Professional Documents
Culture Documents
Changes shown by ➧
CONTENTS
Section Page
SCOPE ............................................................................................................................................................ 4
REFERENCES ................................................................................................................................................ 4
BACKGROUND .............................................................................................................................................. 4
INLETS............................................................................................................................................................ 5
LIQUID INLETS TO TOP TRAY.............................................................................................................. 5
LIQUID INLETS BETWEEN TRAYS ....................................................................................................... 7
VAPOR INLETS (INCLUDING KETTLE REBOILER RETURNS) ........................................................... 7
VAPOR-LIQUID INLETS (EXCLUDING REBOILER RETURNS) ......................................................... 10
DESIGN OF PERFORATED PIPE DISTRIBUTORS ............................................................................ 11
DESIGN / RATING OF FLASHBOX INLETS ........................................................................................ 12
WATER DRAWOFFS.................................................................................................................................... 41
HINGED TRAYS............................................................................................................................................ 53
TRANSITIONS .............................................................................................................................................. 54
CONTENTS (Cont)
Section Page
DEENTRAINMENT DEVICES....................................................................................................................... 57
WIRE MESH ENTRAINMENT SCREENS (CWMS) ............................................................................. 57
VANE-TYPE MIST ELIMINATOR (CHEVRONS).................................................................................. 58
NOMENCLATURE ........................................................................................................................................ 66
TABLES
Table 1 Major Truss Information .................................................................................................. 5
Table 2 Setting Notch And Lip Dimensions For Circular Chimneys ........................................... 46
FIGURES
Figure 1 Tray Supports.................................................................................................................. 5
Figure 2 Liquid Inlets To Top Tray................................................................................................. 6
Figure 3 Liquid Inlets Between Trays ............................................................................................ 7
Figure 4A Vapor Inlets Between Trays ............................................................................................ 8
Figure 4B Vapor Inlets Between Trays ............................................................................................ 9
Figure 5A Vapor-Liquid Feed Distributor Between Trays Of New Towers ..................................... 10
Figure 5B Vapor-Liquid Feed Distributor For Typical Flashbox Layout.......................................... 13
Figure 5C Vapor-Liquid Feed: Flashbox Design For Side Downcomer Arrangement ................... 14
Figure 5D Vapor-Liquid Feed: Flashbox Design For Center / Off-Center
Downcomer Arrangements............................................................................................ 15
Figure 6A Perforated Pipe Distributors .......................................................................................... 16
Figure 6B Pipe Distributor Arrangement For Four-Pass Trays ...................................................... 16
Figure 7 Distributor Arrangements .............................................................................................. 17
Figure 8 Insulating Baffles For Downcomers............................................................................... 17
Figure 9 Surfaces At Feed Inlet Locations .................................................................................. 17
Figure 10 Vapor Side Drawoffs ..................................................................................................... 18
Figure 11 Drawoff Nozzle Location Vs. Diameter......................................................................... 19
Figure 12 Drawoff With Seal Dam – Side (Outboard) Downcomer................................................ 20
Figure 13 Drawoff With Seal Dam – Center (Inboard) Downcomer............................................... 20
Figure 14 Drawoff Without Seal Dam – Side (Outboard) Downcomer........................................... 21
Figure 15 Drawoff Without Seal Dam – Center (Inboard) Downcomer.......................................... 21
Figure 16 Spacing And Free Area Requirements For Trays With Drawoff Boxes ......................... 23
Figure 17A Coke Strainer (For Vacuum Pipestills, Cat Fractionators And Other
Fouling Services) .......................................................................................................... 24
Figure 17B Coke Strainer (For Delayed Coking Fractionators and Other Very Fouling Services)... 25
Figure 18 Bottom Tray Seal .......................................................................................................... 26
Figure 19 Drawoff Pan And Reboiler Return Arrangement ........................................................... 30
Figure 20A Alternative Seal Pan Elevation ...................................................................................... 33
Figure 20B Alternative Reboiler Drawoff And Return Configuration With Flashbox Return ............. 34
Figure 21 Reboiler Drawoffs (Single-Pass Trays) ......................................................................... 35
Figure 22 Reboiler Drawoffs (Two-Pass Trays)............................................................................. 36
Figure 23 Mid-Reboiler Drawoff Tray Details ................................................................................ 37
Figure 24 Intercooler Drawoff Tray Details.................................................................................... 39
Figure 25 Water Drawoff Tray Details ........................................................................................... 41
Figure 26 Chimney Trays - Layout (Total Drawoff)........................................................................ 43
CONTENTS (Cont)
Section Page
Figure 27 Spacing Requirements Of Chimney Trays .................................................................... 45
Figure 28 Details Of Drawoffs On Chimney Trays......................................................................... 48
Figure 29A Chimney Details ............................................................................................................ 49
Figure 29B V-Hat Rectangular Chimney Details .............................................................................. 50
Figure 30 Tangential Vapor-Liquid Inlet (Annular Ring)................................................................. 51
Figure 31 Pipestill Collector Ring And Collector Pan Details ......................................................... 52
Figure 32 Hinged Tray ................................................................................................................... 53
Figure 33 Tray Transitions: One-Pass To Two-Pass With Liquid Or Vapor-Liquid Feed............... 54
Figure 34 Tray Transitions: Two-Pass To One-Pass (Center Downcomer)................................... 55
Figure 35 Tray Transitions: Two-Pass To One-Pass (Side Downcomer) ...................................... 56
Figure 36 Vane-Type Mist Eliminator ............................................................................................58
Figure 37 CWMS Pressure Drop - Friction Factor ......................................................................... 59
Figure 38 CWMS Pressure Drop - Liquid Holdup .......................................................................... 60
Revision Memo
12/00 The highlights of this revision are:
1. Deleted reference to IP 5-2-1 regarding seal welding in the downcomer floor area.
2. Reverted to common industry nomenclature regarding side, center and off-center
downcomers. Also reverted to downcomer width instead of rise. (The older terms are still in
parentheses.)
3. Added discussion on the potential problem with hydraulic hammer at reflux inlets and design
considerations to avoid problems.
4. Added criteria to ensure all feed and drawoff tray assemblies do not limit tower section.
5. Added references to Section III-G for additional recommendations on vapor distributors in
packed towers.
6. Added an alternative configuration for vapor inlets between trays (new Figure 4B). Showed
alternative locations for distributor vent and drain holes (revised Figure 7C).
7. Included a discussion on designing/rating flashbox inlets and added new Figures 5B, 5C,
and 5D.
8. Added the preferred distributor arrangement for four-pass trays (new Figure 6B).
9. Added that internal piping for drawoffs is not the preferred design and made same notation
on Figure 11. Added a note to check the vendor design of seal pan weirs to avoid possible
interference from horizontal stiffening flanges. Removed option of total drawoff with no
downstream distributor from notes for Figures 12, 13, 14, 15. Showed drawoff box sloped
sides as an option in Figure 16 to minimize interference at downcomer inlets.
10. Changed discussion regarding when an extended downcomer design is permissible for
tower bottoms. Also included a discussion on the various types of tower bottom
configurations for thermosiphon reboiler circuits, forced circulation arrangements, kettle
reboiler arrangements, and internal reboiler arrangements. Included a discussion on
evaluating the impact of entrainment from the reboiler return nozzle/distributor and options to
reduce/handle entrainment. Included an alternative reboiler drawoff and return configuration
with a flashbox return (new Figure 20B). Added notes to Figures 21 and 22.
11. Added chimney tray design notes. Revised chimney tray lower open area from 10% to 15%.
Changed reasonable range for chimney tray open area from 10 to 25% to 15 to 30%. Added
comment regarding higher open area for vacuum tower chimney trays. Included the V-hat
design for rectangular chimney hats as the preferred design(new Figure 29B).
12. Added comment regarding use of conical hat chimney trays below tangential inlet to improve
vortex action and stripping tray performance.
13. Added notes for Eq. 10 and added Eq. 13. Added note stating that an orifice coefficient of
0.7 for perforated plates is adequate for rough estimates only and not suitable for detailed
head calculations for liquid distributors.
14. Added conceptual design of coker strainer for severe fouling services (new Figure 17B).
SCOPE
This section covers the techniques for specifying the process design features of tower internals other than the basic contacting
devices. Detailed mechanical design is normally handled by the fabricator. This section covers distributors, drawoffs, tray
supports, nozzle arrangements for feed and products, reboiler circuitry, coke strainers and entrainment screens. See Section
lll-G for packed or grid tower internals that are not covered here, such as liquid distributors and spray nozzles.
REFERENCES
DESIGN PRACTICES
• Section V Drums • Section XII Instrumentation
• Section IX Heat Exchange Equipment • Section XIV Fluid Flow
INTERNATIONAL PRACTICE
IP 5-2-1 Internals for Towers and Drums
➧ OTHER REFERENCES
1. Atmospheric Pipestill Guide, EMRE Manual No. EEPE 006
2. Fractionating Tower Troubleshooting Guide, EMRE Manual No. TMEE 021
3. Fuels Vacuum Pipestill Guide, EMRE Manual No. EETD 076
4. Mobil Technology Company Process Design Practices, Practices No. II, Volume No. 2, Trayed Tower Internals
5. Sideropoulos, T., Tower Reboiler Return Arrangements - Test Program Results and Tentative Recommendations for
Design Practices Changes, 99CET 018, January 28, 1999
BACKGROUND
For trouble-free startup and normal operation of fractionating towers, it is imperative that all auxiliary equipment (i.e., drawoffs,
return distributors, entrainment screens, etc.) be properly designed. The design techniques presented herein have been
developed over a number of years and will generally assure economical, trouble-free operation.
TRAY SUPPORTS
The method by which trays are supported is set by the fabricator during the detailed design. The supports must meet or
exceed the minimum standards of IP 5-2-1. The number, size, and thickness of the support members depend on several
factors, including tower diameter, the load to be supported, the need for accessibility for maintenance, and the corrosion
allowance required.
Typically, in towers with diameters less than about 10 ft (3000 mm), the entire load of the tray is transmitted to the shell via the
tray support ring which is 0.25 - 0.50 in. (6 - 13 mm) thick. In towers greater than 10 ft (3000 mm), the load is carried by one or
more trusses attached to the shell as well as by the support ring. These items are discussed in more detail below.
➧ SUPPORT RINGS
The required width of support rings (Figure 1) is generally between 2 and 3 in. (50 - 75 mm) and increases with increasing
tower diameter. The tray panels and the minor trusses are attached to the support ring by bolts or clips.
For maintaining tray efficiency at low liquid loadings in critical services, consider continuously seal welding the downcomer floor
to the support ring to prevent leakage. Also consider seal welding whenever the downcomer floor panels are oriented parallel
to the direction of liquid flow (perpendicular to the edge of the downcomer) and the seams extend under the downcomer.
➧ TRUSSES
The minor trusses on trays are frequently formed as an integral part of the tray panel (i.e., integral truss). This reduces overall
cost and permits faster installation. For tower diameters greater than about 10 ft (3000 mm) major trusses are usually needed
in addition to minor trusses and support rings (see Figure 1B and Table 1). For tower diameters up to about 20 ft (6000 mm),
these trusses usually consist of I-beams or channels. Where the tower diameter is greater than about 20 ft (6000 mm), built-up
“lattice" type trusses are normally used and two trays are usually supported from each set of trusses (Figure 1C). Enough
open area is built into “lattice" trusses to insure good lateral vapor distribution and to provide access to tray sections on both
sides of the truss.
FIGURE 1
TRAY SUPPORTS
A B C
Tray Support Ring Major/Minor Trusses Lattice Truss
Minor
Trusses Tray A
Weld To
Shell
Major
Truss
Vessel
Tray Support Shell Liquid Flow
Ring
Tray B
DP3HF01
TABLE 1
MAJOR TRUSS INFORMATION
INLETS
Proper introduction of a vapor, liquid or vapor-liquid stream onto a tray is essential for reaching the hydraulic capacity potential
of the internals. This section contains guidelines for selection and design of a) liquid inlets to top tray, b) liquid inlets between
trays, c) vapor inlets, including kettle reboiler returns, and d) vapor-liquid inlets, excluding reboiler returns. It also includes
guidelines for the design of perforated pipe distributors. Vapor-liquid reboiler returns are discussed under REBOILER
DRAWOFFS AND RETURNS and tangential inlets are discussed under FLASH ZONES AND TANGENTIAL (ANNULAR
RING) INLETS.
INLETS (Cont)
Reflux inlets must be carefully designed for configurations in which the tower vapor can flow into the reflux line at low reflux
rates and the vapor can suddenly collapse by mixing with the colder reflux stream, resulting in hydraulic hammer and vibration.
Long horizontal piping runs at the reflux inlet nozzle elevation should be avoided. A FRACTIONATION SPECIALIST should be
consulted when evaluating options for sealing a reflux inlet nozzle or distributor with a sub-cooled reflux stream to avoid
hydraulic hammer. Although seldom used in trayed towers, reflux distributors with downtubes should be avoided. This is
because of potential problems with liquid maldistribution caused by siphoning effects. Please consult with a FRACTIONATION
SPECIALIST if you are rating a tower with this configuration.
FIGURE 2
LIQUID INLETS TO TOP TRAY
A B C
SINGLE-PASS CENTER (INBOARD) SIDE (OUTBOARD)
TRAY DOWNCOMER DOWNCOMERS
OF DOUBLE-PASS TRAY OF DOUBLE-PASS TRAY
False
Baffle Downcomers
False (7)
1.5 Dr Down- 1.5 Dr
Dr comer Dr
False
Downcomer
Baffle Dr
Top Top
Open Open
VIEW A-A VIEW B-B VIEW C-C
(4)
(6) False
(5) (2)
(1) Downcomers
(1)
(1)
DP03Hf02
INLETS (Cont)
➧ FIGURE 3
LIQUID INLETS BETWEEN TRAYS
Notes:
(1) The distance between the bottom of the
distributor and the tray below should be about
9 in. (225 mm). Revamps or designs with
large downcomer clearances should ensure
(2) (3) that the distributor liquid impinges a minimum
A A
(4) of 2 in. (50 mm) above the clearance. An
impingement point can be determined by
(5) drawing a straight line from the center of the
distributor through the center of the distributor
(1)
holes or slots.
(2) The distance between the distributor and the
downcomer or insulating baffle (Figure 8)
should be about 3 in. (75 mm).
(3) The minimum distance between the top of the
distributor and the tray above is 8 in. (200
View A-A mm).
(4) For flooding calculations, treat the projected
area of the distributor and insulating baffle (if
used) as waste area.
The distributor holes or slots should discharge downward at a 45° angle for vertical downcomers and at a lesser angle from
the horizontal for sloped downcomers. The distributor holes should be designed according to the method outlined under
Design of Perforated Pipe Distributors in this subsection. Stepped downcomers should be avoided at tower inlet
locations. For trays with modified arc downcomers and for distributors on trays without downcomers from above (e.g., one
side of a one-to-two pass transition tray) see Design of Perforated Pipe Distributors and Figure 7(B).
(5) To prevent vaporization in the downcomer of the tray above the feed, an insulating baffle should be provided when the feed
temperature exceeds the temperature of the downcomer liquid (Figure 8). The impingement surfaces for feed inlets should
be smooth (Figure 9). DP03Hf03
INLETS (Cont)
Distributors Below the Bottom Tray should avoid interference between the vapor and the bottoms liquid or the liquid leaving
the seal pan(s). They should direct the vapor downward and toward the vessel wall, employing one or two rows of holes or
slots, each at about 45° angle from the horizontal. The distance between the top of the distributor (or flush nozzle) and the tray
above should be minimum, but not less than 8 in. (200 mm). The minimum distance between the bottom of the perforated pipe
distributor and the high (or the emergency) liquid level is the greater of 24 in. (600 mm) or one pipe diameter. See DESIGN OF
PERFORATED PIPE DISTRIBUTORS.
Distributors Below the Bottom Packed Bed should be as symmetrical as possible to minimize vapor maldistribution. They
should have 2 or more legs (i.e., be “T" or “H" shaped) and should direct the vapor downward, employing two rows of holes or
slots on each leg, each discharging at about 45° angle from the horizontal. There should be 12 in. (300 mm) between the top
of the distributor and the packed bed above. The minimum distance between the bottom of the perforated pipe distributor and
the high (or the emergency) liquid level is the greater of 24 in. (600 mm) or one pipe diameter. See DESIGN OF
PERFORATED PIPE DISTRIBUTORS and Section III-G, VAPOR DISTRIBUTORS for additional requirements.
Distributors Between Packed Beds or Distributors Between a Tray and a Packed Bed. For these less common cases see
Section III-G and consult your FRACTIONATION SPECIALIST.
Distributors or Flush Nozzles Between Trays. See Figure 4A and Figure 4B.
➧ FIGURE 4A
VAPOR INLETS BETWEEN TRAYS
Notes:
(1) Flush nozzles should be used only if the vapor added is less than 6% of
the tray’s vapor load and good distribution is not critical. They should be
(3) radial, line-size, and discharge across the tray perpendicular to the liquid
flow. Figure 4B shows an alternative configuration with an inlet baffle.
(6)
Dr (2) Perforated pipe distributors between trays should have two rows of holes
discharging horizontally in opposite directions. They should be
(5) perpendicular to the liquid flow and centered under the bubble area of the
tray above. See Design of Perforated Pipe Distributors in this
Flush Nozzle (1) (4) subsection.
or Distributor (2) (3) The distance between the top of the distributor or flush nozzle and the
tray above should be minimum, but not less than 8 in. (200 mm).
(4) Provide at least 2/3 of the normal tray spacing (the higher of the tray
below or above) between the bottom of the distributor or flush nozzle and
the tray below.
(5) The feed tray should be designed such that it is not the limiting tray in a section. The tray spacing should be the higher of:
(a) the spacing of the tray below or above, (b) the sum of the dimensions (3), (4) and Dr or (c) the tray spacing that satisfies
the tray hydraulic calculations described below.
Two sets of calculations should be made for the feed tray:
(A) For all criteria other than jet flood and ultimate capacity: Follow the standard calculation procedure (it uses the vapor
entering the tray from below and the total liquid leaving the feed tray).
(B) For jet flood and the ultimate capacity: Repeat calculation for item (A) using a waste area that includes the projected
areas of the feed distributor and the insulating baffle (if present); also, the vapor rate and density should be those of
the total vapor entering the tray above.
(6) To prevent vaporization in the downcomer of the tray above the feed, an insulating baffle should be provided when the feed
is directed against the downcomer and its temperature exceeds the temperature of the downcomer liquid (Figure 8).
DP03Hf04a
INLETS (Cont)
➧ FIGURE 4B
VAPOR INLETS BETWEEN TRAYS
ALTERNATIVE CONFIGURATION WITH NOZZLE INLET BAFFLE (6)
A 1.5 Dr
1 Dr
0.5 L
L Dr (Note 4)
A
C
L
0.5 Dr
(Note 2)
View A-A Dr L
(Note 3) (Note 5)
Notes:
(1) For existing nozzles, Dr is the nozzle diameter. For new nozzles, Dr and L are sized to meet a max F-factor
of 20 (24), where F-factor = Vn ρv .
(2) Minimum spacing is measured from the top of the nozzle to the tray above. This spacing applies from the
top of the baffle to the tray above. It is 6 in. (150 mm) for tower diameters < 10 ft. (3 m) and 9 in. (225 mm)
for larger towers.
(3) Inlet nozzle must be parallel with downcomer panel and located on the vessel centerline.
(4) For existing nozzles, baffle is required when F-factor > 20 (24). L is sized to limit discharge F-factor to < 20
(24) with a minimum of 1.5 Dr. The baffle is closed on the top and the bottom and open on the sides for
vapor flow.
(5) Minimum spacing is from the bottom of the nozzle to the tray below. This spacing applies from the bottom of
the baffle to the tray below. This spacing is 3/4 of the tray spacing or 18 in. (450 mm) minimum.
(6) Design Criteria from Reference 4. DP03Hf04b
INLETS (Cont)
FIGURE 5A
VAPOR-LIQUID FEED DISTRIBUTOR BETWEEN TRAYS OF NEW TOWERS
Notes:
(1) The distance between the bottom of the
distributor and the tray below should be at
least the normal tray spacing (the higher of
the tray above or below). For evaluating
(3) (4) existing towers see the text.
(2) The distance between the distributor and the
A A downcomer or insulating baffle should be
(2) about 3 in. (75 mm).
(5) (3) The minimum distance between the top of the
(1)
distributor and the tray above is 8 in. (200
mm).
(4) The distributor holes or slots should
discharge downward at a 45° angle for
vertical downcomers and at a lesser angle
from the horizontal for sloped downcomers.
The distributor holes should be designed
View A-A according to the method outlined under
Design of Perforated Distributors in this
subsection. To ensure equal vapor/liquid
distribution between the two
passes of a two-pass tray, the feed piping arrangement should be symmetrical. For trays with modified arc downcomers and
for distributors on trays without downcomers from above (e.g., one side of a one-to-two pass transition tray) see Design of
Perforated Pipe Distributors and Figure 7(B).
(5) To prevent vaporization in the downcomer of the tray above the feed, an insulating baffle should be provided when the feed
temperature exceeds the temperature of the downcomer liquid (Figure 8). Downcomer apron panels at feed inlet locations
should provide a smooth surface for vapor/liquid impingement (Figure 9).
DP3HF05a
➧ Rating and Modifying Existing Vapor-Liquid Distributors Between Trays. The inlet arrangement should be evaluated by a
FRACTIONATION SPECIALIST if any of the following criteria are not met:
1. The distance between the bottom of the distributor and the tray below should be at least 2/3 of the normal tray spacing (the
higher of the tray above or below).
2. The feed impingement point on the downcomer should be a minimum of 12 in. (300 mm) above the tray deck. An
impingement point should be determined by drawing a straight line from the center of the distributor through the center of
the distributor holes or slots.
3. Criteria of Notes (2), (3), (4), or (5) in Figure 5A are not satisfied.
INLETS (Cont)
4. The adjusted jet flood and ultimate capacity should not cause the feed tray to be the limiting tray in the section. Increase
the tray spacing as required to insure this. In a revamp situation, one or 2 trays may need to be removed. Another
possible solution is to segregate the feed vapor from the feed tray rating by means of a flashbox. Please contact a
FRACTIONATION SPECIALIST for assistance with this type of design. To calculate the adjusted jet flood and ultimate
capacity: a) use a waste area that includes the projected areas of the feed distributor and any insulating baffle, b) use the
rate of the liquid leaving the trays, c) use the vapor rate and density to the tray above (except in the unusual case where
the vapor load, VL, to the feed tray is greater).
