3. The equivalent low-side parameters of a 250-kVA, 4160--480-V, 60-
Hz transformer are ReqLS = 0.00920 Ω, and XeqLS = 0.0433 Ω. The
transformer is operating in the step-down mode. Determine the
voltage regulation, in percent, if the transformer is delivering rated
current at rated voltage to a unity power factor load.
Solutions:
Solutions:
5. The percent resistance and percent reactance of a 75-kVA, 2400--
240-V, 60-Hz transformer are 0.90 and 1.30, respectively. Determine
the equivalent reactance referred to the high side.
Solutions:
Solutions:
7. A 25-kVA, 7620--480-V distribution transformer is supplying a 10-kVA
load at 0.65 power-factor lagging. The percent resistance and the
percent reactance are 1.2 and, 1.4, respectively. Determine the
transformer regulation, in percent, for the specific load. Give your
answer to 3 decimal places.
Solutions:
Solutions:
9. Data obtained from short-circuit and open-circuit tests of a 75-kVA,
4600--230-V, 60-Hz transformer are:
Solutions:
Solutions:
11. Data obtained from short-circuit and open-circuit tests of a 75-kVA,
4600--230-V, 60-Hz transformer are: