Professional Documents
Culture Documents
Stability Evaluation of AC/DC Hybrid Microgrids Considering Bidirectional Power Flow Through The Interlinking Converters
Stability Evaluation of AC/DC Hybrid Microgrids Considering Bidirectional Power Flow Through The Interlinking Converters
ABSTRACT The bidirectional power flow through the interlinking converter (IC), in ac/dc hybrid microgrids
(HMGs) consisting of distributed generators (DGs) with droop controllers, plays an important role on the
stability of such systems during islanding. This paper investigates the impact of the power flow direction on
the small-signal stability of islanded droop-based HMGs. Firstly, a linearized state-space model of an HMG
is developed. Secondly, eigenvalue analysis is carried out to realize the dominant modes, which are the
rightmost eigenvalues. Thirdly, participation factor analysis is performed to identify the system and control
parameters that effect stability the most. Lastly, sensitivity analysis is conducted to determine the critical
droop gains and stability margin. It is observed from the eigenvalue and sensitivity analysis that the dominant
modes of HMGs become more stable as more power flows from dc to ac subgrid. On the contrary, an increase
in the power flow from ac to dc subgrid degrades the HMG stability. Additionally, the sensitivity of the
dominant modes to changes in ac and dc droop gains is studied under bidirectional power flow through the IC
to ascertain their impact on the stability margins. Finally, time-domain simulations, in MATLAB/Simulink,
suggest that more generation on the dc subgrid would enhance the overall HMG stability margin during
islanding.
INDEX TERMS Bidirectional power flow, distributed generator, droop controller, ac/dc hybrid microgrid.
I. INTRODUCTION without the need for communication, the HMG stability has
Hybrid microgrids (HMGs) are evolving with the ability been identified as a fundamental requirement for the reliable
to exchange power between ac and dc subgrids. A bidi- operation.
rectional power flow operation of the interlinking converter Previous research has focused on the stability issues of
(IC) is employed to exchange power between ac and dc the decentralized control methods for islanded dc [1], and ac
subgrids in the HMG. The HMG can operate in either grid- microgrids [2]. A method of constructing the characteristic
connected or islanded mode, and can be controlled in a cen- matrix to study the small-signal stability of ac and dc micro-
tralized or decentralized manner. The decentralized control grids is employed in [3] and [4]. In [5], an ac power derivative-
methods, which employ droop characteristics, are widely based decentralized control scheme is proposed to improve
utilized for power sharing [1]. Although decentralized control the stability of the ac microgrid. The impact of ac microgrid
methods achieve power sharing between ac and dc subgrids loads on the stability of droop-controlled dc/ac voltage source
inverters (VSIs) is presented in [6]. In [7], a decentralized
The associate editor coordinating the review of this manuscript and control strategy with an additional droop gain is proposed to
approving it for publication was Salvatore Favuzza . preserve the ac microgrid stability.
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/
43876 VOLUME 9, 2021
A. A. Eajal et al.: Stability Evaluation of AC/DC HMGs Considering Bidirectional Power Flow Through Interlinking Converters
cycle of the dc/dc converter [8]. From Fig. 2b, the duty cycle where Kpp and Kip are the PI gains of the PLL. Furthermore,
can be obtained by the ac frequency (ω0 ) and dc voltage (v0dc ) are brought to a
per-unit range of [−1, 1], through a normalization process
d = kpc kpv v∗O − mdc iO − vO + kiv φv − iL + kic φc
adopted from [13]. Based on the difference between the
(14) normalized frequency (ωpu 0 ) and the normalized dc voltage
0
(vdc,pu ) and the setting of the IC active power droop gain
where kpc and kic are the PI gains of the dc current controller, (mIC ), the reference power (P∗IC ) of the IC is calculated
respectively; kpv and kiv are the respective PI gains of the dc by (20a). The IC droop gain default setting with respect to
voltage controller; φv and φc are the integral term outputs a maximum normalized error (1eωV ,max ) between the dc
of the dc voltage and current controllers, respectively; and voltage and frequency is obtained by (20b).