INLETS (Cont)
INLETS (Cont)
➧ FIGURE 5B
VAPOR-LIQUID FEED DISTRIBUTOR FOR TYPICAL FLASHBOX LAYOUT (5)
Flash Baffles
(Note 3)
Internal Slots
2" (50 mm)
Flanges (Note 2)
Wide Lips
Tee
Tee End
3" End Closed
3/8" (9 mm) (75 mm) No Slots Closed
Min.Drain
Normal Vapor Rates High Vapor Rates
D. Typical Slot Arrangement
C. Typical Slot Orientation
Notes:
(1) Flashbox arrangements are appropriate for flashing feed inlet nozzle at velocities below 100 ft/s (30 m/s).
(2) The discharge velocity of the two-phase mixture through the slots should be less than 6 ft/s (2 m/s).
(3) The distributor support and side baffles must be rigid enough to withstand the impact force of the fluid and vibration
effects. The minimum thickness for the flashbox baffles is 10 gage (0.134 in.) (3.5 mm).
(4) A FRACTIONATION SPECIALIST should be consulted when designing or rating a flashbox.
(5) Design Criteria from Reference 4. DP03Hf05b
➧ FIGURE 5C
VAPOR-LIQUID FEED: FLASHBOX DESIGN FOR SIDE DOWNCOMER ARRANGEMENT (11)
Flashbox Top Width
(Note 9)
Spacing 60" (1525 mm)
(50 mm)
Flashbox 1.5 Dr
Height
(Note 5)
3/4 TS or
18" (450 mm)
c + 2"(50mm)
min. (Note 8) (Note 7) c
Tray Below Feed Inlet 2"
(50 mm)
Inlet Width
(Note 4)
Flashbox
Top Width
2" (50 mm) Wide Lip
on Each Side of Downcomer
Flashbox Panels 2" (50 mm) Width
Slot 30°
C Slot Flashbox
L
30° Height
A A
Dr / 6 or 3" (Note 3)
View A-A (75 mm) min
Notes:
1. Flashing feed distributor should have an equal number of slots on each side
of distributor pipe. Maximum slot velocity is 6 ft/s (2 m/s).
2. No shaped lips are permitted on downcomer panels or flashbox baffles.
3. No slots are permitted on tee, except a 3/8" (9 mm) drain hole located on the bottom centerline of the tee.
4. Valves or sieve holes are to be omitted from the designated inlet width.
5. The free area adjacent to the flashbox for the vapor from the tray below must be sized for 85% of ultimate capacity or less.
6. The minimum width of the flashbox is twice the outside diameter of the pipe distributor or the pipe diameter plus 8 in. (200 mm),
whichever is greater. The net open area must be sized to minimize entrainment by designing for a capacity factor (Cs) of 0.3 ft/s
(0.1 m/s) or for 85% of ultimate capacity, whichever is less. The open area at the flashbox top excludes the area occupied by the 2 in. (50
mm) lips on both sides of the baffles. The lips help to prevent vapor from entraining liquid off the top of the baffle walls and also act as
stiffeners to add rigidity to the flashbox side baffles.
7. The flashbox bottom width for side flashbox arrangements should be sized to limit the downward liquid velocity to 0.6 ft/s (0.18 m/s) for
non-foaming systems and 0.4 ft/s (0.12 m/s) for foaming systems. The minimum allowable width is 3 in. (75 mm).
8. The minimum side flashbox clearance from the tray deck is the downcomer clearance plus 2 in. (50mm).
9. A minimum 2 in. (50 mm) spacing between the side flashbox baffle and the downcomer panel is required. This 2 in. (50 mm) clearance
prevents the flashing feed vapor/liquid from heating the liquid in the downcomer and avoids interference with downcomer stiffeners.
10. A FRACTIONATION SPECIALIST should be consulted when designing or rating a flashbox.
11. Design Criteria from Reference 4. DP03Hf05c
➧ FIGURE 5D
VAPOR-LIQUID FEED: FLASHBOX DESIGN FOR
CENTER / OFF-CENTER DOWNCOMER ARRANGEMENTS (4) (5)
1- Pass Tray 2- Pass Tray
4- Pass Tray
2- Pass Tray
Dr
Maximum
Velocity Velocity dependent on
Downcomer Design for
(Note 3) Maximum Horizontal Trays Below the Feed
Velocity Under the (Note 3)
Flashbox
(Note 2)
Inlet Weirs
Width = Downcorner
Width Bottom Width of Width
Trays Below
Designs With Inlet Weirs Designs Without Inlet Weirs
D. Flashbox Designs With & Without Inlet Weirs
Notes:
1. The minimum width of the flashbox is twice the outside diameter of the pipe distributor or the pipe diameter plus 8 in. (200 mm), whichever is
greater. The net open area must be sized to avoid entrainment by designing for a capacity factor (C s) of 0.3 ft/s (0.1 m/s) or for 85% of
ultimate capacity, whichever is less. The open area at the flashbox top excludes the area occupied by the 2 in. (50 mm) lips on both sides of
the baffles. The lips help to prevent vapor from entraining liquid off the top of the baffle walls and also act as stiffeners to add rigidity to the
flashbox side baffles.
2. Center and off-center flashboxes can be designed with or without inlet weirs. Inlet weirs can improve liquid distribution for the tray below the
feed. Inlet weirs are also required to seal the flashbox. The maximum horizontal liquid velocity leaving the bottom of the flashbox is 1 ft/s
(0.3 m/s) for designs without inlet weirs and 1.5 ft/s (0.5 m/s) for designs with inlet weirs. A minimum clearance of 1 in. (25 mm) between the
tray deck to the bottom of the flashbox is required.
3. The flashbox bottom width for center and off-center flashbox arrangements (with inlet weirs) should be sized to limit the downward liquid
velocity to 0.6 ft/s (0.18 m/s) for non-foaming systems and 0.4 ft/s (0.12 m/s) for foaming systems. The flashbox bottom width for center and
off-center flashbox arrangements (without inlet weirs) should be sized to limit the downward liquid velocity based on the downcomer design
below the feed.
4. A FRACTIONATION SPECIALIST should be consulted when designing or rating a flashbox. Note that downpipes or troughs may be required
when there is a seal pan above the feed inlet or when there is a change in tray geometry in the feed zone.
5. Design Criteria from Reference 4. DP03Hf05d
INLETS (Cont)
FIGURE 6A
PERFORATED PIPE DISTRIBUTORS
Straight "T" Type "U" Type "H" Type
Preferred over "U"
(2) (2)
(2)
(1) (1)
(1) (1)
Notes:
(1) Do not perforate this section of the pipe. DP03Hf06a
(2) Capped end.
➧ FIGURE 6B
PIPE DISTRIBUTOR ARRANGEMENT FOR FOUR-PASS TRAYS
(2) (2)
(1) (1)
Notes:
(1) Do not perforate this section of
the pipe.
(2) Capped end.
(3) External piping to be symmetrical.
DP03Hf06b
INLETS (Cont)
➧ FIGURE 7
DISTRIBUTOR ARRANGEMENTS
C
A B Holes or slots at
"T" Distributor and Feed Nozzle Segmented Distributor For 45° Downward Angle
at Different Elevations Modified Arc Downcomers
Modified Arc Downcomer 1/4" (6 mm) Vent
Hole on End Cap
45°
Hole on Bottom of
Pipe at End of Lateral
α
FIGURE 8
INSULATING BAFFLES FOR DOWNCOMERS
Downcomer
(3) Notes:
Insulating
(1) To prevent vaporization in the downcomer of the tray above the feed, an
Baffle (1) insulating baffle should be provided when the feed temperature exceeds
the temperature of the downcomer liquid.
(2) The distance between the bottom of the insulating baffle and the tray
should be the greater of 4 in. (100 mm) or the downcomer clearance plus
2 in. (50 mm).
(3) The horizontal distance between the insulating baffle and the downcomer
(4) should be 1/2 to 1 in. (12 to 25 mm). The space between the baffle and
the downcomer should be open at both the bottom and top for drainage
and ventilation.
(2) (4) The top of the insulating baffle should be flush with the top of the
Tray distributor. DP03Hf08
➧ FIGURE 9
SURFACES AT FEED INLET LOCATIONS
Acceptable Acceptable Not Acceptable
Notes:
(1) Downcomer apron panels at feed inlet locations
should have jogged overlapping seams to
provide a smooth surface for vapor/liquid
impingement. Otherwise, a smooth, flat plate
must be installed to provide such a surface.
(2) When an insulating baffle is used, it must also
provide a smooth surface for vapor/liquid
impingement.
(3) Stepped downcomers should be avoided at
Jogged Smooth tower inlet locations. Sloped downcomers
Joint Plate Seam or
should be used instead.
Stiffening
DP3HF09
Element
VAPOR DRAWOFFS
Vapor drawoffs typically use nozzles that are line size.
Deentrainment. If entrained liquid can cause product contamination, a deentrainment device, such as a crinkled wire mesh
screen (CWMS) may be considered. For the design of deentrainment devices for vapor drawoffs using collector pipes consult
your FRACTIONATION SPECIALIST.
Side Drawoffs. If not properly designed, a side drawoff can cause premature flooding due to high localized vapor velocities.
The design of a side drawoff should reduce vapor maldistribution and make allowances for any maldistribution that is expected
to occur. See Figure 10.
FIGURE 10
VAPOR SIDE DRAWOFFS
8 in.
(200mm)
(3)
(2) (2)
(3)
(1) Capped (1) Capped
End End
Notes:
(1) The bottom of the collector pipe should be one normal tray spacing plus 12 in. (300 mm) above the tray.
(2) The end of the collector pipe should have two side-facing slots located above the center of the bubbling area. The
total slot area should be about 150% of the pipe cross-sectional area.
(3) Small diameter collector pipes (say under 12 in. (300 mm) diameter) may have to be supported; consult a
MECHANICAL SPECIALIST. For revamps with limited vertical height and for towers with diameters over 8 ft (2400
mm), a more complex collector may be required. For these cases and when there is a CWMS below the drawoff or
when there is weeping from the tray above, consult a FRACTIONATION SPECIALIST. DP3HF10
SPACING AND FREE AREA REQUIREMENTS FOR TRAYS WITH DRAWOFF BOXES
The concern with inadequate spacing is that the drawoff box may reduce the free area (Af) or it may obstruct liquid flow into the
downcomer of the tray below. Both effects may cause premature tray flooding. Figure 16 provides spacing recommendations
between the drawoff and the tray below.
➧ FIGURE 11
DRAWOFF NOZZLE LOCATION VS. DIAMETER
Dt / 2
➧ FIGURE 12
DRAWOFF WITH SEAL DAM – SIDE (OUTBOARD) DOWNCOMER, (1)
Overflow
Weir
Tray
Downcomer
hd1 (6)
Overflow
Weir (3) (6)
Feed (6) C
hd2
Dd (9) Distributor (9)
(if Required) hw (3)
(2)
C+1" (1)
C
Anti-Vortex
Baffle
Tray
(5) (4)
Seal Dam
(8)
Open Top DP3HF12
Dr (7)
➧ FIGURE 13
DRAWOFF WITH SEAL DAM – CENTER (INBOARD) DOWNCOMER, (1)
Seal Dam
Overflow Weir Tray
(6)
Feed hd1 (6)
Overflow
Distributor Weir (3)
(If Required) (6)
hd2
Top Open (2) (2)
C Seal
(4)
hw(3) Dam
C+1" (9) C
Anti-Vortex
Baffle Tray
Anti-Vortex
(9) Baffle (9)
(5)
(8)
(7)
Dr Dr
Dd
DP03Hf13
See Applicable Notes After Figure 15
➧ FIGURE 14
DRAWOFF WITHOUT SEAL DAM – SIDE (OUTBOARD) DOWNCOMER (1)
Downcomer
Tray
(6) (6)
Open
C hd1
Top
(6)
Feed hd2 hw(3)
Dd (9) Distributor
(If Required) (2)
(9) Overflow
C
Weir (3)
Anti-
Vortex (1) Tray
(5)
Baffle (8)
Overflow (4)
Weir
(7)
Dr
DP03Hf14
See Applicable Notes After Figure 15
➧ FIGURE 15
DRAWOFF WITHOUT SEAL DAM – CENTER (INBOARD) DOWNCOMER (1)
Overflow
Weir
Tray
(10) Overflow
hd1 (6) Weir (3)
(6) (1)
(2) hd2 (6)
≥ 3 Dd
hw(3)
C
C (9)
(10)
Tray (4)
Feed
Distributor
(5)
Dr (If Required)
Dr (7) (8)
Dd
hd
Minimum tray spacing is the greater of: 1 + h w and [H (1 - fd ) + hd1 + hw ]
fd
(b) For pressure > 100 psia (690 kPa) or for foaming systems
ρL
hd2 = (ht + 2hud ) + how + h w + 1 (or + 25 if Metric )
ρL − ρ V
H is the spacing of the tray above and fd is the allowable downcomer filling expressed as a fraction. Drawoff tray
and tray above should be designed so they do not limit tower capacity. Verify that final tray spacing is such that the
drawoff tray does not limit the tray section. Calculate how from FLUID FLOW EQUATIONS Eq. 3. Calculate how
even for total drawoff cases, since the tower must be able to work in the event that total drawoff operation ceases.
