You are on page 1of 6

BILL OF QUANTITIES OF 33/6.

6 KV SUBSTATION AT PUMPING STATION


Sr. No. Description UOM Qty SCOPE OF WORK
Supply Installation Remarks
A B C D
1 Vacuum Circuit Breaker
Supplying, erecting, testing and commissioning of 36 kV rated insulation class BIL 170
kV peak 630 A, 25 KA breaking capacity, 3 phase, 50 cycles, outdoor type Vacuum
Circuit Breaker operating mechanism, etc. Nos. 3.00 YES YES

2 Isolators
a Supplying, erecting, testing and commissioning of 36 kV rated insulation class BIL 170
kV peak 200 A,25 KA for 1 second), 3 phase, 50 cycles, tilting outdoor type isolator Nos. 1.00 YES YES
with earth blades.
b Supplying, erecting, testing and commissioning of 36 kV rated insulation class BIL 170
kV peak 200 A,25 KA for 1 second), 3 phase, 50 cycles, tilting outdoor type isolator Nos. 4.00 YES YES
without earth blades.
3 Current Transformer
Supplying, erecting, testing and commissioning of 36 kV rated insulation class BIL 170
kV peak single phase 50 Hz, hermetically sealed, outdoor type Current Transformer of
following ratings
a) 35/1/1 A, 2 Core ( Details as per SLD) Nos. 3.00 YES YES
b) 35/1/1/1 A, 3 Core ( Details as per SLD) Nos. 6.00 YES YES
4 Potential Transformer
Supplying, erecting, testing and commissioning of 36 kV rated insulation class BIL 170
kV peak single phase 50 Hz, Two core, hermetically sealed, outdoor type voltage
transformer having voltage ratio 33 kV/110 V. Core details will be as per SLD Nos. 3.00 YES YES

5 Board Metering
a) Supplying, erecting, testing and commissioning of 36 kV rated insulation class BIL 170
kV peak single phase 50 Hz, two core, hermetically sealed, outdoor type Current
Transformer as per MPEB specifications for Board Metering Nos. 3.00 YES YES

b) Supplying, erecting, testing and commissioning of 36 kV rated insulation class BIL 170
kV peak single phase 50 Hz, Two core, hermetically sealed, outdoor type voltage
transformer having voltage ratio 33 kV/110 V as per MPEB specifications for Board Nos. 3.00 YES YES
Metering

c) Supplying, erecting, testing and commissioning of Board specified Digital Trivector


meter (Main and Check) to measure various electrical parameters Nos. 1.00 YES YES

6 Lightning Arrester
Supplying, erecting, testing and commissioning of 30 kV rated voltage, 36 kV rated
insulation class, BIL 170 KV peak, single phase 50 Hz, Gapless type, station class,
outdoor, lightning arrester along with surge counter and insulation base. Nos. 9.00 YES YES

7 Pole Structure
Supplying, erecting, testing and commissioning of Galvanised steel structures required
for Bus bar equipments alongwith hardware such as nuts, bolts, washers, foundation
bolts etc.
ISHB 150 x 150 mm, 10 M Long (Wt. 37.1 kG / M) Nos. 10.00 YES YES
ISMC 100 x 50 mm, 5.5 M Long (Wt. 9.2 kG / M) Nos. 30.00 YES YES
Clamps, nut bolts, Hardware, etc. Lot 1.00 YES YES
8 Galvanised Steel Structure
Supplying, erecting, testing and commissioning of Galvanised steel structures required
for Bus bar equipments, gantry towers alongwith hardware such as nuts, bolts, washers, Lot 1.00 YES YES
foundation bolts etc.
a Supply, Transport, insurance, erection, of 33 kV Vacuum Circuit Breaker Supporting
Structure (by Manufacturer) Nos. 3.00
b Supply, Transport, insurance, erection, of 33 kV CT Supporting Structure (Connected to
breaker structure) Nos. 3.00
c Supply, Transport, insurance, erection, of 33 kV LA Supporting Structure
Nos. 6.00
9 Bus-Bar Material and Insulators

