CONTRACTOR : Ed.ZUBLIN AG
This page is a record of all revisions of this document. All previous issues are hereby
superseded and are to be destroyed.
REASON APPROVED
REV DATE BY CHKD REVD
FOR ISSUE PEM PMC COMPANY
NOTES:
(a) By a vertical line in the right-hand margin against the revised text.
(b) By a triangle symbol for graphics, the revision number being denoted within
the symbol.
Revision symbols are positioned adjacent to the revision.
(c) CHKD = Checked by, REVD = Reviewed by, PEM = Project Engineering
Manager, PMC = Project Management Consultant
NOTES:
TABLE OF CONTENTS
1 Scope of Work
The intention of this document is to provide clean agent system calculations for the
EPC-6 contract buildings. This document covers particularly the clean agent system
calculations for the main workshop as per fire fighting design basis and related DGS
documents for the EPC-6 contract
The clean agent system design shall be based on the following documents and
standards:
NFPA-2001
3 Units of Measurement
4 Software
The clean agent system design is based on the total flooding fixed fire extinguishing
system utilizing “Inergen” Clean agent for the following protected areas of the main
workshop building
a. UPS room.
The number of cylinders and the nozzles are calculated based on the minimum
design concentration of 37.5%.
6 Conclusion
The clean agent system calculations have been prepared for every room individually
as per the above description. The calculations results are attached in appendix A.
Appendix A
PROJECT INFORMATION
Project Name: RUWAIS REFINERY EXP.(PACK-6,PROJ # 5578) NON PROCESS BLDG
Project Designer: JANARDHANAN
Project Location: ABU DHABI
Project Account: 66-11
Project Description: UPS ROOM @ GROUND FLOOR (MAIN WORKSHOP)
Project Filename: E:\jana\(66-11) RUWAIS REFINERY EXP.(PACK-6,PROJ # 5578) NON
PROCESS BLDG. (FALCON)\DESIGN-01\REV-00\Main Workshop\UPS
ROOM.pro
CUSTOMER INFORMATION
Company Name: M/S NAFFCO
Company Address: ABU DHABI
P.O.BOX:4192
Company Phone: 02-6904555
Company Fax: 02-6904777
Contact Information: M.SASI KUMAR
Page 1 of 6
Pro-Inert Flow Calculation Software Fike Corporation
Nozzle Performance
Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure
0101 0.5625 mm 37.79 m³ 48.62 m³ 583.00 kPa
Agent Concentration
Minimum Conc Design Conc Min Predicted Conc Max Predicted Conc
38.00% 38.00% 45.94% 45.94%
Venting Requirements
Enclosure Wall Strength Vent Flow Coefficient Vent Safety Factor Vent Area Required
5.00 kPA 0.60 2.00 239 in² (1.7 ft²)
Agent Discharge Time
36.9 seconds to reach 95% of Design Concentration
Page 2 of 6
Pro-Inert Flow Calculation Software Fike Corporation
Page 3 of 6
Pro-Inert Flow Calculation Software Fike Corporation
Page 4 of 6
Pro-Inert Flow Calculation Software Fike Corporation
Final calculation with selected nozzle codes. Convergance of the iteration of nozzle flow rate and pressure is 2.5%
Venting Report
Enclosure 1 with 5 lbs/sq ft enclosure strength requires minimum of 239 square inches vent area or 1.66 square feet.
Flow coefficient for vent must be at least 0.6. A safety factor of 2 was used in the vent calculation.
Page 5 of 6
Pro-Inert Flow Calculation Software Fike Corporation