(7) Vertical distance between the bottom of box and the tray below should be per Figure 16.
(8) Drawoff piping must drop 10 ft (3000 mm) vertically before it can be swaged or contain a horizontal run.
(9) Provide one tier of anti-vortex baffle that is flush with the top of the entrance to the drawoff box. Baffle length should
be ≥ 3Dd. The baffle width should be the same as the drawoff box width.
(10) Optional nozzle location (Figure 15 only). Anti-vortex baffles of length 3Dd should be provided above the nozzles
and flush with the tray deck. Please consult with a FRACTIONATION SPECIALIST regarding this design. The
drawoff piping must not interfere with the downcomer entrance on the tray below. If interference does occur, the
nozzles may be placed in the side of the drawoff box with drawoff pipe elbows oriented horizontally. Box length is
the same as the tower diameter.
WHEN METRIC DIMENSIONS ARE NOT PROVIDED USE THE FOLLOWING METRIC EQUIVALENTS
1 25 3 75 5 125
2 50 4 100 6 150
➧ FIGURE 16
SPACING AND FREE AREA REQUIREMENTS FOR TRAYS WITH DRAWOFF BOXES
(4)
(3,4) (4) (3,4)
(3,4)
(7) (5)
(7)
Unacceptable Location (7)
of Support Beam (6) (5) Waste Area (2)
Aw /2 (1) Unacceptable Location
of Support Beam
Waste Area (2)
AW (1)
(3)
(3) (3)
CL
Notes:
(1) The minimum distance between the bottom of the drawoff box and the top of tray below should be equal to the normal tray spacing
of the tray below.
(2) Hydraulic calculations for the tray below the drawoff box should use a waste area (Aw) equal to the portion of the drawoff box area
that extends beyond the downcomer of the tray below.
(3) Hydraulic calculations should use as free area the marked area (by Arrow) minus the area of inlet distributors (if present) and any
other waste area (Aw see Note 2). If the Ab/As ratio of the trays is less than 0.40 try to increase Ab using sloped downcomers (see
Note 4) or consult your FRACTIONATION SPECIALIST.
(4) Because of its reduced free area, the tray at the drawoff box elevation may be the limiting tray of the section. To reduce the percent
flood of this tray, the tray spacing may be increased and the downcomers of the tray above may be sloped, even if straight
downcomers are used on higher trays. Downcomers can be sloped to less than 0.65 Dt chord length criterion provided the seal dam
or the overflow weir meet this criterion and the downcomer outlet velocity criteria is not exceeded. For partial drawoff services
where carryunder of some vapor is acceptable, the drawoff arrangements without a seal dam (Figures 14 and 15) may be chosen
as they will provide higher free area.
(5) The drawoff box should extend across the entire length of the overflow weir and should cover the entire chordal area (side) or tray
diameter (center).
(6) Drawing Note. The drawings provided to the tower internals vendor should include the following note: No support beams or other
construction elements should be placed under the drawoff box perpendicular to the liquid flow.
(7) Drawoff boxes may have sloped sides to minimize interference at downcomer inlets on the tray below. The minimum permissable
cross sectional area for liquid flow in the tapered section is the horizontal area at the entrance of the box.
DP3HF16
BOTTOM DRAWOFFS
Bottom drawoffs typically use nozzles that are line size. Anti-vortex baffles are required and should be designed according to
IP 5-2-1.
Coke Strainers. These are installed above the bottom nozzle inside towers where solid particles may accumulate, such as
vacuum pipestills and cracked/coker products fractionators, to keep large pieces of coke out of pump suction lines (see Figure
17A for design details). A newer design concept developed for delayed coker fractionators and other extremely fouling
services, is shown in Figure 17B. With this design, solids are not allowed to accumulate in the tower, and instead are removed
through a continuous recirculation loop that has coke crushing pump impellers and dual parallel external strainers. The return
of this recirculation system is via a ring sparger that is designed to keep the coke particles in suspension in the bottom of the
tower. The recirculation drawoff nozzle should have a cross-style vortex breaker, to avoid fouling. A standpipe strainer is
required to protect the bottoms product pumps against a massive coke drum foamover, which temporarily overwhelms the
recirculating system. Consult with a FRACTIONATION SPECIALIST and a RESID CONVERSION SPECIALIST regarding
whether this enhanced bottoms straining circuit is correct for the tower being designed and also regarding the specific internal
and external design details of this system.
FIGURE 17A
COKE STRAINER
(FOR VACUUM PIPESTILLS, CAT FRACTIONATORS AND OTHER FOULING SERVICES)
DS + 6 in.
(DS +150 mm)
DS (2) (5)
Square or round
baffle with a slope
(1) about 3 in./ft
HS (4) (0.25 mm/mm)
(3)
Notes:
(1) The strainer shall be removable to permit access to the tar pot or drawoff nozzle.
(2) The strainer diameter (Ds) should be twice the nozzle ID, however, if a tar pot is provided to minimize
bottoms holdup time, Ds should be made equal to the tar pot diameter.
(3) The entire strainer should be perforated with 3/8 in. (9 mm) holes on 1/2 in. (13 mm) square pitch. The hole
area should be at least 4 times the nozzle area (nozzle on vessel or tar pot).
(4) Strainer height as required for total hole area, but at least 12 in. (300 mm).
(5) Distance between outer edge of the baffle and strainer top should be the greater of Ds/3 or 2 in. (50 mm).
DP3HF17a
➧ FIGURE 17B
COKE STRAINER (1)
(FOR DELAYED COKING FRACTIONATORS AND OTHER VERY FOULING SERVICES)
HHLL
Standpipe strainer
HLL
(Note 2)
Cross-style Vortex
Ring Sparger:
Breaker
Use holes in the distributor ring (See Detail A) 4 to 7 ft (1.2 - 2.1 m)
pointing down and outward at LLL (Note 2)
a 45° angle toward vessel wall.
Number of holes and ring LLLL
diameter are a function of the
system hydraulics. (A half-ring
section of the sparger is shown
for clarity.)
45°
Alternate Recirculating
Detail A
Loop Return from Strainers
Cross-style Vortex
Breaker Detail
Dd
2 Dd
Dd Dd
2
Notes:
(1) Consult with a RESID CONVERSION SPECIALIST regarding details of this design.
(2) Liquid levels and dimensions to be confirmed during detailed process design engineering. DP03Hf17b
FIGURE 18
BOTTOM TRAY SEAL
Side (Outboard) Seal Pan Center (Inboard) Seal Pan Extended Downcomer
(2)
High
(2) (2)
Liquid Level
(1) Low
(1)
Liquid Level
2C 2C (3) 4 inches min.
C C
(100 mm) min.
Notes:
(1) The minimum is “c;” in most cases “2c” is preferred since wider clearances allow some solids settling without
blocking the downcomers.
(2) As required by the reboiler return arrangement (see REBOILER DRAWOFFS AND RETURNS and VAPOR INLETS
- Distributors Below the Bottom Tray) but no less than one normal tray spacing.
(3) See discussion in text on limitations of this design. DP3HF18
➧ REBOILER ARRANGEMENTS
Figures 21 and 22 illustrate various reboiler drawoff arrangements. Under each diagram is a list of the main advantages and
disadvantages to aid the designer in selecting the most desirable drawoff for a given situation. For more information on reboiler
types and hydraulic considerations, see Section IX. For kettle reboiler returns see VAPOR INLETS.
➧ FIGURE 19
DRAWOFF PAN AND REBOILER RETURN ARRANGEMENT (11)
(10) (10)
(4)
(4)
(8)
r (5) Dd Dd
ϕ ρL y
fVL = ϕ ln 1 + − 1 Eq. (A)
y ρ V ϕ
a3) Liquid Volume. Multiply these average liquid volume fractions by the total volumes of the reboiler and return
piping, respectively, to obtain the total liquid volumes. The drawoff piping to the reboiler is excluded from these
calculations since it is always assumed to be full of liquid.
b. Liquid Volume in the Reboiler and its Return Piping for Reduced Vaporization. Repeat the calculations in step
(3-a) using (0.73y) in place of y in Eq. (A) and Eq. (B). This gives the liquid volume in the reboiler and return piping
assuming a 20% reduction in vaporization rate and a simultaneous 10% increase in the total circulation rate.
c. Required Holdup. The required liquid holdup above the drawoff nozzle is the difference between the results of
steps (3-a3) and (3-b). This calculated holdup should be sufficient to supply liquid to the reboiler circuit during
changes in heat input to the reboiler. However, as mentioned under step (2-a), it may be necessary to reduce this
holdup in order to minimize residence time in certain fouling services.
d. Dimension A. Use Table 1, Section III-K and the holdup calculated in step (3-c) to calculate dimension A. Keep in
mind that the following volume of liquid is not to be included: 1) Liquid below the top of the drawoff nozzle, 2) Liquid in
the downcomer, 3) Liquid inside or upstream the seal pan. The minimum value of dimension A is 24 in. (600 mm).
4. Drawoff Nozzle Diameter (Dd). Calculate the drawoff nozzle diameter, Dd, from FLUID FLOW EQUATIONS, Eq. 9. If this
nozzle size exceeds the desired line size for piping to the reboiler, the line can be swaged down in the vertical run outside
the tower, at a point 10 ft (3000 mm) below the elevation of the drawoff nozzle.
➧ 5. Other Considerations.
a. Baffle Surface. The baffle should provide a smooth surface for vapor-liquid impingement. It must be fabricated and
installed so that the bolting web (if any) is on the back side of the baffle. See Figure 9. The downcomer apron should
not be used in place of a baffle.
b. Nozzles. To minimize piping lengths, the reboiler drawoff and return nozzles are normally located on the same side of
the tower. The reboiler return should be a perforated pipe distributor or flashbox.
c. Perforated Pipe Distributors. A perforated pipe distributor for reboiler return service should be designed per the
guidelines established for mixed feed inlets. All external piping arrangements feeding multipass tray geometries
should be symmetrical. The diameter of the distributor pipe must match the reboiler outlet nozzle and the pipe flow
regime and slot velocity should be checked. If necessary, the diameter of the distributor pipe should be changed to
avoid slug flow. The slot velocity should be minimized and the distributor slot pressure drop should not exceed 0.25
psi (1.7 kPa).
