TABLE OF CONTENTS
1 Scope of Work
The intention of this document is to provide clean agent system calculations for the
EPC-6 contract buildings. This document covers particularly the clean agent system
calculations for the Fire and safety building as per fire fighting design basis and
related DGS documents for the EPC-6 contract
The clean agent system design shall be based on the following documents and
standards:
NFPA-2001
3 Units of Measurement
4 Software
The clean agent system design is based on the total flooding fixed fire extinguishing
system utilizing “Inergen” Clean agent for the following protected areas of the fire and
safety building
The number of cylinders and the nozzles are calculated based on the minimum
design concentration of 37.5%.
6 Conclusion
The clean agent system calculations have been prepared for every room individually
as per the above description. The calculations results are attached in appendix A.
Appendix A
PROJECT INFORMATION
Project Name: RUWAIS REFINERY EXP.(PACK-6,PROJ # 5578) NON PROCESS BLDG
Project Designer: JANARDHANAN
Project Location: ABU DHABI
Project Account: 66-11
Project Description: EMERGENCY RESPONSE CENTRE @ GROUIND FLOOR
(FIRE & SAFETY BUILDING)
Project Filename: E:\jana\(66-11) RUWAIS REFINERY EXP.(PACK-6,PROJ # 5578) NON
PROCESS BLDG. (FALCON)\DESIGN-01\REV-00\Fire
Safety\CALC\EMERGENCY RESPONSE CENTRE (@ GROUND FLOOR).pro
CUSTOMER INFORMATION
Company Name: M/S NAFFCO
Company Address: ABU DHABI
P.O.BOX:4192
Company Phone: 02-6904555
Company Fax: 02-6904777
Contact Information: M.SASI KUMAR
Page 1 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Nozzle Performance
Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure
0101 0.5312 mm 17.87 m³ 20.93 m³ 292.00 kPa
0102 0.5312 mm 17.87 m³ 19.74 m³ 273.00 kPa
0103 0.5312 mm 17.87 m³ 19.74 m³ 273.00 kPa
0104 0.5312 mm 17.87 m³ 18.36 m³ 244.00 kPa
0105 0.5312 mm 17.87 m³ 18.36 m³ 244.00 kPa
0106 0.5312 mm 17.87 m³ 18.36 m³ 244.00 kPa
0107 0.5312 mm 17.89 m³ 18.36 m³ 244.00 kPa
Agent Concentration
Minimum Conc Design Conc Min Predicted Conc Max Predicted Conc
38.00% 38.00% 40.04% 40.04%
Venting Requirements
Enclosure Wall Strength Vent Flow Coefficient Vent Safety Factor Vent Area Required
5.00 kPA 0.60 2.00 765 in² (5.3 ft²)
Agent Discharge Time
45.5 seconds to reach 95% of Design Concentration
Page 2 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Nozzle Performance
Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure
0301 0.2280 mm 3.58 m³ 3.82 m³ 289.00 kPa
0302 0.2380 mm 3.58 m³ 4.01 m³ 273.00 kPa
0303 0.2380 mm 3.58 m³ 4.01 m³ 273.00 kPa
0304 0.2380 mm 3.58 m³ 3.57 m³ 228.00 kPa
0305 0.2380 mm 3.58 m³ 3.57 m³ 228.00 kPa
0306 0.2380 mm 3.58 m³ 3.57 m³ 228.00 kPa
0307 0.2380 mm 3.57 m³ 3.57 m³ 228.00 kPa
Agent Concentration
Minimum Conc Design Conc Min Predicted Conc Max Predicted Conc
38.00% 38.00% 39.29% 39.29%
Venting Requirements
Enclosure Wall Strength Vent Flow Coefficient Vent Safety Factor Vent Area Required
5.00 kPA 0.60 2.00 150 in² (1.0 ft²)
Agent Discharge Time
49.1 seconds to reach 95% of Design Concentration
Nozzle Performance
Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure
0201 0.2610 mm 4.17 m³ 5.44 m³ 318.00 kPa
0202 0.2610 mm 4.17 m³ 5.12 m³ 296.00 kPa