Supply, Erection, Testing and Commissioning of Bus bar material ACSR conductor,
suspension / support insulator, insulator hardware, power connectors,clamps, shield wire
(for lightning protection), etc.
a) ACSR `RACCON' Conductor Lot 1.00 YES YES
b) Clamps and connectors for ACSR conductor Lot 1.00 YES YES
c) 33 kV Disc Insulator Nos. 18.00 YES YES
d) 33 kV Pin Insulator Nos. 3.00 YES YES
10 Junction Boxes
Supplying, erecting, testing and commissioning of Junction Boxes for each equipment in
a bay including wiring cabling, connecting clamps, terminal connectors etc. and also Lot 1.00 YES YES
marshalling boxes one for each bay.
11 Control and Relay Panel
a Supplying, erecting, testing and commissioning of 33 kV incoming feeder control panel
to be located inside switchgear room. Nos. 1.00 YES YES
b Supplying, erecting, testing and commissioning of 33 kV control panel for transformer
feeders to be located inside switchger room. Nos. 2.00 YES YES
12 Transformers
a) Supplying, erecting, testing and commissioning of 33/6.6 kV, 1.6 MVA, ONAN, Dyn11
transformer with OLTC (-15% to +5% in step of 1.25%) Nos. 2.00 YES YES

b) Supplying, erecting, testing and commissioning of RTCC panels to be located inside


control room for remote operation of Transformer OLTC Nos. 2.00 YES YES
BILL OF QUANTITIES OF 33/6.6 KV SUBSTATION AT PUMPING STATION
Sr. No. Description UOM Qty SCOPE OF WORK
Supply Installation Remarks
A B C D
c) Supplying, erecting, testing and commissioning of 6.6 kV, Neutral Grounding
Resistor cubicle with NGR to limit 1.6 MVA transformer neutral current. Nos. 2.00 YES YES
BILL OF QUANTITIES OF 33/6.6 KV SUBSTATION AT PUMPING STATION
Sr. No. Description UOM Qty SCOPE OF WORK
Supply Installation Remarks
A B C D
13 LT Power and Control Cables
Designing, Preparing cable schedule, Supplying, laying, terminating on both ends by
providing cable glands and lugs of required sizes, testing and commissioning of 1.1 kV
grade LT power and control cables for 33 kV substation Lot 1.00 YES YES

14 Cable Trays
a) Designing, Preparing Cable tray layout, Supplying and erecting at site Galvanised ladder
and perforated type cable trays along with cable tray supports for laying power and
control cables inside switchyard in trenches and from switchyard to control room and Lot 1.00 YES YES
inside control room.

b) Providing, installing at site of work the Chequred Plates / RCC slabs to cover trenches,
cable tray supports with angles and channels etc. RCC Slab shall be
Lot 1.00 YES YES
excluded from SOW

15 Substation Earthing
Desiigning, Preparing Earthing Layout, Supplying, erecting and testing at site Earthing
materials including Earthmat, Earthing conductors for equipment and structure earthing
and earth pits, etc. complete as per relavent IS / IEEE standards. Lot 1.00 YES YES

i Earth strip of Minimum 60 mm x 8 mm size for Earthmat


ii Pipe Type Treated Earth Pits
iii Rod type Earth pits
16 Designing, Preparing Lighting layout, Supplying, erecting, testing and commissioning of
Lighting system for Substation including lighting poles, LED type lighting fixtures with
lamp, Fixture controlling MCB / MCCB, wiring, Switchyard lighting panel etc. Lot 1.00 YES YES

17 Supplying and erecting at site Chain Link Fencing, gates etc. Mtr 100.00 YES YES
18 Supplying at site set of spares, maintenance tools and tackles Lot 1.00 YES YES
19 Firefighting system and Emulsifier system
Supplying, erecting, testing and commissioning of Firefighting system and Emulsifier
system for switchyard having sand bucket and CO2 extinguisher etc. Lot 1.00 YES YES

20 VFD (475 KW)


a) Supplying, erecting, testing and commissioning of 6.6 kV, 475 KVA,VFD
Nos. 2.00 YES YES

Notes :
1. If any item / items not listed above, but required to complete the job, will be in the scope of
Contractor.

2. For Main power transformers of 8 MVA and its RTCC panels, only erection, precommissioning
checks at site, charging and commissioning will be in the scope of contractor. Main power transformers
along with RTCC panels will be supplied by LCEPL
BILL OF QUANTITIES OF ELECTRICAL WORKS AT PUMPING STATION
SCOPE OF WORK
Sr. No. Description UOM Qty
Supply Installation Remarks
A B C D
1 6.6 kV PMCC PANEL
Supplying, installing at site of work, testing and commissioning of sheet steel dust and
vermin proof, indoor floor mounting type, fully draw out type 6.6 kV HT PMCC panel,
incuding VCBs, CTs and PTs of required ratio for metering and protection, protection
relays, meters, bus bars, indicating lamps, Annunciator windows ect., completely
assembled, wired, tested, painted, confirming to relevent IS, completely suitable for Nos. 1.00 YES YES
following duties, specifications and confirming to detailed specifications

a) Electrical system – 6.6 kV, 3 phase, 50 Hz


b) Bus Bar Capacity – 600 Amps, 25 kA for 1 sec AL Busbar.
c) Panel shall comprise of the following
i. Two nos. incoming VCBs with current rating of 630 A, 25 kA for 1 sec.