iO is the output current of the dc/dc converter. The dynamic
equations of the dc voltage and current controllers can be P∗IC = (v0 dc,pu − ω0 pu ) /mIC (20a)
| {z }
derived as 1eωV
φ̇v = v∗O
− mdc iO − vO (15) mIC = 1eωV ,max /SIC
rated
(20b)
φ̇c = kpv v∗O − mdc iO − vO + kiv φv − iL rated
(16) where SIC is the IC rated apparent power. It should be
mentioned that the IC droop controller is only needed for
The dynamic equation of the dc coupling line can be power sharing among multiple ICs [13]. In case of a single
described as IC, a simple PI controller can be used instead. Further, the IC
diO ro 1 is primarily concerned with the active power transfer. Thus,
= − iO + (vO − vdc ) (17) the IC reference reactive power (Q∗IC ) can be set to zero when
dt lo lo
the power flows from the dc to ac subgrid, as illustrated
where ro and lo are the resistance and inductance of the dc
in Fig. 3 and (21) [13], [23]. Nevertheless, according to its
coupling line; and vdc is the dc subgrid bus voltage.
(QIC − V ) droop characteristics defined by (21), the IC can
contribute to the reactive power sharing when supporting an
C. MODELING OF IC IN THE HMG
ac subgrid with limited reactive power resources.
The overall structure of the IC is depicted in Fig. 3. This
control scheme implements a bidirectional power controller 1 (V ∗ − v0 ) P∗ > 0
od IC
followed by a current controller [13]. The state equations of Q∗IC = nIC (21)
0 P∗IC ≤ 0
the IC current controller and the output filter are the same
as (7)-(11). Hence, these equations are not repeated here. where nIC denotes the IC reactive power droop gain. The dc
As shown in Fig. 3, the IC employs a phase-locked loop subgrid is irrelevant to the reactive power support capability
(PLL) to determine the output ac voltage frequency (ω0 ) and of the IC. Furthermore, the dominant eigenvalues are found
angle (θ 0 ) at its ac terminal. The state equation of the PLL is to be less sensitive to the reactive power droop gains [23].
describe by Accordingly, the stability analysis is mainly directed towards
0 the bidirectional active power flow through the IC.
φ̇p = v0oq − voq
∗
(18)
III. SMALL-SIGNAL MODELING AND ANALYSIS
where φp is the integral term output of the PLL. The corre-
A. SMALL-SIGNAL MODEL OF THE HMG
sponding dynamic equation can be written as
Based on the dynamic modeling presented in section II,
ω0 = Kpp φ̇p + Kip φp + ω∗ (19) the state equations of the HMG can be derived.
The small-signal model of the entire HMG is constructed TABLE 1. Dominant eigenvalues for zero power flow condition.
using the module-based approach offered in [11]. Fig. 4
demonstrates how the individual state-space models are
combined. As depicted in Fig. 4, the outputs of the ac and
dc subnetwork state-space models are the inputs to the IC
state-space model, whereas; the outputs of the IC state-space
model are the inputs to the ac and dc subnetwork state-space
models. Using small-signal approximation [3], the afore-
mentioned equations in section II can be linearized near an
equilibrium point and the small-signal model of the HMG
can be realized as
1xHMG
˙ (t) = AHMG 1xHMG (t) (22)
where AHMG is the system state matrix of the entire HMG; and
1xHMG denotes the vector of the state variables. The derived
eigenvalues of the characteristic matrix, AHMG , are used as
the basis for the subsequent stability analysis.
FIGURE 6. Participation factors (a) Modes 1 and 4 (b) Modes 2 and 3.
C. PARTICIPATION ANALYSIS
Participation factor analysis for conventional power systems
FIGURE 5. Dominant eigenvalues of the HMG at zero power flow discussed in [24] is extended to HMGs. The participation of a
conditions. certain state variable in an oscillatory behavior can be quan-
tified by its participation factor [24], which is calculated by
B. EIGENVALUE ANALYSIS pki = φki 9ik (23)
The active power droop gains of all DGs in Fig. 1 are
where pki measures the participation of the kth state variable
set according to their ratings and frequency/voltage operat-
xk in the ith mode; φki is the kth entry of the right eigenvector
ing range to 0.02 p.u. By considering the maximum power
φi ; and 9ik is the kth entry of the left eigenvector 9i .
exchange capacity of the IC being equal to its rating (1 p.u),
The participation factor pki also defines the sensitivity of
the IC droop gain mIC in (20b) would be 2 p.u. Fig. 5 plots
the eigenvalue λi to the diagonal element akk of the system
the complex eigenvalue pair distribution of the most dominant
state matrix A, as described by
modes for the HMG shown in Fig. 1, considering zero power
flow through the IC. The frequency and damping ratio of ∂λi
pki = (24)
these low-frequency modes are presented in Table 1. Accord- ∂akk
ing to this table, the HMG is stable since all eigenvalues are Fig. 6 shows the highest participating states in the
located in the left-half side of the complex plane. Table 1 also behavior of the most dominant modes. The participation
factors in Fig. 6a show that mode 1 is highly sensitive most dominant mode) moved further into the left-half side
to the state variables of the ac subgrid power controllers of the complex plane, and the damping increased. However,
(1Pac1 , 1Pac2 , 1θ2 ) and the ac subgrid voltage controllers different behavior of the dominant modes can be deduced for
(1φvd1 , 1φvd2 ). The subscripts 1 and 2 represent DG1 and power transfers from ac to dc subgrid. The results in Fig. 7
DG2 in each subgrid in Fig. 1, respectively. Furthermore, suggest that if there is a continuous increase in the power flow
modes 2 and 3 are sensitive to the dc subgrid output volt- from ac to dc subgrid, mode 1 moves to the right-half plane
ages (1vO1 , 1vO2 ) and dc voltage controllers (1φv1 , 1φv2 ) and the system becomes unstable. This is mainly because
states, as shown in Fig. 6b. Mode 4 is sensitive to the state when power is exchanged from ac to dc subgrid, the dynamics
variables of the ac subgrid power controllers (1Pac2 , 1θ2 ), of the ac subgrid will affect those of the dc subgrid and
the ac subgrid voltage controllers (1φvd1 , 1φvd2 ), the IC potentially make the entire HMG unstable. Thus, as the power
current controller (1φcd 0 ), and the IC filter inductor current transfer from ac to the dc subgrid increases, the HMG stability
0
(1ild ), as depicted in Fig. 6a. The participation factor analysis margin could be significantly reduced.
reveals that the states associated with the ac subgrid have a
higher impact on the dominant modes as compared to those
of the dc subgrid.
D. SENSITIVITY ANALYSIS
To further characterize the small-signal stability of the HMG
in Fig. 1, the behavior of the dominant modes to changes in
the power flow direction through the IC is further analyzed.
To zoom in the impact of the power flow direction on the
HMG stability, the dominant eigenvalues movement because
of other factors including the grid impedance is excluded. The
root loci of the dominant modes of the HMG are identified for
FIGURE 8. The loci of dominant modes to ac and dc droop gain changes
five power transfer scenarios shown in Table 2. The first two considering different power transfers.
scenarios, with the power flows through the IC are 1.0 p.u
and 0.5 p.u, correspond to the power transfer from dc to
ac subgrid while scenario 3 considers zero power transfer E. STABILITY MARGIN ANALYSIS
between the subgrids. Thus, in scenario 3, the ac and dc
The stability margin of the HMG is characterized by the
subgrids are operated independently with no power exchange.
maximum power transfer capability of the ICs and the critical
The last two scenarios, 4 and 5, correspond to power flows
droop gains of the DGs [25]. In the following subsections,
(−0.5 p.u and −1.0 p.u) from ac to dc subgrid.
the dc to ac subgrid power flow (0.5 p.u), zero power flow,
and ac to dc subgrid power flow (−0.5 p.u) conditions are
considered. Firstly, let us consider the loci of the dominant
modes to changes in the droop gains (mac = mdc ). By con-
stantly increasing the droop gains from a value of 0.02 p.u,
Fig. 8 shows that mode 1 moves towards the right-half plane.
