radiant heat density on front face of shield tubes, Btu/hr ft2 (W/m2)
φ1-side = Average radiant section heat density for tubes fired from one side only, Btu/hr ft2 (W/m2)
COMPUTER PROGRAMS
GUIDANCE AND CONSULTING
For up-to-date information on available programs and how to use them, affiliate personnel should get in touch with their Affiliate
Library Contact. Florham Park personnel should consult the Heat Transfer Equipment Section of ER&E.
LITERATURE
The following references are available:
• Fired Heater Simulation Program 03558 Manual Published by ER&E.
• Application Technology Set (ATS) Catalog No. CPEE126 Published by ER&E.
AVAILABLE PROGRAMS
The applicable programs available at the time of this writing are listed below:
PROGRAM TITLE AND DESCRIPTION
3558 Fired Heater Simulation Program
➧ This program has been incorporated into the Pegasys System and includes a new graphical user interface as well
as updated correlations. This program can be used for several design and trouble-shooting purposes:
• Fired Heater Simulation
Heat transfer calculations are performed for individual geometries in the convection section, thereby allowing
determination of process, flue gas and material temperatures. The program provides several options, giving
the user flexibility in choosing calculated variables. If desired, these options permit simulation of the entire fired
heater operation, including the radiant section. The following are determined for each geometry: (1) Flue gas
temperature in and out, (2) process temperature in and out, (3) heat duty, and (4) material temperature. The
heater geometry, number of tubes, tube materials, and extended surface type can be modified iteratively to
arrive at an acceptable design.
• Heat Available Curve
By defining the fuel gas or liquid composition, without the need to enter a furnace geometry, the program will
develop the heat available curve and lower heating value for that fuel.
• Stack Calculations
Once the fired heater geometry and process conditions have been established, the program can also be used
to design a stack or check the design of an existing one. The program can handle any ductwork or convection
section geometry in its calculations. The output is an itemized listing of the pressure losses and gains, as well
as the computed stack size if requested.
➧ CFX-4.2c Computational Fluid Dynamics (CFD) software available from AEA Technology
This program can be used to simulate fluid flow, heat transfer, and reactive chemistry in a fired heater, heat
exchanger, piping network, ducting, or other process equipment. CFX consists of intensive numerical solution
algorithms, which solve the conservation equations (mass, momentum, and energy). The user needs to specify the
geometry, fluid, boundary conditions, and the physics being modeled. A "picture" of the flowfield is obtained as well
as velocity, temperature, pressure, species concentration, etc. Changes to the existing design can be simulated
and tested prior to implementation in the field.
• Applications of this program have included the following:
Optimization of injector locations in a Thermal DeNOx application to reduce NOx emissions
Simulation of flame impingement in a POWERFORMER furnace
Simulation of fuel and air mixing patterns in a SATCON lift pipe
FIGURE 1A
CYLINDRICAL STUD EXTENDED SURFACE
DP8CF1A
FIGURE 1B
HELICAL FIN EXTENDED SURFACE
DP8CF1B
FIGURE 2
ARRANGEMENT OF CONVECTION SECTION TUBES
Tg2
Tb2
L
S
L
S
ST Tb1 ST
Tg1
a Notes
b
a = 3/4 in. (19.1 mm) min.
Extended b,d = 1 1/2 in. (38.1 mm) min.
Surface Tubes d
a is approxiamtely equal to 1/2 b
a is approxiamtely equal to c
Corbelling
c' b'
Convection
Section
Side Wall
WC
FIGURE 3
TEMPERATURE FACTOR F1
)
3.0 71° C
° F (8
1600
)
Tube Metal 60° C
400° F (7
Temperature 1
)
9° C
2.0 (64
0° F
120
)
8° C
(53
° F
00
10
C)
27°
(4
F
0°
1.0 80
Temperature Factor, F
0.9
0.8
)
°C
15
(3
0.7
F
0°
60
0.6
)
°C
04
(2
0.5
F
0°
40
C)
3°
(9
F
0.4
0°
20
0.3
0.2
600 800 1000 1200 1400 1600 1800 2000
FIGURE 4
PARTIAL PRESSURE OF CO2 + H2O IN FLUE GAS
0.35
0.30
, Atmospheres (10 –2 kPa)
0.25
+ H2O) 2
P (CO
Fuel %H H
0.20 (wt)
Comp. In Fuel C
H2 100
CH9 90 .750
C 0 0
0.10
0 20 40 60 80 100
FIGURE 5
CONVECTION SECTION CHARACTERISTIC FACTOR, F2
F2
1 1.5 2 3 4
1.0 30
.9
.8
.7 20
.6
.5
.4
10
.3
]
.2
+ H2O)
] + H2O)
2
5
Lb[P (CO
2
.15 Lb[P (CO
.10 3
.09
.08
.07
2
.06
.05
1.0
5 10 20 30
Metric [F2] DP8CF05
he ( or he')
hs kmds
ENGINEERING
0 .2 .4 .6 .8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
1.0
E = Efficiency Factor
E' = Local Efficiency Factor
.9 E" = Stud Tip Temperature Factor
hs = Stud Length, in. [mm]
ds = Stud Diameter, in. [mm]
.8 2
km= Stud Thermal Conductivity, Btu/Hr ft [W/m °C]
°F/in.
he = Stud Heat Transfer Coefficient,
.7 Btu/Hr Sq Ft °F [W/m2 °C]
he' = Local Stud Heat Transfer Coefficient,
Btu/Hr Sq Ft °F [W/m2 °C]
.6 Efficiency Factor E or E',
Based on he or he'
FIRED HEATERS
.5
FIGURE 6
SECTION AND STACKS
.4
STUD EFFICIENCY FACTORS E, E′, E′′
.3
PROPRIETARY INFORMATION - For Authorized Company Use Only
.2
Date
.1 Based on he'
VIII-C
.0
0 10 20 30 40 50 60 70 80 90 100
Page
December, 1999
he ( or he')
hs (Metric)
67 of 79
kmds
DP8CF06
DESIGN PRACTICES
Date
W (metric)
Section
he or he',
m2°C
VIII-C
0 28 57 85 113 142 170 227 283 340 397 453 510 567
1.0
Page
December, 1999
0.9
68 of 79
DESIGN PRACTICES
Stud Height, hs
5/8 (16)
0.7
3/4 (19)
0.6
1 (25)
0.5
1-1/4 (32)
0.2 3 (76)
SECTION AND STACKS
DESIGN OF CONVECTION
0.1
Scale
0
0 5 10 15 20 25 30 40 50 60 70 80 90 100
Btu/hr
Note: Assumed Stud Temperature = 800°F (425°C) he or he',
ft2°F
Btu/hr ft2
km = 280 (40 W/m°C)
°F/in.
DP8CF7A
EXXON
No significant change for other stud temperatures in range of 400 - 1200°F (200 - 650°C)
ENGINEERING
W
he', (metric)
m2°C
EXXON
0 28 57 85 113 142 170 227 283 340 397 453 510 567
1.0
ENGINEERING
0.9
0.8
Stud Height, hs
0.7
in. (mm)
5/8 (16)
0.6
3/4 (19)
0.5
FIRED HEATERS
FIGURE 7B
0.4
SECTION AND STACKS
1 (25)
0.3
1-1/4 (32)
STUD TIP TEMPERATURES FACTORS E′′
PROPRIETARY INFORMATION - For Authorized Company Use Only
0.2
1-1/2 (38)
FOR 1/2 in. (12.7 mm) DIAMETER CARBON STEEL STUDS
1-3/4 (44)
0.1
2 (51)
Date
Scale
3 (76)
VIII-C
0
0 5 10 15 20 25 30 40 50 60 70 80 90 100
Btu/hr DP8CF7B
Note: Assumed Stud Temperature = 800°F (425°C) he',
ft2°F
2
Page
Btu/hr ft
December, 1999
No significant change for other stud temperatures in range of 400 - 1200°F (200 - 650°C)
DESIGN PRACTICES
Date
Section
VIII-C
he ( or he')
hf kmtf (metric)
0 10 20 30 40 50 60 70 80 90
1.0
Page
December, 1999
E =Efficiency Factor
70 of 79
4.0
FIGURE 8
0.4
0.3
SECTION AND STACKS
DESIGN OF CONVECTION
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
he ( or he')
hf kmtf DP8CF08
EXXON
ENGINEERING
he'
(metric)
EXXON
hf kmtf
0
ENGINEERING
10 20 30 40 50 60 70 80 90
1.0
0.9
E" =Fin-Tip Temperature Factor
hf =Fin Height, in. (mm)
0.8 Do =Tube Diameter, in. (mm)
Df =Diameter Across Fins, in. [mm]
=Do + 2hf
tf =Fin Thickness, in. (mm)
0.7
km =Fin Thermal Conductivity,
Df Btu/Hr ft2
(W/m • °C)
Do = 1.0 °F/In.
0.6 he' = Local Fin Heat Transfer Coefficient,
Btu/Hr ft2 °F (W/m2 • °C)
1.4
0.5
FIRED HEATERS
Factor E"
2.0
FIGURE 9
SECTION AND STACKS
0.4
DESIGN OF CONVECTION
3.0
0.3
FIN TIP TEMPERATURE FACTOR E′′
PROPRIETARY INFORMATION - For Authorized Company Use Only
0.2
Date
0
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
he'
Page
hf DP8CF09
December, 1999
kmtf
71 of 79
DESIGN PRACTICES
DESIGN PRACTICES FIRED HEATERS
Section Page DESIGN OF CONVECTION
VIII-C 72 of 79 SECTION AND STACKS EXXON
Date ENGINEERING
December, 1999 PROPRIETARY INFORMATION - For Authorized Company Use Only
FIGURE 10
FLUE GAS PRESSURE GAINS AND LOSSES
S
2
Stack Effect
in Stack Stack Friction in Stack and Ducts
HS
Pressure Drop Across Damper
3
4
20° Min.
5
Stack Entrance Losses
C Convection 40 ft Max.
Section
HC 6 (12.2 m Max.)
Stack Effect
in Convection Convection Section Pressure Drop For Each Take-Off
Section
Side View
R Radiant
Section
Stack Effect HR
in Radiant
Section
8
Burner Pressure Drop
DP8CF10
FIGURE 11
PRESSURE LOSSES IN BENDS
α +
Rt
y d
Miter Rt / x > 0.5 Rt / x > 0.5
α V2 α V2
∆P = K ( 90°) (0.1186) ( Tg + 460 ) Or Metric [ ∆P = K ( 90° ) (0.176 ) ( Tg + 273 )]
K Factors
Duct Type Rt / x
Miter 0.5 0.75 1.0 1.5
Rectangular Ducts, No Turning Vanes 1.5 1.1 0.5 0.3 0.2 Valid for y/x ≥ 0.4
Rectangular Ducts, With Turning Vanes 0.75 0.3 0.1 0.1 0.1 }
For y/x < 0.4 multiply by 1.2
Circular Ducts 0.9 0.9 0.5 0.35 0.25
Turning Vanes
lv
+ rv x
e lv
e
Note 1
+
Note 1: Inside and outside corners of miter bend should be rounded to the same radius as that of the vanes.
DP8CF11
FIGURE 12
DUCTING ARRANGEMENTS
40 ft Max.
(12.2 m Max.)
For Each
Take-Off
(a) Typical Breeching Arrangement
Baffle Plate
V1 V1
α
∆ Pa = Approx. 6VH ∆ Pa = 0 V1
45° ∆ Pa = 3 VH (α = 45°)
AVOID Max.
∆ Pa = 0.7 VH (α = 22°)
(b) (c) (d)
Baffle Plate
Notes:
(1) Losses listed above (∆Pa) are due to intersection of flue gas streams, and are IN
ADDITION yo normal bend and expansion or contraction losses.
(2) VH = Velocity Head
(3) Losses listed are typical and should be used for design. See the following references if more
details of bend and arrangement losses are required:
ASHRAE, Guide and Data Book, 1969
General Electric Co., Heat Transfer and Fluid Flow, 1970 DP8CF12
FIGURE 13
CONVECTION SECTION FRICTION FACTOR
0.20
1.0
[ µ x 10-3 = 2000 ] 0.20
1.5 [ µ x 10-3 = 8000 ]
SL/Dcp 1.0
0.15 1.0 0.15
fc fc SL/Dcp
1.5
0.10 0.10 1.0
0.09 2.0 0.09
1.5
0.08 3.0 0.08
2.0
0.07 0.07 3.0
0.06 0.06
0.05 0.05
1.0 1.5 2.0 2.5 3.0 4.0 1.0 1.5 2.0 2.5 3.0 4.0
ST ST
Dcp Dcp
0.10 0.10
0.09 SL/Dcp 0.09
0.08 0.08
1.0
0.07 0.07 SL/Dcp
1.5
0.06 2.0 0.06 1.0
3.0 1.5
0.05 0.05 2.0
3.0
1.0 1.5 2.0 2.5 3.0 4.0 1.0 1.5 2.0 2.5 3.0 4.0
ST ST
Dcp Dcp
Note:
For nomenclature and explanatory sketch, see Figure 13A.
Source: E.D. Grimison - Trons - ASME Pro - 59 - 8, 1937 DP8CF13
FIGURE 13A
CONVECTION SECTION FRICTION FACTOR
(EQUILATERAL PITCH)
0.20 1.2
1.3
0.15 1.5
1.8
2.0
fc
0.10
3.0
0.04
15 20 30 40 50 60 80 100 200 300 400 500
Dcp Gcp
µ
Nt = Number of tubes per row
fc = Friction factor
Wc
Dcp = Outside diam. of tubes and extended surface, in. (mm)
Gcp = Mass velocity = Wf/Af = lb/sec ft2 (kg/s m2)
ST
Dcp Wf = Flue gas rate, lb/sec (kg/s)
DcpNt + C DcpNt + C
+ + + Af = Free flow area = Lc Wc – (
12 , ft ) [
2
; = Lc(Wc –
1000 ) ], m 2
Nc G2cp fc
DP8CF13a
or Metric [ ∆P 6 = 0.002
ρ ]
FIGURE 14
APPROXIMATE STACK TEMPERATURE LOSSES FOR STEEL STACKS
700 700
1200 1200
.0 m)
m)
600 600
10 ft (3
(1.2
m)
1000 1000
m)
(3.0
4 ft
)
m
)
(Ts - Ta), °C
(Ts - Ta), °C
(Ts - Ta), °F
(Ts - Ta), °F
m
500 500
1.8
.6
.2
(0
t
t (
10 f
(1
ft
800 800
6f
ft
2
4
.=
400 400
m
ia
D
m)
k
ac
600 0.6 600
St
t ( 300 300
2f
.=
iam
400 kD 400
ac 200 200
St
200 200
0 100 200 0 100 200
∆ Tu, °F/100 ft ∆ Tu, °F/100 ft
Uninsulated Stack Insulated Stack
Correction Factors
Velocity Type Uninsulated Insulated
Stack Stack
Stack Gas Velocity
ft/sec (m/s) Cvs Cvs
FIGURE 15
APPROXIMATE STACK EXIT TEMPERATURES FOR CONCRETE STACKS
300 90
3.6)
.4)
.6)
.3)
.0)
5.0)
.5)
)
28 (8.5
8 (2
4 (0
2 (0
20 (6
24 (7
12 (
16 (
200 60
Stack Height, ft
Stack Height, m
)
(m
,. ft
100 iam 30
ckD
a
St
0 0
800 425
St
90 ac
0 kI
(4 nle
80 tT
) em
700 80 p. 370
0( ° F(
42 °C
5) )
70
0(
37
0)
600 315
600
(31
5)
500 260
500
(26
0)
400 205
400 (
205)
200 95
DP8CF15
FIGURE 16
STACK EFFECT
Fundamental Equation
1900
Ma Pa Mg Pg
SE = 0.01796 [T - ] 1000
1800 a+ 460 Tg + 460
or Metric
]]
Ma Pa Mg Pg
1700 [ SE = 0.001181 [T
a + 273
-
Tg + 273
900
1600 SE = Stack effect, in. of water per foot of height
(kPa per meter of height)
Ma = Mol. wt. of air = 28.84
1500
Mg = MW of flue gas. Varies from 28.00 to 28.84
800
(assumed to be 28.84 for this chart)
1400 Pa = Air pressure, psia (kPa, abs)
Pg = Flue gas pressure,psia (kPa, abs)
Pa = 14.7 psi for this chart (101 kPa)
1300 Ta = Air temperature, °F (°C)
700
Tg = Flue gas temperature, °F (°C)
1200
1100 600
1000
500
900
800
400
700
600
Air Temperature, ºF (ºC) 300
60 (°C)
500
70 (°C)
80 (°C)
400 90 (°C)
200
100 (°C)
110 (°C)
300 120 (°C)
200 100
100
0 .002 .004 .006 .008 .010 .012