0203 0.2610 mm 4.17 m³ 5.12 m³ 296.00 kPa
0204 0.2610 mm 4.17 m³ 4.71 m³ 267.00 kPa
0205 0.2610 mm 4.17 m³ 4.71 m³ 267.00 kPa
0206 0.2610 mm 4.17 m³ 4.71 m³ 267.00 kPa
0207 0.2610 mm 4.17 m³ 4.71 m³ 267.00 kPa
Agent Concentration
Minimum Conc Design Conc Min Predicted Conc Max Predicted Conc
38.00% 38.00% 39.02% 39.02%
Venting Requirements
Enclosure Wall Strength Vent Flow Coefficient Vent Safety Factor Vent Area Required
5.00 kPA 0.60 2.00 197 in² (1.4 ft²)
Agent Discharge Time
51.1 seconds to reach 95% of Design Concentration
Page 3 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Page 4 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Page 5 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Page 6 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Page 7 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Page 8 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Final calculation with selected nozzle codes. Convergance of the iteration of nozzle flow rate and pressure is 2.5%
Venting Report
Enclosure 1 with 5 lbs/sq ft enclosure strength requires minimum of 765 square inches vent area or 5.32 square feet.
Flow coefficient for vent must be at least 0.6. A safety factor of 2 was used in the vent calculation.
Enclosure 2 with 5 lbs/sq ft enclosure strength requires minimum of 197 square inches vent area or 1.37 square feet.
Flow coefficient for vent must be at least 0.6. A safety factor of 2 was used in the vent calculation.
Enclosure 3 with 5 lbs/sq ft enclosure strength requires minimum of 150 square inches vent area or 1.04 square feet.
Flow coefficient for vent must be at least 0.6. A safety factor of 2 was used in the vent calculation.
Page 9 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Page 10 of 11
Pro-Inert Flow Calculation Software Fike Corporation
Page 11 of 11
Pro-Inert Flow Calculation Software Fike Corporation
PROJECT INFORMATION
Project Name: RUWAIS REFINERY EXP.(PACK-6,PROJ # 5578) NON PROCESS BLDG
Project Designer: JANARDHANAN
Project Location: ABU DHABI
Project Account: 66-11
Project Description: SERVER ROOM @ GROUIND FLOOR
(FIRE & SAFETY BUILDING)
Project Filename: E:\jana\(66-11) RUWAIS REFINERY EXP.(PACK-6,PROJ # 5578) NON
PROCESS BLDG. (FALCON)\DESIGN-01\REV-00\Fire Safety\CALC\SERVER
ROOM (@ GROUND FLOOR).pro
CUSTOMER INFORMATION
Company Name: M/S NAFFCO
Company Address: ABU DHABI
P.O.BOX:4192
Company Phone: 02-6904555
Company Fax: 02-6904777
Contact Information: M.SASI KUMAR
Page 1 of 9
Pro-Inert Flow Calculation Software Fike Corporation
Nozzle Performance
Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure
0101 0.5938 mm 27.28 m³ 28.02 m³ 331.00 kPa
0104 0.5938 mm 27.28 m³ 28.02 m³ 331.00 kPa
0102 0.5938 mm 27.28 m³ 28.02 m³ 331.00 kPa
0103 0.5938 mm 27.28 m³ 28.02 m³ 331.00 kPa
Agent Concentration
Minimum Conc Design Conc Min Predicted Conc Max Predicted Conc
38.00% 38.00% 38.80% 38.80%
Venting Requirements
Enclosure Wall Strength Vent Flow Coefficient Vent Safety Factor Vent Area Required
5.00 kPA 0.60 2.00 669 in² (4.6 ft²)
Agent Discharge Time
50.4 seconds to reach 95% of Design Concentration
Page 2 of 9
Pro-Inert Flow Calculation Software Fike Corporation
Nozzle Performance
Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure
0204 0.2420 mm 4.31 m³ 4.39 m³ 305.00 kPa
0203 0.2420 mm 4.31 m³ 4.39 m³ 305.00 kPa
0201 0.2420 mm 4.31 m³ 4.39 m³ 305.00 kPa
0202 0.2420 mm 4.31 m³ 4.39 m³ 305.00 kPa
Agent Concentration
Minimum Conc Design Conc Min Predicted Conc Max Predicted Conc
38.00% 38.00% 38.57% 38.57%
Venting Requirements
Enclosure Wall Strength Vent Flow Coefficient Vent Safety Factor Vent Area Required
5.00 kPA 0.60 2.00 106 in² (0.7 ft²)
Agent Discharge Time
52.0 seconds to reach 95% of Design Concentration
Page 3 of 9
Pro-Inert Flow Calculation Software Fike Corporation
Page 4 of 9
Pro-Inert Flow Calculation Software Fike Corporation
Page 5 of 9
Pro-Inert Flow Calculation Software Fike Corporation
Page 6 of 9
Pro-Inert Flow Calculation Software Fike Corporation
Page 7 of 9
Pro-Inert Flow Calculation Software Fike Corporation
Final calculation with selected nozzle codes. Convergance of the iteration of nozzle flow rate and pressure is 2.5%
Venting Report
Enclosure 1 with 5 lbs/sq ft enclosure strength requires minimum of 669 square inches vent area or 4.65 square feet.
Flow coefficient for vent must be at least 0.6. A safety factor of 2 was used in the vent calculation.
Enclosure 2 with 5 lbs/sq ft enclosure strength requires minimum of 106 square inches vent area or .73 square feet.
Flow coefficient for vent must be at least 0.6. A safety factor of 2 was used in the vent calculation.
Page 8 of 9
Pro-Inert Flow Calculation Software Fike Corporation
Page 9 of 9
Pro-Inert Flow Calculation Software Fike Corporation
PROJECT INFORMATION
Project Name: RUWAIS REFINERY EXP.(PACK-6,PROJ # 5578) NON PROCESS BLDG
Project Designer: JANARDHANAN
Project Location: ABU DHABI
Project Account: 66-11
Project Description: UPS ROOM @ FLOOR FLOOR
(FIRE & SAFETY BUILDING)
Project Filename: E:\jana\(66-11) RUWAIS REFINERY EXP.(PACK-6,PROJ # 5578) NON
PROCESS BLDG. (FALCON)\DESIGN-01\REV-00\Fire Safety\CALC\UPS
ROOM (@ FIRST FLOOR).pro
CUSTOMER INFORMATION
Company Name: M/S NAFFCO
Company Address: ABU DHABI
P.O.BOX:4192
Company Phone: 02-6904555
Company Fax: 02-6904777
Contact Information: M.SASI KUMAR
Page 1 of 6
Pro-Inert Flow Calculation Software Fike Corporation
Nozzle Performance
Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure
0102 0.4688 mm 17.23 m³ 24.31 m³ 385.00 kPa
0101 0.4688 mm 17.23 m³ 24.31 m³ 385.00 kPa
Agent Concentration
Minimum Conc Design Conc Min Predicted Conc Max Predicted Conc
38.00% 38.00% 49.06% 49.06%
Venting Requirements
Enclosure Wall Strength Vent Flow Coefficient Vent Safety Factor Vent Area Required
5.00 kPA 0.60 2.00 235 in² (1.6 ft²)
Agent Discharge Time
32.2 seconds to reach 95% of Design Concentration
Page 2 of 6
Pro-Inert Flow Calculation Software Fike Corporation
Page 3 of 6
Pro-Inert Flow Calculation Software Fike Corporation
Page 4 of 6
Pro-Inert Flow Calculation Software Fike Corporation
Final calculation with selected nozzle codes. Convergance of the iteration of nozzle flow rate and pressure is 2.5%
Venting Report
Enclosure 1 with 5 lbs/sq ft enclosure strength requires minimum of 235 square inches vent area or 1.63 square feet.
Flow coefficient for vent must be at least 0.6. A safety factor of 2 was used in the vent calculation.
Page 5 of 6
Pro-Inert Flow Calculation Software Fike Corporation