However, for the condition in Fig. 8a where 0.5 p.u flows
from dc to ac subgrid, the HMG dominant modes remain
in the left-half plane and retain the system stability when
mac = mdc ≤ 0.034 p.u. Thus, the stability margin for
FIGURE 7. Dominant eigenvalue sensitivity for different power flow
scenarios. this condition is given as 0.034 p.u. Furthermore, Fig. 8b
shows a trace of the dominant modes when there is no power
Fig. 7 shows the loci of the dominant modes for the five transfer between both subgrids. By increasing the droop
power flow scenarios. As seen in this figure, as the power gains, the system becomes unstable when mode 1 crosses the
flow from dc to ac subgrid increased, mode 1 (which is the imaginary axis at mac = mdc = 0.029 p.u, which dictates
FIGURE 10. The loci of dominant modes to dc droop gain changes only
considering different power transfers.
Secondly, the loci of the dominant modes, when mdc is set A. DC TO AC SUBGRID POWER FLOW OPERATION
to 0.02 p.u while mac is varied in steps, are depicted in Fig. 9. The power flow direction from dc to ac subgrid with and
The results in Fig. 9a show that the critical droop gain for without the reactive power support capability of the IC is
the power flow condition of 0.5 p.u transfered from dc to ac investigated.
subgrid is mac = 0.036 p.u. For zero power flow condition,
the loci of the dominant modes are depicted in Fig. 9b. 1) DC TO AC SUBGRID POWER FLOW OPERATION
We observe that the stability margin is defined by the ac droop WITHOUT IC REACTIVE POWER SUPPORT
gain mac = 0.030 p.u. Whereas, Fig. 9c shows that a droop In this case study, the . Initially, to investigate the impact of
gain of 0.026 p.u is the critical value for the ac to dc subgrid the power flow from dc to ac subgrid on the HMG stability,
power flow of −0.5 p.u. It can be concluded that the dc to ac the dc subgrid of the HMG in Fig. 1 is loaded with a total dc
power flow condition still exhibits a wider stable operating power demand of 1.0 p.u. Furthermore, the ac loads of the ac
range of the power transfer through the IC, as compared to subgrid are varied such that 1) For time t = 0 to 5 s, the ac
the other operating conditions. Finally, when mac is set at subgrid is loaded with 2.0 p.u. 2) At t = 5 s, the ac subgrid is
0.02 p.u while the dc droop gain mdc is varied, the loci of overloaded at 2.5 p.u by connecting an additional 0.5 p.u load
the dominant modes are plotted in Fig. 10. Fig. 10 shows that at Bus-A1. 3) At t = 10 s, by connecting another 0.5 p.u load
mode 1 would remain almost constant for the three power at Bus-A2, the ac subgrid total load is increased to 3.0 p.u.
transfer conditions. Thus, the overall stability of the HMG Simulation results in Fig. 11a show that the load power
is not greatly affected, as the most dominant modes slightly of the ac subgrid increased to 2.5 p.u and 3.0 p.u from the
move when mdc is changed while mac is kept constant. From interval of 5 to 10 s and 10 to 15 s, respectively, while the dc
Fig. 8-10, the ac subgrid dominates the HMG dynamics and subgrid is loaded at 1.0 p.u for the entire period. Furthermore,
stability margin. the DGs’ output power responses of both ac and dc subgrids
are depicted in Fig. 11b and 11c, respectively. The dynamic
IV. TIME-DOMAIN SIMULATION RESULTS response of the power flowing through the IC is shown
Time-domain simulations are carried out to verify the impact in Fig. 11d. The ac frequency and dc voltage measured at the
of the IC power flow direction on the HMG stability. Several IC terminals are plotted in Fig. 11e. From t = 0 to 5 s, both
FIGURE 13. Dynamic responses for ac to dc power flow condition. FIGURE 14. Dynamic responses for an increase in the ac power
generation capacity.