Due to the high momentum associated with mixed phase reboiler returns, most of the fluid will travel and impact at the
end of the nozzle. The distributor support must be rigid enough to withstand the impact force of the fluid and vibration
affects.
d. Flashbox. The flashbox design shown in Figure 5B, Figure 5C, and Figure 5D for mixed phase feed inlets may be
used for reboiler returns. A typical constant head arrangement using a flashbox for two-pass trays is shown in Figure
20B. A FRACTIONATION SPECIALIST and Reference 4 should be consulted for designing or rating a flashbox for a
reboiler return service.
FIGURE 20A
ALTERNATIVE SEAL PAN ELEVATION
Dd + 4" Dd + 4"
(Dd+100mm) (Dd+100mm)
Dd Dd
Note:
The elevation of the seal pan is the only design change offered by this alternative design. All other
design features illustrated in Figure 19 and described under Reboiler Drawoff Design Procedure apply.
DP03Hf20a
➧ FIGURE 20B
ALTERNATIVE REBOILER DRAWOFF AND RETURN CONFIGURATION WITH FLASHBOX RETURN (7)
lud
Flash Box
Width of
VIEW A Lips B additional design details.
(7) See Reference 4 for additional design criteria.
End Plate B
VIEW B-B
Dt
Bottom Tray
Dr+6"(150mm)
Side 3/4 TS or
Dr 18"(450 mm)
Downcomer
TS
(4) 1.5 Dr
Flashbox (1) or 24"
(600mm) min.
6"(150mm)
24" Overflow Weir (5)
(600mm) 9" (225mm)
min.
HLL
Reboiler Baffle (3)
CL
18" (450 mm) diameter
Baffle Hatchway (2)
LLL Optional
6" (150mm) Side Draw
LLLL
min.
T.L.
D
0.1 Dt + d
2
Dd
Vortex Breaker Outlet Nozzle
to Reboiler VIEW A
➧ FIGURE 21
REBOILER DRAWOFFS (1) (SINGLE-PASS TRAYS)
Recirculating Reboilers
A B C
(2) (2) (2)
(5) Baffle
(5)
24 in. min.
(600mm min.)
(6)
Not Acceptable
(3)
(8,9)
Optional
(7,8,9)
Extension
(8,9) (8,9)
(7) (6)
(8,9)
(8,9) Optional
Extension
(8,9) (8,9)
Product Reboiler
Product Reboiler
D. For thermosiphon reboilers. Head over E. For furnaces, thermosiphon or pump-through F. For Kettle reboilers only. Large
drawoff varies. Moderate holdup in reboilers. Large holdup. Provides holdup. Head over drawoff
pan. Reboiler start-up line required. downcomer seal if optional extension is used. varies. Simple construction.
Notes:
(1) Detailed sizing criteria, dimensions, design of perforated pipe distributor are in the text. See also Figure A1, Section IX-E.
(2) Perforated pipe distributor(s). When impinging shell, consider using wear plate if service is erosive or corrosive.
(3) Closed drawoff box may flood tray if reboiler pressure drop increases as a result of fouling.
(4) Flush nozzle if distribution not critical. Distance to tray above minimum but not less than 8 ins. (200 mm).
(5) Weir top to distributor bottom shall be the greater of 1 tray spacing or 18 in. (460 mm).
(6) See text, Bottom Tray Seal.
(7) Limit velocity to 0.2 ft/s (0.06 m/s).
(8) Provide anti-vortex baffles per IP 5-2-1.
DP03Hf21
(9) See Figure 16, Section XII-C for liquid holdup requirements.
➧ FIGURE 22
REBOILER DRAWOFFS (1) (TWO-PASS TRAYS)
Recirculating Reboilers
A B
Center Center
(2) (2) (2) (2) (2)
(2) Downcomer Downcomer
Baffles Side
Downcomers
Side
Downcomers (7)
(6)
(6)
Not Acceptable
(8,9) (8,9) (8,9) (3) (8,9)
Reboiler Reboiler
Product Product Product Product
A. For thermosiphon reboilers. Baffles insulate liquid in B. For furnaces, thermosiphon or pump-through reboilers.
downcomer(s). Head over drawoff constant. Moderate Provides the largest reboiler feed holdup. Head over drawoff
holdup in pan. Reboiler start-up line required. varies. Provides the poorest approach to a theoretical stage of
types shown. Simple construction.
Once-Through Reboilers
C D
Center
(2) (2) Downcomer (2) 2"
(50 mm) (4) (4) (4)
(5) (5)
Side
Downcomers (7) Center
Downcomer
(6)
Side (6)
Downcomers
Reboiler Reboiler
Product Product
C. For thermosiphon reboilers. Head over drawoff varies. D. For kettle reboilers only. Large holdup. Head
Moderate holdup in pan. Reboiler start-up line required. over drawoff varies. Simple construction.
Notes:
(1) Detailed sizing criteria, dimensions, design of perforated pipe distributor are in the text. See also Figure A1,
Section IX-E.
(2) Perforated pipe distributor(s). When impinging shell, consider using wear plate if service is erosive or
corrosive.
(3) Closed drawoff box may flood tray if reboiler pressure drop increases as a result of fouling.
(4) Flush nozzle if distribution not critical. Distance to tray above minimum but not less than 8 in. (200 mm).
(5) Weir top to distributor bottom shall be the greater of 1 tray spacing or 18 in. (450 mm) minimum.
(6) See text, BOTTOM TRAY SEAL.
(7) Balance lines between drawoff pans may be required. Chimney tray type arrangement also possible.
(8) Provide anti-vortex baffles per IP 5-2-1.
(9) See Figure 16, Section XII-C for liquid holdup requirements. DP03Hf22
FIGURE 23
MID-REBOILER DRAWOFF TRAY DETAILS (1), (2)
FIGURE 23 (Cont)
MID-REBOILER DRAWOFF TRAY DETAILS (1), (2)
Section A-A
Optional Second
(3) Nozzle Location (6)
Chimney (4)
Anti-Vortex
Baffles (7)
Overflow Weir
(7) (Notched) (13)
(7)
min.
(9) (12)
(9)
Dd
c
2c
Dr min. c
(9)
(3)
(4)
(10)
(5)
Overflow Weir
12" (Notched)
(300mm)
A (6) A
(11) (3)
(6)
(8)
c = Downcomer clearance, in. (mm). DP03Hf23
INTERCOOLER DRAWOFFS
➧ Intercooler drawoffs are provided on certain towers, such as absorbers, so that the heat of absorption can be removed from the
recirculating absorption oil. The heat transfer is done external to the tower by drawing off the absorption oil and passing it
through a heat exchanger. It is then returned to the chimney tray from which it was taken. To insure maximum heat transfer
efficiency, however, the cold liquid should not be mixed with the material being drawn off. Nevertheless, provision must be
made to recycle some of this cold oil in case the drawoff rate momentarily exceeds that available from the tray above. These
objectives are met (Figure 24) by directing the cold absorption oil against a vertical baffle that is elevated slightly above the
drawoff tray.
FIGURE 24
INTERCOOLER DRAWOFF TRAY DETAILS (1), (2)
FIGURE 24 (Cont)
INTERCOOLER DRAWOFF TRAY DETAILS (1), (2)
Section A-A
Dr
Impingement
Baffle
Anti-Vortex
Baffles Not
Shown
Dd
(6)
Dd
(11) 2c
(3)
(4) (4)
(5)
(8)
6"
(150mm) 2" (50mm)
(11)
A A Dr
(7)
(7)
(13) Impingement
Baffle
(6) (14)
(6)
(15) (12)
(3)
(9)
WATER DRAWOFFS
Water drawoffs remove insoluble water from a hydrocarbon tower. They are used in towers where water may create corrosion
problems or where it may “build up" and cause flooding, for example, when the tower top is too cold and the bottom too hot for
the water to escape. Since there is usually inadequate holdup time in the tower to achieve effective water settling, the entire
stream is withdrawn to an external drum. The hydrocarbon phase is then returned to the downcomer leaving the drawoff tray.
➧ The drawoff tray typically is a chimney tray (see Figure 25). While this figure shows a two pass side (outboard) configuration, it
can be readily modified for single pass or two pass center (inboard) downcomer designs. See your FRACTIONATION
SPECIALIST if help is needed. This tray is designed like any other chimney tray except:
• There must be sufficient liquid height on the tray between the high and low liquid level (HLL and LLL). A distance of at
least 14 in. (350 mm) should be provided, based on minimum level controller range requirements (pumped hydrocarbon
return). Review the final design with your INSTRUMENTATION SPECIALIST.
• The centerline of the hydrocarbon return nozzle(s) should be located at the elevation shown in Figure 25.
• If the hydrocarbon returns to the tray below by gravity, the height between the drawoff and return must provide the head
needed to overcome all frictional losses in the system.
In towers where water washing is necessary to remove soluble salts such as ammonium chloride, a chimney tray drawoff
following the guidelines in Figure 25 should be provided to remove the wash water. Since process conditions vary widely from
case to case, the specific application should be reviewed with a FRACTIONATION SPECIALIST before the design is initiated.
FIGURE 25
WATER DRAWOFF TRAY DETAILS (1), (2)
Section A-A
Optional Second
Nozzle Location
(3)
Dr
(7) Overflow
Chimney (4) Weir
(7)
Drawoff c
Box (6)
Dd
2c
c
(3)
(4)
(10) (5) (4) (8)
(12) HLL
(12) (11)
LLL
(12) (7)
A A
(6)
Dr
Dd
(6)
(9)
2c + 0.5 Dr DP3HF25
CHIMNEY TRAYS
Chimney trays are used to provide good vapor distribution to the internals above, liquid collection and mixing for drawoff or
internal reflux, and liquid holdup. In columns containing packing or grid, especially in vacuum towers where pressure drop is
critical, good chimney tray design is essential to provide uniform vapor distribution while minimizing pressure drop. (For packed
column designs, see Section III-G, VAPOR DISTRIBUTORS for additional guidelines.) If trays are used above the chimney
tray, vapor distribution is not critical since the pressure drop of the trays will normally “even out" the vapor flow.
DESIGN CONSIDERATIONS
1. Types of Liquid Drawoffs. Chimney trays can operate in the zero, partial or total drawoff mode. They can be used in
both trayed and packed columns and can have one or more passes. Figure 28 shows a chimney tray in a trayed column
that can operate in any one of these modes.
For zero or partial drawoff the reflux must overflow a weir and enter a downcomer to the tray or liquid distributor below.
Notches placed in the weir will help to even out the reflux flow rate. However, the rate may be small and will take the
swings of any process changes. If this condition is not acceptable and the reflux must be “pumped back" for control
reasons, the designer should consider changing to a total drawoff tray operating mode.
For total drawoff the liquid is typically removed from the tray by level control. Since all the liquid must be withdrawn from
the tray, every effort must be taken to provide an unobstructed path for liquid flow to the drawoff box(s). Therefore, if long
rectangular chimneys are used, their longer dimension MUST be parallel to the liquid flow to prevent gradient problems.
For design details for partial and total drawoff chimney trays, see Figures 26 and 28 and their respective notes.
For chimney trays with feed inlets, the chimney tray arrangements shown in Figures 26 and 28 have to be modified to
assure good vapor and liquid distribution and to prevent entrainment of liquid to the device above; contact your
FRACTIONATION SPECIALIST.
FIGURE 26
CHIMNEY TRAYS - LAYOUT (TOTAL DRAWOFF) (1)
Round Chimneys
Long Rectangular Chimneys (Preferred) (Acceptable But Usually More Expensive)
Dd Dd
Dd
rflow
Ove on
Opti )
(2
Notes:
(1) For chimney tray details, see Figures 29 A and B and the associated text.
