You are on page 1of 22

technical data

air conditioning systems


Slim concealed ceiling unit

FXDQ-PVE - FXDQ-NAVE
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

TABLE OF CONTENTS
FXDQ-PVE - FXDQ-NAVE

1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 Safety device settings ............................................. 4

3 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Cooling capacity tables .............................................. 6
Heating capacity tables .............................................. 8

5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 10


Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

6 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

7 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

9 Fan characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

• VRV Systems • Indoor Units 1


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

1 Specifications

at s e im- cne nUtE o sV CrPy oS- moQ idDV nXlR FVIS


1-1 TECHNICAL SPECIFICATIONS FXDQ20PVE FXDQ25PVE FXDQ32PVE FXDQ40NAVE FXDQ50NAVE FXDQ63NAVE
Nominal Cooling kW 2.20 2.80 3.60 4.50 5.60 7.10
Capacity Heating kW 2.50 3.20 4.00 5.00 6.30 8.00
Power input Cooling kW 0.086 0.086 0.089 0.160 0.165 0.181
(Nominal) Heating kW 0.067 0.067 0.070 0.147 0.152 0.168
1 Casing Material Galvanised steel plate
Dimensions Unit Height mm 200 200 200 200 200 200
Width mm 700 700 700 900 900 1100
Depth mm 620 620 620 620 620 620
Weight Unit kg 23.0 23.0 23.0 27.0 28.0 31.0
Heat Dimensions Nr of Rows 2 2 3 3 3 3
Exchanger Fin Pitch mm 1.50 1.50 1.50 1.50 1.50 1.50
Face m² 0.126 0.126 0.126 0.176 0.176 0.227
Area
Nr of Stages 12 12 12 12 12 12
Fin Fin type Cross fin coil
Fan Type Sirocco fan
Quantity 1 1 1 1 1 1
Air Flow Rate Cooling High m³/min 8.0 8.0 8.0 10.50 12.50 16.50
Low m³/min 6.4 6.4 6.4 8.50 10.00 13.00
Fan External static High Pa 30 30 30 44 44 44
pressure Standard Pa 10 10 10 15 15 15
Motor Output W 62 62 62 62 130 130
(high)
Drive Direct drive
Refrigerant Name R-410A
Cooling Sound High dBA 33.0 33.0 33.0 34.0 35.0 36.0
Pressure Low dBA 29.0 29.0 29.0 30.0 31.0 32.0
Piping Liquid (OD) Type Flare connection
connections Diameter mm 6.4 6.4 6.4 6.4 6.4 9.5
Gas Type Flare connection
Diameter mm 12.7 12.7 12.7 12.7 12.7 15.9
Drain Diameter mm VP20 (I.D. 20/O.D. 26)
Air Filter Removable/washable/Mildew proof
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices Fuse
Fan motor thermal protector
Standard Standard Accessories Installation and operation manual
Accessories Drain hose
Sealing Pads
Clamps
Washer
Insulation for fitting
Clamp metal
Washer fixing plate
Screws for duct flanges
Air filter
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7,5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure can be changed by the remote control.
The operation sound levels are conversion values in anechoic chamber. In practice, sound levels tend to be higher
than the specified values due to ambient noise or reflection. When the suction place is changed to bottom suction,
sound level will increase by approximately 5dBA.

2 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

1 Specifications

1-2 ELECTRICAL SPECIFICATIONS


Power Supply Name
FXDQ20PVE FXDQ25PVE FXDQ32PVE
VE
FXDQ40NAVE FXDQ50NAVE FXDQ63NAVE 3
Phase 1 1 1 1 1 1
Frequency Hz 50 50 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps A 0.80 0.80 0.80 1.00 1.00 1.10 1
(MCA)
Maximum fuse amps (MFA) A 15 15 15 15.00 15.00 15.00
Full load amps (FLA) A 0.60 0.60 0.60 0.80 0.80 0.90
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA<= 4 x FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker

• VRV Systems • Indoor Units 3


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

2 Safety device settings

FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NA


PC board (A1P) fuse 250V 5A
Fan motor thermal protector OFF: 130 “ 5ƒC OFF
ON: 83 “ 15ƒC ON

4D043861F
2

4 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

3 Control systems

Individual control systems

FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NA


Wired remote control BRC1D52
Infrared remote control H/P BRC4C62
C/O BRC4C64
Simplifide remote control BRC2A51 3
Remote control for hotel use BRC3A61

Centralised control systems

FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NA


Central remote control DCS302CA51
Unified on/off control DCS301BA51
Schedule timer DST301BA51

Others

FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NA


Wiring adapter for electrical appendices (1) KRP2A53
Wiring adapter for electrical appendices (2) KRP4A54
Remote sensor KRCS01-1A
Installation box for adapter PCB KBP1BA101
Electrical box with earth terminal 2 blocks KJB212AA
3 blocks KJB311AA
Noise filter (for electromagnetic interface use only) KEK26-1A
External control adapter for outdoor unit (must be installed on indoor units) DTA104A53
4D045731C