FIGURE 15. Dynamic responses for an increase in the dc power FIGURE 16. Dynamic responses for ac to dc power flow condition in case
generation capacity. of (Pac − V ) and (Qac − ω) droop control in the ac subgrid.
the X/R ratio of the ac subgrid, the active power can be highly
dependent on the voltage magnitude whereas the reactive
power is strongly coupled with the frequency [26]. Thus,
the (Pac − V ) and (Qac − ω) droop characteristics would be
used instead. This case study is therefore designed to investi-
gate the HMG dynamics when the inverter-based DGs in the
ac subgrid adopt (Pac −V ) and (Qac −ω) droop characteristics.
The inverter-based DGs in Fig. 1 are equipped with droop
controllers that implement the (Pac − V ) and (Qac − ω) droop
FIGURE 17. Hybrid microgrid with different DG ratings, multiple ICs, and
equations. The test HMG in Fig. 1 is simulated and the time- meshed topology.
domain response is reported in Fig. 16. As observed in this
figure, droop-based HMGs would still exhibit an oscillatory
behavior for ac to dc power flow direction even when the DGs capacity is increased to 1.75 p.u. The impact of the power
in the ac subgrid adopt different droop characteristics. flow from the ac to dc subgrid on the stability of the meshed
HMG with multiple ICs is evaluated as follows. Initially from
F. HYBRID MICROGRID OPERATION WITH DIFFERENT DG t = 0 to 5 s, the ac and dc loads are 0.75 p.u and 2.25 p.u,
RATINGS, MULTIPLE ICs, AND MESHED TOPOLOGY respectively, as shown in Fig. 18a. Fig. 18b and 18c depict
The stability analysis is extended to a meshed HMG with the dynamic responses of the DGs’ power outputs of both ac
multiple ICs and DGs having different ratings. The meshed and dc subgrids, respectively. Fig. 18d shows the dynamic
HMG involves six DGs distributed in two subgrids, two responses of the power transfer of both ICs. Fig. 18e presents
ICs, and ac/dc loads. The meshed HMG is depicted by its the normalized ac frequency and dc voltage of IC1. Since
schematic diagram in Fig. 17. The total capacity of the both subgrids can supply their own loads, the ICs transfer no
ac subgrid is 25 kVA with DG1, DG2, and DG3 having power to either subgrid, as shown in Fig. 18d. At t = 5 s,
capacities of 5 kVA, 7.5 kVA, and 10 kVA, respectively. a step load increase of 0.75 p.u has occurred on the dc side.
Whereas, the dc subgrid has a maximum capacity of 25 kW Consequently, the DGs on the ac side increase their outputs,
and dc-type DG1, DG2, and DG3 are rated at 5 kW, 7.5 kW, as shown in Fig. 18b, to supply the load increase in the
and 10 kW, respectively. This meshed HMG is created by dc side. At t = 10 s, the dc load is further increased by
adding a DG unit and a distribution line in each subgrid 0.75 p.u and the dc subgrid requests more power from its
and a second IC, IC2, with the rating of 7.5 kVA connected neighboring ac subgrid. Accordingly, the ICs start to increase
between buses A3 and B4. Thus, the total power transfer the power flow from the ac to dc subgrid, resulting in a highly
VI. CONCLUSION
The operating point including the amount and direction of the
power flow between ac and dc subgrids in an HMG largely
affects the stability. Thus, this paper investigated the impact
of the power flow on the stability of HMGs formed by the
interconnection of ac and dc subgrids through bidirectional
ICs. It is observed that as the power flow from the ac to dc
subgrid increases, the stability margin of the HMG may be
reduced. This is mainly because when the power is exchanged
from the ac to dc subgrid, the dynamics associated with the
ac subgrid have greater influence on the HMG stability as
compared to those of the dc subgrid. Moreover, an increase
in the generation capacity of the ac subgrid increases the
power flow from the ac to dc subgrid to supply the dc load
power, which could degrade the stability of the HMG. Thus,
it is technically advised to design the HMG such that the
ac subgrid receives power from the dc subgrid. The stability
analysis presented in this paper is not meant to emphasize
that the amount and direction of the power transfer could
FIGURE 18. Dynamic responses for ac to dc power flow condition in case
of different DG ratings, multiple ICs, and meshed topology. always jeopardize the stability but rather, precaution should
be exercised when transferring power from one subgrid to the
other.