(2) The drawoff sump of chimney trays in severely fouling services, such as vacuum pipestill overflash drawoffs,
should be able to overflow to the space below. This is necessary in case that total drawoff is not possible due
to plugging or loss of pumps.
DP3HF26
FIGURE 27
SPACING REQUIREMENTS OF CHIMNEY TRAYS
Gap Gap
Gap
Gap
Gap
Bubble Area
Gap
Gap Gap
DP3HF27
➧ 6. Chimney Hats (see Figure 29A and 29B). All chimneys, regardless of shape, should be covered with a baffle or “hat"
whose width (or diameter if circular) is at least that of the chimney. This will minimize liquid bypassing the chimney tray.
For packed or grid beds, the chimney hat liquid rate is prorated from the total liquid rate by the ratio of chimney hat area to
packed bed cross-sectional area. For trays, the total liquid of the tray above is prorated by the ratio of chimney hat area to
the bubble area of the tray above, (worst case; assumes all liquid dumps through the tray).
For rectangular or square chimneys the preferred hat design (for new chimney tray designs) is a V-hat as shown in
Figure 29B. The older style drip chute design is shown in Figure 29A. The V-hat should be designed with a turned up lip
on 2 or 3 of its 4 sides. These turned up lips should be at least 1.5 in. [38 mm] high to form a gutter for liquid flow. The
liquid depth in the gutter should be calculated from Eq. 1 and/or Eq. 2, FLUID FLOW EQUATIONS. Then, the lip height
should be set 1/2 in. (13 mm) higher than the gutter's liquid depth, but rounded up to the next 1/2 in. (13 mm) increment
[i.e., 1.33 liquid depth becomes 1.5 in. (38 mm), and the lip height becomes 2 in. (50 mm)]. The V-hat is more leak
resistant than the drip chute design since its hat is 15% wider than the vapor riser. It also has a lower pressure drop due to
the fact that the vapor doesn’t have to make a full 90 degree turn to exit the riser. Although most V-hat designs have two
open sides for vapor flow, the third side can also be open by installing a seal dam on the V-hat at that end.
For circular chimneys, the “notch" width for liquid flow, up to 3 in. (75 mm), and the number of notches needed (normally
3 max.) should be varied to limit the lip height to 2 in. (50 mm) maximum (see also the Table below). The lip height should
be calculated in the same way as for rectangular or square chimneys. To minimize costs, place the notch above one or
more of the hat's support legs. The purpose of the notch is to control where the liquid leaves the hat so that it is not re-
entrained by the ascending vapor. Each notch should have its own drip chute (see Figure 29A).
TABLE 2
SETTING NOTCH AND LIP DIMENSIONS FOR CIRCULAR CHIMNEYS
LIQUID RATE PER HAT NUMBER OF WIDTH OF EACH NOTCH LIP HEIGHT
NOTCHES
gpm dm3/s in. mm in. mm
1 0.063 1 1 25 1.5 38
2 0.126 1 1 25 1.5 38
5 0.315 1 2 50 1.5 38
10 0.632 2 2 50 1.5 38
20 1.264 3 3 75 1.5 38
30 1.896 3 3 75 2.0 50
50 3.15 3 3 75 2.0 50
The “notch and lip" design replaces the drip ring formerly used on the underside of the hats for many years. Therefore, if a
chimney tray requires other modifications, existing drip rings should be replaced with the “notch and lip" design during
revamps. Otherwise, the drip rings can be retained as originally designed.
➧ 7. Chimney Tray Drawoff Box Location. As mentioned earlier, if long, rectangular chimneys are used, the long dimension
should be parallel to the direction of liquid flow to the drawoff box (see Figure 26). This minimizes any gradients that could
develop on the tray and helps prevent liquid overflowing the chimneys farthest from the drawoff nozzle or overflowing any
downcomer weirs before external drawoff rates are satisfied.
The depth of the drawoff box should be 6 in. (150 mm) or 1.5 Dd, whichever is greater. The drawoff box is usually square
(plan view) and sized for a maximum downward velocity of 1 ft/s (0.3 m/s). In larger towers, however, the designer should
make the box at least 18 in. x 18 in. (450 x 450 mm) square to permit easy access. If two or more nozzles are used a
rectangular or chordal box may be required. If revamps require a different box layout, see your FRACTIONATION
SPECIALIST. The drawoff nozzle(s) must be flush with the bottom of the drawoff box to permit drainage during shutdown.
Size the drawoff nozzle diameter (Dd) using FLUID FLOW EQUATIONS, Eq. 9. Keep the line size downstream of the
drawoff nozzle equal to Dd until the line has dropped vertically 10 ft (3000 mm) or more. Then it can be swaged. Provide 2
tiers of anti-vortex baffles above the drawoff nozzle as shown on Figure 28.
When used in a trayed column, the vertical distance between the bottom of the drawoff box and the top of the weir on the
tray below should be obtained from Figure 16. For a packed column, the vertical distance will depend on the box size, the
internal below and the need for access.
8. Chimney Height
a. Determine high liquid level (HLL) needed for process and/or control purposes and provide at least 6 in. (150 mm)
between HLL and the top of the chimney.
b. If the level on the chimney tray is controlled provide a minimum of 6 in. (150 mm) between LLL and the tray deck.
c. The minimum chimney height is 8 in. (200 mm).
9. Partial Drawoff Under Packed Beds. Part of the liquid falling from a packed bed to a partial drawoff chimney tray, falls
directly into the downcomer(s). If the amount of the liquid falling directly into the downcomer(s) is 80% or higher than the
amount desired to move to the section below, a hood above the downcomer can be used to divert the falling liquid to the
tray. For the design of the hood contact your FRACTIONATION SPECIALIST.
In drawoffs below packed beds the liquid has to cross the tray to enter the drawoff box. To assure that the desirable
amount of liquid is removed from the drawoff box and that it does not overflow the chimney risers, the liquid height on the
tray must be calculated. Adjustment in the chimney riser and weir heights may have to be made. Checking the liquid
height is especially important when the chimney trays handle large liquid rates, e.g., below pumparounds, and when the
chimneys occupy a large portion of the liquid path. Use FLUID FLOW EQUATIONS, Eq. 1, Eq. 3, and Eq. 12, as
discussed in 2. above.
➧ FIGURE 28
DETAILS OF DRAWOFFS ON CHIMNEY TRAYS (8)
A B
Single-Pass Arrangement Two-Pass Arrangement
(10) (10)
c 2c 2"
(5) (5)
Anti-Vortex
Dd Dd Baffles
Vapor Downcomer
Drawoff Nozzle, D
d Risers (3) Seal Dam
(6)
Inlet
Downcomer (4) Outlet Weir
(4)
(1)
Notes:
(1) Provide rectangular notches 8 -10 in. (200 - 250 mm) deep if important to minimize changes in overflow rate with
changes in liquid level. For sizing, see Fluid Flow Equations, Eq. 1.
(2) For a discussion of holdup requirements, refer to Section XII.
(3) For chimney details, see text and either Figure 29 A or 29 B.
(4) Provide enough area so that the liquid velocity in the drawoff box ≤ 1 ft/s (0.3 m/s). Size anti-vortex baffles to cover
entire drawoff box (Figure A) or length and width equal to the box width (Figure B). Provide two tiers of baffles.
(5) 1.5 Dd or 6 in. (150 mm), whichever is greater. Also see Note 6.
(6) For large diameter towers (say > 12 ft; 3600 mm) and/or in cases where the drawoff box for a single nozzle is deep
and would interfere with the tray below, consider using two drawoff nozzles.
(7) The center row of chimneys is omitted in side view of Figure A for clarity.
(8) For chimney trays below three or more pass trays, consult your FRACTIONATION SPECIALIST for help.
(9) Tray spacing and downcomer filling above the top of the overflow weir: follow criteria outlined under Note 6 for
Figures 12 - 15. DP3HF28
(10) See text for spacing requirements above and below chimney tray.
➧ FIGURE 29A
CHIMNEY DETAILS
Hat
(6)
Isometric View
(2)
(1)
(10)
(1)
(8)
Hat (6)
(2)
(1) Hat Support
Legs
(7) (5) (3 Shown)
Di (9)
re
cti (4) (5) (9)
on (8)
of (3)
Liq Drip Chute
uid
Flo
w
(3)
Rectangular Chimney
Side View (Schematic)
Vapor
Isometric View
Liquid From
Hat
Hat (7)
Chimney Tray
Floor Liquid Level
on Chimney Tray
Notes:
(1) Vapor flows from three open sides.
(2) This dimension should be great enough so that the vapor flow area between the hat and the chimney equals the cross-
sectional area of the chimney.
(3) In most cases, rectangular chimney width should be 14 - 16 in. (350 - 400 mm) and circular chimney diameter should be
18 in. (450 mm). See discussion in text.
(4) Vary chimney length as needed to get the open area desired. Long side of chimney must be parallel to liquid flow on tray.
(5) This portion of chimney closed to vapor flow to prevent liquid re-entrainment. For circular chimneys, make leg width equal
to or wider than notch width. Provide a 1 in. (25 mm) drip chute angled downward at 45° to deflect falling liquid away from
the chimney. Also see Note 7.
(6) Set hat lip height at 1.5 in. (38 mm) or that determined from the procedure in the text, whichever is greater.
(7) For rectangular chimneys, leave one end of hat open. For circular chimneys, provide a notch.
(8) At least 8 in. (200 mm) or 6 in. (150 mm) above the high liquid level, whichever is greater. See text for details.
(9) Chimney horizontal stiffening members, if required, should be located at least 4 in. (100 mm) below the upper edge of the
chimney riser to prevent liquid splashing into the chimney.
(10) Chimney hat width/diameter must be at least equal to chimney width/diameter. DP03Hf29a
➧ FIGURE 29B
V-HAT RECTANGULAR CHIMNEY DETAILS
(2)
V-Depth
(7)
Vapor Slot
Chimney
Height (8)
(3)
(5)
(1)
(10)
(5)
Chimney
Length (4)
Notes:
(1) Vapor flows from two open sides.
(2) This dimension should be great enough so that the vapor flow area between the hat and the chimney equals the cross-
sectional area of the chimney.
(3) In most cases, rectangular chimney width should be 14-16 in. (350-400 mm). See discussion in text.
(4) Vary chimney length as needed to get the open area desired. Long side of chimney must be parallel to liquid flow on tray.
(5) This portion of chimney closed to vapor flow to prevent liquid re-entrainment.
(6) Set hat lip height at 1.5 in. (38 mm) or that determined from the procedure in text, whichever is greater.
(7) For most cases, leave both ends of hat open and have two side walls of riser open for vapor flow. If more open area is
required, three sides of the riser can be open for vapor flow by installing a hat dam at the end where the third side is open.
(8) At least 8 in. (200 mm) or 6 in. (150 mm) above the high liquid level, whichever is greater. See text for details.
(9) Chimney horizontal stiffening members, if required, should be located at least 4 in. (100 mm) below the top edge of the
chimney to prevent liquid splashing into the chimney.
(10) Chimney hat width must be at least 1.15 times the chimney width.
DP3Hf29b
FIGURE 30
TANGENTIAL VAPOR-LIQUID INLET (ANNULAR RING)
DN + 2 in.
(4)
2 in. (50mm)
(DN+ 50mm)
(7)
(300mm)
(4) Core Dia. DR (1)
12 in.