ii. One nos. of bus coupler VCBs with current rating of 630 A, 25 kA for 1 sec.

iii. 4 nos. outgoing Feeders (for 475 kW motors) with VCBs of current rating 630 A, 25 kA
for 1 sec.
iv. 2 nos. outgoing Feeders (for 475 kW VFD with VCBs of current rating 630 A, 25 kA
for 1 sec.
v. 1 nos. of Auxiliary Transformer feeders with VCBs of current rating 630A, 25kA for 1
sec.
vi. 2 nos. of Capacitor feeders with VCBs of current rating 630A, 25 kA for 1 sec.

1 6.6 kV MOTOR STARTING PANEL


Supplying, installing at site of work, testing and commissioning of sheet steel dust and
vermin proof, indoor floor mounting type, fully draw out type 6.6 kV HT PMCC panel,
incuding VCBs, CTs and PTs of required ratio for metering and protection, protection
relays, meters, bus bars, indicating lamps, Annunciator windows ect., completely
assembled, wired, tested, painted, confirming to relevent IS, completely suitable for Nos. 1.00 YES YES
following duties, specifications and confirming to detailed specifications

a) Electrical system – 6.6 kV, 3 phase, 50 Hz


b) Bus Bar Capacity – 600 Amps, 25 kA for 1 sec AL Busbar.
c) Panel shall comprise of the following
i. Two nos. incoming VCBs with current rating of 630 A, 25 kA for 1 sec.

ii. One nos. of bus coupler VCBs with current rating of 630 A, 25 kA for 1 sec.

iii. 4 nos. outgoing Feeders (for 475 kW motors) with VCBs of current rating 630 A, 25 kA
for 1 sec.
2 LT Panel
Supplying, installing at site of work, testing and commissioning of sheet steel, dust and
vermin proof, indoor floor mounting type, compartmentalized, Main L.T. Panel
including ACB, MCCBs, MCBs, SFUs, CTs of required ratio for metering and
protection, protective relays, meters, bus bars, indicating lamps, push buttons ect.
completely assembled, wired, tested, painted, confirming to relevant IS completely
suitable for following duties, specifications and confirming to detailed specifications . Nos. 1.00 YES YES
The Panel should have feeders to cater the auxiliary load of the system.

Electrical System - 0.415 kV, 3 Phase, 4 wire 50 Hz.


Busbar Capacity - 300 A, 25 kA, TPN AL Busbar

3 ACDB Panel
Supplying, installing at site of work, testing and commissioning of sheet steel, dust and
vermin proof, indoor floor mounting type L.T. ACDB Panel including MCCBs, MCBs,
SFUs, CTs of required ratio for metering and protection, protective relays, meters, bus
bars, indicating lamps, push buttons ect. completely assembled, wired, tested, painted,
confirming to relevant IS completely suitable for following duties, specifications and Nos. 1.00 YES YES
confirming to detailed specifications . The Panel should have feeders to cater the
auxiliary load of the system.

Electrical System - 0.415 kV, 3 Phase, 4 wire 50 Hz.


Busbar Capacity - 50 A, 25 kA, TPN AL Busbar

4 Valve Actuator Panel


Supplying, installing at site of work, testing and commissioning of sheet steel, dust and
vermin proof, indoor floor / wall mounting type L.T. Valve Panel including MCCBs,
MCBs, SFUs, CTs of required ratio for metering and protection, protective relays,
meters, bus bars, indicating lamps, push buttons ect. completely assembled, wired,
tested, painted, confirming to relevant IS completely suitable for following duties, Nos. 1.00 YES YES
specifications and confirming to detailed specifications . The Panel should have feeders
to cater the Load of HOPD Valves.

Electrical System - 0.415 kV, 3 Phase, 4 wire 50 Hz.