[2] R. Majumder, ‘‘Some aspects of stability in microgrids,’’ IEEE Trans. [25] S. Peyghami, H. Mokhtari, and F. Blaabjerg, ‘‘Autonomous operation of
Power Syst., vol. 28, no. 3, pp. 3243–3252, Aug. 2013. a hybrid AC/DC microgrid with multiple interlinking converters,’’ IEEE
[3] E. A. A. Coelho, P. C. Cortizo, and P. F. D. Garcia, ‘‘Small-signal stability Trans. Smart Grid, vol. 9, no. 6, pp. 6480–6488, Nov. 2018.
for parallel-connected inverters in stand-alone AC supply systems,’’ IEEE [26] J. M. Guerrero, L. GarciadeVicuna, J. Matas, M. Castilla, and J. Miret,
Trans. Ind. Appl., vol. 38, no. 2, pp. 533–542, Aug. 2002. ‘‘Output impedance design of parallel-connected UPS inverters with wire-
[4] F. Gao, S. Bozhko, A. Costabeber, C. Patel, P. Wheeler, C. I. Hill, and less load-sharing control,’’ IEEE Trans. Ind. Electron., vol. 52, no. 4,
G. Asher, ‘‘Comparative stability analysis of droop control approaches pp. 1126–1135, Aug. 2005.
in voltage-source-converter-based DC microgrids,’’ IEEE Trans. Power
Electron., vol. 32, no. 3, pp. 2395–2415, Mar. 2017.
[5] J. M. Guerrero, L. GarciadeVicuna, J. Matas, M. Castilla, and J. Miret,
‘‘A wireless controller to enhance dynamic performance of parallel invert-
ers in distributed generation systems,’’ IEEE Trans. Power Electron.,
vol. 19, no. 5, pp. 1205–1213, Sep. 2004.
[6] A. Kahrobaeian and Y. A.-R.-I. Mohamed, ‘‘Analysis and mitigation
of low-frequency instabilities in autonomous medium-voltage converter-
based microgrids with dynamic loads,’’ IEEE Trans. Ind. Electron., vol. 61, ABDELSALAM A. EAJAL (Member, IEEE)
no. 4, pp. 1643–1658, Apr. 2014. received the B.Sc. degree (Hons.) in electrical
[7] H. Liang, B. J. Choi, W. Zhuang, and X. Shen, ‘‘Stability enhancement of engineering from Sirte University, Sirte, Libya,
decentralized inverter control through wireless communications in micro- in 2001, the M.A.Sc. degree in electrical and
grids,’’ IEEE Trans. Smart Grid, vol. 4, no. 1, pp. 321–331, Mar. 2013. computer engineering from Dalhousie University,
[8] L. Guo, S. Zhang, X. Li, Y. W. Li, C. Wang, and Y. Feng, ‘‘Stability Halifax, NS, Canada, in 2008, the Ph.D. degree
analysis and damping enhancement based on frequency-dependent virtual in electrical and computer engineering from the
impedance for DC microgrids,’’ IEEE J. Emerg. Sel. Topics Power Elec- University of Waterloo, Waterloo, ON, Canada,
tron., vol. 5, no. 1, pp. 338–350, Mar. 2017. in 2018. From 2003 to 2005, he worked as a
[9] Y. Li and L. Fan, ‘‘Stability analysis of two parallel converters with Power Engineer with General Electricity Company
voltage-current droop control,’’ IEEE Trans. Power Del., vol. 32, no. 6, of Libya (GECOL). From 2008 to 2012, he worked as an Undergraduate
pp. 2389–2397, Dec. 2017. Instructor with Sirte University. In Fall 201l, he joined the University of
[10] M. Hamzeh, M. Ghafouri, H. Karimi, K. Sheshyekani, and J. M. Guerrero, Tripoli, Tripoli, Libya, as a Visiting Lecturer. He has been recognized as
‘‘Power oscillations damping in DC microgrids,’’ IEEE Trans. Energy one of the best reviewers for the IEEE TRANSACTIONS ON SMART GRID. He is
Convers., vol. 31, no. 3, pp. 970–980, Sep. 2016. currently a Postdoctoral Fellow with the University of Waterloo. His research
[11] N. Pogaku, M. Prodanovic, and T. C. Green, ‘‘Modeling, analysis and interests include planning, operation, stability, and control of ac/dc hybrid
testing of autonomous operation of an inverter-based microgrid,’’ IEEE distribution systems.