A Tangential Inlet A
is Inside Annular ring
(One Inlet Shown) (3)
DN
2.5 DN
Core
(7)
Annular Ring Plate
(5)
View A-A
Second Nozzle (2)
Location (if needed)
Notes:
(1) The capacity factor (Cs) for the “core" as defined by DR , should not exceed 0.5 (Customary) or 0.15 (Metric). Cs is defined as vapor
load, VL, divided by the “core" cross-sectional area. If Cs exceeds the recommended value, consider using two inlet nozzles to reduce
DN and thus increase DR. If the core velocity is still too high or the tower pressure exceeds 50 psia (345 kPa), consult your
FRACTIONATION SPECIALIST.
(2) When two nozzles are used, they should provide rotation in the same direction.
(3) No support members are permitted within the annular ring.
(4) The tangential feed nozzle(s) may be offset by up to 2 in. (50 mm) from the vessel wall. Their projection should not intersect the inner
annular ring wall, that is, an unobstructed path should be provided for the vapor entering the annular ring.
(5) Minimum distance is the greater of 0.25 DR or 24 in. (600 mm).
(6) For mechanical details see IP 5-2-1. For collector ring details see Figure 31.
(7) Annular ring plate and wear plate thickness 0.5 in. (12 mm) unless otherwise specified. DP03Hf30
➧ FIGURE 31
PIPESTILL COLLECTOR RING AND COLLECTOR PAN DETAILS
Pipestill Collector Ring Pipestill Collector Pan
(For Swaged Towers) (For Straight Side Towers)
D = Diameter of
Stripping Section Open Top
(7)
A A
(4)
False (5)
(2) Downcomer (1) (3) 18"
(450mm)
Section A-A
Open Top
False
Downcomers 18"
(1) (450mm) (6)
C
(2)
Diameter of
Stripping Section
Notes:
(1) For one-pass trays, the collector ring should have only one false downcomer.
(2) Outlet weirs and anti-jump baffles not shown for clarity.
(3) For one-pass trays, the collector pan would have an outboard downcomer.
(4) Anti-jump baffle not shown, outlet weirs not required.
(5) For chimney tray details see Chimney Trays, Design Considerations.
(6) Outer edge of chimneys should fall within circle with diameter equal to the tower internal diameter minus the width of the
annular ring above. This prevents feed liquid from impinging on the chimneys, thereby reducing entrainment and/or
foaming in the flash zone.
(7) Dimensions for tangential inlets nozzles are given in Figure 30. DP03Hf31
HINGED TRAYS
Background. In a number of services, tower internals are exposed to sudden, unexpected surges that can dislodge the
internals. If tray damage occurs frequently, hinged tray use may be justified. They are not normally installed in new designs
unless problems are expected. Surges can occur in two ways:
• Pressure Surges. They usually occur in the bottoms and sidestream strippers of atmospheric and vacuum pipestills when
stripping steam containing water (condensate) enters the tower and mixes with the hot oil. The water vaporizes almost
instantaneously, causing a sudden, but short lived pressure surge. These surges are strong enough to dislodge the
stripper trays (and usually some trays in the main column) and frequently require an emergency shutdown to correct.
• High liquid level excursions. The gas inlet (usually stripping steam) becomes submerged and one or more of the trays
flood. The turbulence created around the gas inlet and the resultant uneven gas flow up the column creates pressure
differences across the tray. This erratic “bumping" action can dislodge the trays.
To avoid these problems, the designer should ensure that only dry steam enters the stripper and that high level excursions are
minimized by proper instrumentation and a high liquid level steam cutout. Nevertheless, experience has shown that in spite of
these precautions, problems still arise. The best way to minimize the impact of these problems is to use hinged trays. These
are shown conceptually in Figure 32. The purpose of the hinged tray is to help relieve the pressure surges by designing
certain panels on the tray to open at a predetermined pressure drop. By providing a hinge, travel stop, and counter weight on
each hinged panel, the panel will return to its normal position after the surge has passed.
While experience has shown the hinged tray has worked successfully to minimize damage due to upsets, the forces generated
by condensate entering the tower have been large enough to even damage trays with hinged panels. Nevertheless, hinged
trays are still recommended for use in strippers, especially if damage has occurred in the past. The installation of hinged trays
does not eliminate the need for following good operating procedures, in particular, the proper draining of condensate in steam
lines prior to introduction of stripping steam into the tower and shutting off steam flow when the liquid level approaches the
steam inlet.
FIGURE 32
HINGED TRAY
Notes:
(1) The hinged tray design consists of
installing hinges on one or more tray
panels and removing the holddown
clips for those panels. The panels
are then able to lift if a sudden
increase in vapor load increases the
pressure drop across the tray
beyond the acceptable limit.
(2) The hinged tray section should be
App
14 i
Hinge
(4) The hinged design should include a
mm
Weight CL
“travel stop” which prevents the
)
Support
+ hinged panel from flipping
completely over.
+ Truss (5) No efficiency debit is expected
Support Channel during normal tower operation.
+
(6) They can be used on all types of
Strike Plate Gusset trays (sieve, valve, bubble cap,
DP3HF32
Side View and Travel Stop etc.).
(Hinged Panel In Open Position) (7) It is strongly recommended that
hinged tray designs are reviewed by
a FRACTIONATION SPECIALIST.
TRANSITIONS
➧ Figures 33, 34 and 35 show recommended transitions between single pass and double pass trays and their respective design
criteria. The configurations shown in Figures 34 and 35 are complex and therefore the use of a chimney tray should be
considered to simplify the transition design. There are many different embodiments of these designs. While not every case
has been shown, the details outlined should be adaptable to any other configuration. The designer should check the
downcomer hydraulics and jet flood requirements for both trays in a transition section, since these trays have different free
areas, downcomer clearances, etc.
Transitions for three and four pass trays are not shown because of their infrequent use. Should questions arise, contact your
FRACTIONATION SPECIALIST to optimize the final design.
➧ FIGURE 33
TRAY TRANSITIONS: ONE-PASS TO TWO-PASS WITH LIQUID OR VAPOR-LIQUID FEED (1)
(2) (2)
Inlet Weir
Inlet Weir
3 in. (75 mm)
3 in. (75 mm)
High
High
(3) (3)
Notes:
(1) Use one inlet distributor if external liquid ≤ 60 Vol. % of total liquid to the tray; otherwise use two inlet
distributors.
(2) The distance between the distributor and the tray above should be minimum but not less than 8 in. (200 mm)
for either liquid or vapor-liquid feeds. Use an inlet weir as shown. For all other design features see INLETS
and DESIGN OF PERFORATED PIPE DISTRIBUTORS.
(3) The width between the inlet weir and the tower shell should be the same as the side downcomer outlet width
for the tray below.
DP3HF33
TRANSITIONS (Cont)
FIGURE 34
TRAY TRANSITIONS: TWO-PASS TO ONE-PASS (CENTER DOWNCOMER)
A
Liq C
Two-Pass Tray Flo uid
w (5)
B False
B Downcomer B
(1)
(2)
A Drawoff Box
Section A-A
B
C Liquid Flow
C Seal Plate
(3) False
One-Pass Tray
Downcomer
Not Shown for Clarity: Drawoff Box Deflector Plate, Left Side
of False Downcomer, and Outlet Weirs.
False Downcomer Bubble
(5) Area
One-Pass
6" (150mm) Tray
Inboard
(4) Downcomer Apron
(6) (3)
(7)
Notes:
(1) Clearance under false downcomer should be 1 in. (25 mm) or based on head loss of 2 in. (50 mm) of hot liquid,
whichever is greater.
(2) Liquid drawoff box (if required) area should be based on liquid velocity of 0.6 ft/s (0.18 m/s) of drawn-off material.
Depth of liquid drawoff box is 6 in. (150 mm) or 1-1/2 times nozzle diameter, whichever is greater. Provide anti-
vortex baffles.
(3) Specify welded plate to seal bottom of downcomer from tray above.
(4) Because the one-pass transition tray has less than the normal free area, additional tray spacing is required to
avoid entrainment and premature flooding. If additional spacing is not sufficient, consider using a chimney tray at
the transition.
(5) Provide 2 in. (50 mm) clearance between top of false downcomer and tray above, to prevent gas from being
trapped.
(6) Deflector plate directs liquid toward center of inboard downcomer, so that it does not impinge on liquid entering
drawoff nozzle, D d. Angle of the deflector plate is approximately 30° from horizontal.
(7) Clearance under the section of the inboard downcomer that extends into the chordal area defined by the false
downcomer: The clearance height should be set to yield a pressure drop that is about 1/2 of the pressure drop
through clearance under the false downcomer.
DP03Hf34
TRANSITIONS (Cont)
FIGURE 35
TRAY TRANSITIONS: TWO-PASS TO ONE-PASS (SIDE DOWNCOMER)
Two-Pass Tray
(4) C
A
False
B B
Downcomer B
Flo
w
"Wing" Section of
(1)
False Downcomer
One-Pass Tray Flo
Section A-A w A
Liquid B
Flow
"Wing" Section of
False Downcomer C
Bubble Area
One-Pass
Tray
Section B-B
w
Flo
C
False Downcomer Outboard
Two-Pass Tray Chordal & "Wing" Sections Downcomer
Apron w
Flo
Outboard
Downcomer (3)
Apron (5)
DP3HF35
DEENTRAINMENT DEVICES
hCWMS (in. hot liq.) = 62.4 (hds + hsl ) ρL hCWMS (mm hot liq.) = 1000 (hds + hsl )/ρL
where:
hds, Pressure drop through dry screen inches water mm water
hsl, Pressure drop due to liquid holdup inches water (from Figure 38) mm water (from Figure 38)
hCWMS, Total pressure drop through inches of H2O or hot liquid mm of H2O or hot liquid
screen
f, Friction factor dimensionless (from Figure 37) dimensionless (from Figure 37)
t, Thickness of screen inches (normally 6 in.) mm (normally 150 mm)
VCWMS, Vapor velocity through screen ft/s (based on screen, not vessel cross- m/s (based on screen, not vessel cross-
sectional area) sectional area)
FIGURE 36
VANE-TYPE MIST ELIMINATOR
VANE-TYPE MIST ELIMINATOR (CHEVRONS)
De-entrained Gases
Vane-type mist eliminators are zig-zag baffles which are used for
removing entrained liquid drops from a vapor stream. Spacing between
the baffles, turning angles and number of passes are designed to satisfy
specific removal requirements (see Figure 36). When the vapor and
the entrained liquid drops pass through a vane-type mist eliminator, the
vapor moves freely through the baffles, but the drops, because of their
greater inertia, impinge upon the walls of the baffles, The liquid
collected on the baffles runs down to the bottom surface and drops off
the mist eliminator. Compared to CWMS, vane-type mist eliminators
generally are more resistant to fouling due to their larger physical
openings, but they are more costly and less efficient in removing
entrainment. Design and sizing of vane-type mist eliminators are
carried out by the vendor. Vendors include Koch-Glitsch Otto-York,
ACS Industires, Inc. and Peerless Manufacturing Co. Consult your
FRACTIONATION SPECIALIST before specifying these devices.
Mist Laden Gases
(Vertical Flow)
DP3HF36
FIGURE 37
CWMS PRESSURE DROP - FRICTION FACTOR
Customary Units
1
0.8 a
V ρ
f = 0.86 CWMS v
µ v
0.6
V ρ
where : a = − 0.5066 + 0.03358 ln CWMS v
0.5 µ
v
0.4
f
0.3
0.2
0.1
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 80 100
V CWMS ρ v
µv
Metric Units
1
a
0.8 V ρ
f = 0.86 CWMS v
µv
0.6 V ρ
where : a = − 0.5598 + 0.03358 ln CWMS v
0.5 µv
0.4
f
0.3
0.1
5 6 8 10 20 30 40 50 60 80 100 200 300 400 500
VCWMS ρ v
DP3HF37 µv
FIGURE 38
CWMS PRESSURE DROP - LIQUID HOLDUP
Customary Units
0.7
0.6
0.5
0.4
0.3
0.2
hsl
0.1
h sl = 0.01413 e a
0.08
where : a = 8.505 VCWMS [ρ v / (ρL − ρ v )] 0.5
0.06
Metric Units
20
10
6
hsl
h sl = 0.36 e a
3
where : a = 27.9 VCWMS [ ρ v / (ρL − ρ v )] 0.5
2
0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14
hn
DP3Heq01
b
hn
DP3Heq02
[ho w or ]
hsd = 0.5 (QL / lo ) 2 / 3 [ho w or ]
hsd = 692 (QL / lo ) 2 / 3
how or hsd
DP03Heq03
DP3Heq05
(
ho (in. hot liq.) = 0.925 x 10 −6 QL 2 / Co2 A o 2 ) (
ho (mm hot liq.) = 51x10 −6 QL 2 / Co 2 A o2 )
For flow into submerged tubes consult a For flow into submerged tubes consult a
FRACTIONATION SPECIALIST FRACTIONATION SPECIALIST
(
ho (in. hot liq.) = 0.031 QL 2 / Co 2do 4 ) (
ho (mm hot liq.) = 83 x 106 QL 2 / Co2do 4 )
ORIFICE: VAPOR FLOW Eq. 7
Vo2 ρv Vo 2 ρv
ho (in. hot liq.) = 0.186 2
ho (mm hot liq.) = 50.9
Co ρL Co 2 ρL
Eq. 9 sizes the nozzle diameter for a Eq. 9 sizes the nozzle diameter for a
liquid velocity of 3 ft/s. liquid velocity of 0.9 m/s.
Dd
DP3Heq09
1.3
Partially Submerged
1.2 Horizontal Nozzle
1.1
Dd
1.0 h
For Higher Values:
0.9 h C2vn 2
vn = 0.5 +
0.8 Dd Dd0.5
C2 = 0.7194 Customary
0.7 = 11.90 Metric
Dd0.5
C2vn
Fully Submerged
0.6 Horizontal Nozzle
0.5
h Dd
0.4
0.3 vn
0.2
0.1
0.0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
h / Dd
Notes:
vn is calculated using the total nozzle cross sectional area, even when the nozzle is partially submerged. Eq. 10 provides the
static head required to overcome nozzle entrance head-losses (uses a flow coefficient of 0.6). It does not take into account
any friction or other head requirements downstream the nozzle, that is, it assumes that the liquid flows into an infinite
chamber without resistance. Calculation of h > Dd does not ensure that the nozzle will be fully submerged (e.g., the
downstream pipe may have a vertical pipe drop to another vessel and no flow control device). Similarly, calculation of h < Dd
does not ensure that the nozzle will be partially submerged (e.g., the downstream pipe may have a flow control device). Eq.
10 predicts static head requirements that are somewhat conservative to provide sufficient design contingency.
For revamps, if existing height cannot satisfy the head required by Eq. 10, contact a FRACTIONATION SPECIALIST.
DP3Heq10
Horizontal } (
hgr = lt C3 v t / R2 / 3 ) 2
(
hgr = lt C3 v t / R2 / 3 ) 2
Plane
R = bh / (b + 2h) R = bh / (b + 2h)
lt
C4 QL C4 QL
vt = vt =
h hgr hgr
b h +
b h +
2 2
b DP3Heq12
UNITS, CONSTANTS
Trough Width b inches mm
Constant C3 0.0459 1.3
Constant C4 0.321 1000
Liquid Height in Trough h inches mm
Liquid Gradient at Upstream End hgr inches mm
Trough Length lt inches mm
Hydraulic Radius R inches mm
Liquid Flow Rate QL gpm dm3/s
Liquid Velocity in Trough vt ft/s m/s
There are essentially three flow regimes that can exist in a free hydraulic downward flow condition.
1. Self-Venting Flow
2. Transition
3. Liquid Filled
DP03Heq13
The initial regime, self-venting flow, is essentially a weir flow in which the liquid flows over the perimeter of the nozzle as a liquid
film. Any entrapped vapor is able to escape through the core of the nozzle and the vapor will not be sucked down. This flow
regime has been shown experimentally to occur at low liquid superficial velocities. It is important to design gravity lines and
gravity flow liquid distributors for self-venting flow.
Pipes smaller than the self-venting diameter can experience flow disturbances or surges when vapor is sucked down. Surging
flow can be avoided by designing the piping and outlet nozzles for self-venting flow.
Experimental data used to develop the equation below were based on small pipes less than 10 in. (250 mm). Experience with
larger pipes, larger than 24 in. (600 mm) suggest this correlation is somewhat conservative when extrapolating from its original
database.
The pipe diameter should be increased in proportion to the foam factor for foaming services. Also for flashing services, the
criteria should be used with caution especially when the liquid contains a significant amount of highly volatile components. (The
foam factor is defined as 90% / [recommended % jet flood]). The recommended % jet flood should be obtained from Section
III-B, Table 2, Design Criteria for Specific Towers. Minimum foam factor is 1.
NOMENCLATURE
Ab = Tray bubble area, ft2 (m2).
Ac = Chimney cross-sectional area, ft2 (m2).
As = Tower cross-sectional area, ft2 (m2).
Aw = Tray waste area, ft2 (m2).
b = Width of rectangular notch or trough, in. (mm). See FLUID FLOW EQUATIONS, Eq. 1, Eq. 12.
c = Downcomer clearance, in. (mm).
Co = Orifice coefficient, dimensionless. See FLUID FLOW EQUATIONS, Eq. 5, Eq. 6, Eq. 7.
C2 = Constant used in horizontal drawoff nozzle calculations. See FLUID FLOW EQUATIONS, Eq. 10.
C3 = Constant used in FLUID FLOW EQUATIONS, Eq. 12.
C4 = Constant used in FLUID FLOW EQUATIONS, Eq. 12.
Cs = Capacity factor, defined as vapor load (VL) divided by the appropriate cross-sectional area depending on use,
ft/s (m/s).
do = Hole or orifice diameter, in. (mm). See FLUID FLOW EQUATIONS, Eq. 5, Eq. 6.
Dd = Inside diameter of nozzle, in. (mm).
Dr = Outside diameter of inlet or return nozzle or return piping, in. (mm).
DR = Annular ring inside diameter, ft (mm). See Figure 30.
DN = Inside diameter of tangential inlet nozzle, in. (mm). See Figure 30.
Ds = Strainer diameter, in. (mm). See Figure 17A.
Dt = Tower inside diameter, ft (mm).
f = Friction factor for CWMS.
fd = Allowable downcomer filling, expressed as a fraction.
fVL = Liquid volume fraction. See REBOILER DRAWOFF DESIGN PROCEDURE, Eq. (A).
g = Gravitational constant, 32.2 ft/s2 (9.8 m/s2).
H = Tray spacing, in. (mm).
h = Liquid head above bottom of horizontal drawoff nozzle. See FLUID FLOW EQUATIONS.
hCWMS = Total vapor pressure drop through the CWMS, in. (mm) of hot liquid, unless otherwise indicated.
hd = Downcomer filling, in. (mm) of hot liquid. Calculate per procedure given in the pertinent device's
subsection.
hd1 = Liquid height in the downcomer above the top of the overflow weir or seal dam, in. (mm) of hot liquid.
See Figures 16 - 19.
hd 2 = Liquid height in the downcomer upstream of an overflow weir or seal dam, in. (mm) of hot liquid. See Figures
16 - 19. Reduces to hd if no overflow weir or seal dam is present.
hds = Vapor pressure drop through the dry CWMS, in. (mm) of water.
hed = Effective dry tray pressure drop, in. (mm) of hot liquid.
hgr = Liquid gradient at upstream end of trough, in. (mm) of hot liquid. See FLUID FLOW EQUATIONS, Eq. 12.
hn = Liquid height in notch, in. (mm) of hot liquid. See FLUID FLOW EQUATIONS, Eq. 1, Eq. 2.
ho = Head loss across an orifice, in. (mm). See FLUID FLOW EQUATIONS, Eq. 5 - Eq. 8.
how = Liquid head over a weir, in. (mm) of hot liquid. See FLUID FLOW EQUATIONS, Eq. 3.
hα = Impact height above the distributor centerline, in. (mm). See Figure 5D.
hβ = Impact height below the distributor centerlline, in. (mm). See Figure 5D.
Hs = Strainer height, in. (mm). See Figure 17A.
hsd = Head over seal dam, in. (mm) of hot liquid. See Figure 16 - 19, Note 4. Calculate from FLUID FLOW
EQUATIONS, Eq. 3.
NOMENCLATURE (Cont)
hsl = Pressure drop due to liquid holdup within the CWMS, in. (mm) of water.
ht = Total tray pressure drop, in. (mm) to hot liquid. See notes for Figures 16 - 19.
hud = Head loss under downcomer, in. (mm) of hot liquid. See FLUID FLOW EQUATIONS, Eq. 4.
hw = Height of overflow weir, in. (mm). See Figures 16 - 19, Notes 3 and 6.
lo = Seal dam or overflow weir length, in. (mm). See FLUID FLOW EQUATIONS, Eq. 3.
lt = Trough length, in. (mm). See FLUID FLOW EQUATIONS, Eq. 12.
lud = Downcomer length, in. (mm). See FLUID FLOW EQUATIONS, Eq. 4.
L = Baffle height in Figure 4B, in. (mm).
QL = Liquid volumetric flow rate, gpm (dm3/s) at conditions. Used in various FLUID FLOW EQUATIONS.
qv = Volumetric vapor rate at conditions, ft3/s (m3/s).
R = Hydraulic radius, in. (mm). See FLUID FLOW EQUATIONS, Eq. 12.
t = Thickness of CWMS, in. (mm).
TS = Tray Spacing, in. (mm)
VCWMS = Vapor velocity through the CWMS, ft/s (m/s).
[ ]
0.5
VL = Design vapor load = qv (ρV / (ρL - ρV )
vn = Drawoff or inlet nozzle velocity, ft/s (m/s). See FLUID FLOW EQUATIONS, Eq. 10.
Vo = Hole, chimney, or orifice velocity, ft/s (m/s). See FLUID FLOW EQUATIONS, Eq. 7, Eq. 11.
vt = Liquid velocity, ft/s (m/s). See FLUID FLOW EQUATIONS, Eq. 12.
y = Weight fraction vaporized. See Eq. (A) and (B) in the text under REBOILER DRAWOFF DESIGN
PROCEDURE and FLUID FLOW EQUATIONS, Eq. 8.
∆P = Pressure drop, psi (kPa) or in. (mm) of hot liquid, according to context.
α = Slot angle above distributor centerline, degrees.
β = Slot angle below distributor centerline, degrees.
ϕ = ρV/(ρL - ρV). See REBOILER DRAWOFF DESIGN PROCEDURE in text and FLUID FLOW EQUATIONS, Eq. 8.
ψ = Angle specified for use in FLUID FLOW EQUATIONS, Eq. 2.
µv = Vapor viscosity at conditions, cP (mPas). See CWMS.
ρL = Liquid density at conditions, lb/ft3 (kg/m3).
ρV = Vapor density at conditions, lb/ft3(kg/m3).
ρw = Density of water, 62.4 lb/ft3 (1000 kg/m3).