Professional Documents
Culture Documents
the proper side of the transformer) and basing the derivation on Eq. 2.33. However,
such additional effort is rarely necessary for the purposes of e n g i n e e r i n g accuracy.
EXAMPLE 2.6
With the instruments located on the high-voltage side and the low-voltage side short-circuited,
the short-circuit test readings for the 50-kVA 2400:240-V transformer of Example 2.3 are 48 V,
20.8 A, and 617 W. An open-circuit test with the low-voltage side energized gives instrument
readings on that side of 240 V, 5.41 A, and 186 W. Determine the efficiency and the voltage
regulation at full load, 0.80 power factor lagging.
II S o l u t i o n
From the short-circuit test, the magnitude of the equivalent impedance, the equivalent resistance,
and the equivalent reactance of the transformer (referred to the high-voltage side as denoted
by the subscript H) are
48 617
IZeq'HI = 20.8 = 2.31 f2 Req,H= 20.82 -- 1.42 ~2
Pcore = 186 W
Thus
'H=(50×103)
A 2 e-j436"9°--20"a(O'
0 0 a-jO'6)
The required value of the primary voltage V1H can be calculated as
- 2446 + j13
The magnitude of f'lH is 2446 V. If this voltage were held constant and the load removed,
the secondary voltage on open circuit would rise to 2446 V referred to the high-voltage side.
Then
2 4 4 6 - 2400
Regulation = (100%) = 1.92%
2400
) r a c t i c e P r o b l e m 2.,
Repeat the voltage-regulation calculation of Example 2.6 for a load of 50 kW (rated load, unity
power factor).
Solution
Regulation = 1.24%