Trans. Power Electron., vol. 22, no. 2, pp. 613–625, Mar. 2007.
[12] E. Alizadeh, M. Hamzeh, and A. M. Birjandi, ‘‘A multifunctional control
strategy for oscillatory current sharing in DC microgrids,’’ IEEE Trans.
Energy Convers., vol. 32, no. 2, pp. 560–570, Jun. 2017.
[13] P. C. Loh, D. Li, Y. K. Chai, and F. Blaabjerg, ‘‘Autonomous operation of
hybrid microgrid with AC and DC subgrids,’’ IEEE Trans. Power Electron.,
vol. 28, no. 5, pp. 2214–2223, May 2013.
[14] P. C. Loh, D. Li, Y. K. Chai, and F. Blaabjerg, ‘‘Hybrid AC-DC microgrids
with energy storages and progressive energy flow tuning,’’ IEEE Trans. HARIKRISHNA MUDA (Member, IEEE) recei-
Power Electron., vol. 28, no. 4, pp. 1533–1543, Jul. 2013. ved the M.Tech. and Ph.D. degrees in electrical
[15] N. Eghtedarpour and E. Farjah, ‘‘Power control and management in engineering from the Indian Institute of Technol-
a hybrid AC/DC microgrid,’’ IEEE Trans. Smart Grid, vol. 5, no. 3, ogy Roorkee, India, in 2010 and 2017, respec-
pp. 1494–1505, May 2014. tively. He was a Research Engineer with the
[16] A. A. Radwan and Y. A.-R. I. Mohamed, ‘‘Networked control and power Khalifa University of Science and Technology,
management of AC/DC hybrid microgrids,’’ IEEE Syst. J., vol. 11, no. 3, Abu Dhabi, United Arab Emirates. He is cur-
pp. 1662–1673, Sep. 2014. rently working as a Postdoctoral Associate with
[17] A. A. A. Radwan and Y. A.-R.-I. Mohamed, ‘‘Assessment and mitigation the National Institute of Advanced Studies, Indian
of interaction dynamics in hybrid AC/DC distribution generation systems,’’ Institute of Science, Bengaluru, India. His current
IEEE Trans. Smart Grid, vol. 3, no. 3, pp. 1382–1393, Sep. 2012. research interests include microgrid protection and control, ac/dc hybrid
[18] D. K. Dheer, S. Doolla, and A. K. Rathore, ‘‘Small signal modeling and distribution system stability, active distribution networks, and energy mix.
stability analysis of a droop based hybrid AC/DC microgrid,’’ in Proc. 42nd
Annu. Conf. IEEE Ind. Electron. Soc. (IECON), Oct. 2016, pp. 3775–3780.
[19] S. Leitner, M. Yazdanian, A. Mehrizi-Sani, and A. Muetze, ‘‘Small-signal
stability analysis of an inverter-based microgrid with internal model-
based controllers,’’ IEEE Trans. Smart Grid, vol. 9, no. 5, pp. 5393–5402,
Sep. 2018.
[20] S. Anand and B. G. Fernandes, ‘‘Reduced-order model and stability anal-
ysis of low-voltage DC microgrid,’’ IEEE Trans. Ind. Electron., vol. 60,
no. 11, pp. 5040–5049, Nov. 2013. ADEDAYO ADERIBOLE received the B.Sc.