Busbar Capacity - 50 A, 25 kA, TPN AL Busbar

5 LT Distribution boards
BILL OF QUANTITIES OF ELECTRICAL WORKS AT PUMPING STATION
SCOPE OF WORK
Sr. No. Description UOM Qty
Supply Installation Remarks
A B C D
Providing, installing at site of work, testing and commissioning of sheet steel, dust and
vermin proof, indoor floor mounting / wall mounted type LT Distribution boards like
MLDB's, Ventillation and Fan DB's, Power distribution and junction boxes etc as per Lot 1.00 YES YES
site requirement
BILL OF QUANTITIES OF ELECTRICAL WORKS AT PUMPING STATION
SCOPE OF WORK
Sr. No. Description UOM Qty
Supply Installation Remarks
A B C D
7 Capacitor Cubicle
a) Providing, installing at site of work and testing of 6.6 kV, 3 phase, 50 cycles per second
capacitor cubicles of 150 KVAR (min.) Capacity with Isolator, HRC Fuse for 475KW,
6.6 kV Induction Motor to improve the power factor upto 0.95. Nos. 4.00 YES YES

b) Providing, installing at site of work and testing of 6.6 kV, 3 phase, 50 cycles per second
capacitor cubicles of 25 KVAR Capacity for Transformers to improve the power factor Nos. 2.00 YES YES
to 0.95.
8 Batteries, Battery Charger & DCDB
Sizing, Suppling, installing at site work, testing and commissioning of Lead Acid
Batteries of 300 AH or required capcity, Battery Chargers & D.C.D.B. complete unit Nos. 1.00 YES YES
comprising of following.
i) 110 V DC Batteries with 300 Amps Hour or required capacity long with all accessories

ii) Battery Charger for above Batteries comprising of Dual Float cum Boost Charger
receptivity complete with protective Relays etc.
iii) DCDB with required no. of outgoing feeders
9 LT Auxiliary Transformer
Supply, erection, testing and commissioning of 6.6/0.433 kV, 160 kVA, ONAN, Dyn11
transformer with OCTC (-5% to +5% in step of 2.5%) to cater all LT load of the system Nos. 1.00 YES YES

10 A HT Cables
Supplying, laying, testing and commissioning of 6.6 kV (UE) Aluminum conductor,
XLPE cable of following sizes
i
Lot 1.00 YES YES
1R X 3C X 120 SQ.MM AL XLPE Cable (PMCC Panel from main Transformers)
ii 1R X 3C X 35 SQ.MM AL XLPE (For all outgoing Motor feeders ,Transformer & Lot 1.00 YES YES
VFD)
B HT Termination Kits
Supplying, erecting, testing and commissioning of Heat shrinkable termination kits for
termination of following cables
i 3C X 120 SQMM, 6.6 kV (UE), AL Conductor, XLPE Cable Nos. 4.00 YES YES
ii 3C X 35 SQMM, 6.6 kV (UE), AL Conductor, XLPE Cable Nos. 38.00 YES YES
11 LT Power and Control Cables
Designing, Preparing cable schedule, Supplying, laying, terminating on both ends by
providing cable glands and lugs of required sizes, testing and commissioning of 1.1 kV
grade LT power and control cables for puming station Lot 1.00 YES YES

12 Cable Trays
a) Designing, Preparing Cable tray layout, Supplying and erecting at site Galvanised,
ladder and perforated type cable trays along with cable tray supports, for laying power
and control cables from Switchyard to Switchgear room, inside Switchgear room, from
Lot 1.00 YES YES
Switchgear room to Pump house and inside Pump House

b) Providing, installing at site of work the Chequred plates to cover trenches and cable tray
supports with angles and channels etc. Lot 1.00 YES YES

13 Earthing and Lightning protection


Designing, Preparing layouts, Supplying and erecting at site Earthing and Lightning
protection materials including Earth grid and earth pits, etc. complete as per relavent IS / Lot 1.00 YES YES
IEEE / IEC standards
i Earth grid for Pump house and Switchgear room of required size
ii Earth strip for Equipment earthing of required size
iii Earth strip for Lightning protection of required size
iv Pipe Type Treated Earth Pits
v Rod type Earth pits
vi Lightning protection Test Links
14 Illumination System
Designing, Preparing Lighting layouts, Supplying, erecting, testing and commissioning
of Indoor and Periphery Lighting system for Pumping station, Switchgear room and
aliged buildings including LED type lighting fixtures with lamp, Conduits for wiring,
wiring, Lightin DBs, Switchboadrs, etc. Lux levels should be as per relevant IS / IEEE / Lot 1.00 YES YES
IEC standards

15 Supplying mandatory spares, required tools, tackles etc Lot 1.00 YES YES

Notes :
1. If any item / items not listed above, but required to complete the job, will be in the scope of Contractor.

You might also like