[21] Y. Xia, M. Yu, P. Yang, Y. Peng, and W. Wei, ‘‘Generation-storage coor- degree in electronic/electrical engineering from
dination for islanded DC microgrids dominated by PV generators,’’ IEEE Obafemi Awolowo University, Ile-Ife, Nigeria,
Trans. Energy Convers., vol. 34, no. 1, pp. 130–138, Mar. 2019. the M.Sc. degree in electrical power engineering
[22] C. A. Hill, M. C. Such, D. Chen, J. Gonzalez, and W. M. Grady, ‘‘Battery from the Khalifa University of Science and Tech-
energy storage for enabling integration of distributed solar power genera- nology, Abu Dhabi, United Arab Emirates. He is
tion,’’ IEEE Trans. Smart Grid, vol. 3, no. 2, pp. 850–857, Jun. 2012. currently pursuing the Ph.D. degree in electrical
[23] F. G. Torres, ‘‘Advanced control of renewable energy microgrids with engineering and computer science with the Mas-
hybrid energy storage system,’’ Ph.D. dissertation, Univ. Seville, Seville, sachusetts Institute of Technology (MIT), USA.
Spain, 2015. His research interests include power systems sta-
[24] P. Kundur, N. J. Balu, and M. G. Lauby, Power System Stability and bility and control, power line communication, and smart grid technologies,
Control, vol. 7. New York, NY, USA: McGraw-Hill, 1994. such as demand-side management.
MOHAMED AL HOSANI (Senior Member, and distributed generation. He was a Visiting Professor with the Mas-
IEEE) received the B.Sc. degree in electrical engi- sachusetts Institute of Technology, Cambridge, MA, USA. He is currently
neering from the American University of Sharjah, with the Faculty of Engineering, Cairo University, Egypt, and is on leave
United Arab Emirates, in 2008, and the M.Sc. and from the Khalifa University of Science and Technology, Abu Dhabi, United
Ph.D. degrees in electrical engineering from the Arab Emirates. His current research interests include distribution system
University of Central Florida, Orlando, FL, USA, protection, distributed generation, and micro grids. He is also an Editor for
in 2010 and 2013, respectively. He was an Assis- the IEEE TRANSACTIONS ON ENERGY CONVERSION.
tant Professor with the Department of Electrical
and Computer Engineering, Khalifa University,
Abu Dhabi, United Arab Emirates, from 2014 to
2018, and a Visiting Assistant Professor with the Massachusetts Institute of
Technology, Cambridge, MA, USA, from 2015 to 2016. He is currently the
Department Manager of Demand Side Management (DSM), Abu Dhabi Dis- E. F. EL-SAADANY (Fellow, IEEE) was born
tribution Company, Abu Dhabi. His research interests include demand side in Cairo, Egypt, in 1964. He received the B.Sc.
management, distributed generation protection and control, and modeling and M.Sc. degrees in electrical engineering from
and stability analysis of microgrid and smart grid. Ain Shams University, Cairo, Egypt, in 1986 and
1990, respectively, and the Ph.D. degree in electri-
cal engineering from the University of Waterloo,
Waterloo, ON, Canada, in 1998, where he was a
Professor with the ECE Department till 2019. He is
HATEM ZEINELDIN (Senior Member, IEEE) currently a Professor with the Department of Elec-
received the B.Sc. and M.Sc. degrees in elec- trical and Computer Engineering and the Director
trical engineering from Cairo University, Giza, of the Advanced Power and Energy Research Center, Khalifa University,
Egypt, in 1999 and 2002, respectively, and the Abu Dhabi, United Arab Emirates. His research interests include smart grid
Ph.D. degree in electrical and computer engineer- operation and control, microgrids, self healing, power quality, distributed
ing from the University of Waterloo, Waterloo, generation, power electronics interfacing, and mechatronics. He is also an
ON, Canada, in 2006. He was with Smith and Editor of the IEEE TRANSACTIONS ON SMART GRID, IEEE TRANSACTIONS ON
Andersen Electrical Engineering, Inc., North York, POWER SYSTEMS, and IEEE POWER SYSTEMS LETTERS. He is also a Registered
ON, USA, where he was involved in projects Professional Engineer in the Province of Ontario.
involving distribution system designs, protection,