• VRV Systems • Indoor Units 5


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

4 Capacity tables
4-1 Cooling capacity tables
FXDQ20,25,32P
TC: Total capacity;kW – SHC: Sensible capacity;kW
Indoor air temperature
Outdoor
Nominal 14.0WB 16.0WB 18.0WB 19.0WB 20.0WB 22.0WB 24.0WB
Unit size air temp.
capacity 20.0DB 23.0DB 26.0DB 27.0DB 28.0DB 30.0DB 32.0DB
ƒCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
4 20 2.2 10.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.9 2.0
12.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.9 2.0
14.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.8 1.9
16.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.8 1.9
18.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.7 1.9
20.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.7 1.9
21.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.7 1.9
23.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.6 1.9
25.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.6 1.8 2.6 1.9
27.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.8 2.6 1.9
29.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.8 2.5 1.8
31.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.7 2.5 1.8
33.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.7 2.5 1.8
35.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.7 2.4 1.8
37.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.3 1.9 2.3 1.7 2.4 1.8
39.0 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.2 1.9 2.3 1.6 2.3 1.8
25 2.8 10.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.4 2.2 3.7 2.3
12.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.4 2.2 3.6 2.2
14.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.4 2.2 3.6 2.2
16.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.4 2.2 3.5 2.2
18.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.4 2.2 3.5 2.2
20.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.4 2.2 3.4 2.2
21.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.4 2.2 3.4 2.2
23.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.3 2.2 3.4 2.1
25.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.3 2.2 3.3 2.1
27.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.2 2.2 3.3 2.1
29.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.2 2.1 3.2 2.1
31.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.1 2.1 3.2 2.1
33.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.1 2.1 3.1 2.1
35.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.2 3.0 2.1 3.1 2.0
37.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.0 3.0 2.0
39.0 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 2.9 2.1 2.9 2.0 3.0 2.0
32 3.6 10.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.3 2.8 4.7 2.9
12.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.3 2.8 4.7 2.9
14.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.3 2.8 4.6 2.8
16.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.3 2.8 4.6 2.8
18.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.3 2.8 4.5 2.8
20.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.3 2.8 4.4 2.8
21.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.3 2.8 4.4 2.7
23.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.2 2.8 4.3 2.7
25.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.2 2.7 4.3 2.7
27.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.1 2.7 4.2 2.7
29.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.1 2.7 4.2 2.6
31.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 4.0 2.6 4.1 2.6
33.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 3.9 2.6 4.0 2.6
35.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.8 2.7 3.9 2.6 4.0 2.5
37.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.7 2.6 3.8 2.6 3.9 2.5
39.0 2.4 2.0 2.9 2.3 3.4 2.4 3.6 2.6 3.7 2.6 3.8 2.5 3.8 2.5
ED39226A

6 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

4 Capacity tables
4-1 Cooling capacity tables
FXDQ40,50,63NA 3
TC: Total capacity;kW – SHC: Sensible capacity;kW
Indoor air temperature
Outdoor
Nominal 14.0WB 16.0WB 18.0WB 19.0WB 20.0WB 22.0WB 24.0WB
Unit size air temp.
capacity 20.0DB 23.0DB 26.0DB 27.0DB 28.0DB 30.0DB 32.0DB
ƒCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
40 4.5 10.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.4 3.3 5.9 3.5 4
12.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.4 3.3 5.8 3.5
14.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.4 3.3 5.8 3.5
16.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.4 3.3 5.7 3.5
18.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.4 3.3 5.6 3.4
20.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.4 3.3 5.5 3.4
21.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.4 3.3 5.5 3.4
23.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.3 3.3 5.4 3.3
25.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.2 3.3 5.3 3.3
27.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.2 3.2 5.3 3.3
29.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.1 3.2 5.2 3.3
31.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 5.0 3.2 5.1 3.2
33.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.8 3.2 4.9 3.2 5.0 3.2
35.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.7 3.2 4.9 3.1 5.0 3.2
37.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.7 3.2 4.8 3.1 4.9 3.1
39.0 3.0 2.5 3.6 2.8 4.2 3.3 4.5 3.3 4.6 3.2 4.7 3.1 4.8 3.1
50 5.6 10.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.7 4.2 7.4 4.1
12.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.7 4.2 7.3 4.1
14.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.7 4.2 7.2 4.1
16.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.7 4.2 7.1 4.0
18.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.7 4.2 7.0 4.0
20.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.7 4.2 6.9 4.0
21.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.7 4.2 6.8 4.0
23.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.6 4.2 6.7 3.9
25.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.5 4.1 6.6 3.9
27.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.4 4.1 6.6 3.9
29.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.3 4.0 6.5 3.8
31.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.2 4.0 6.4 3.8
33.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 6.0 4.0 6.1 4.0 6.3 3.8
35.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 5.9 4.0 6.0 3.9 6.2 3.7
37.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 5.8 4.0 5.9 3.9 6.1 3.7
39.0 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 5.7 3.9 5.8 3.9 6.0 3.7
63 7.1 10.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.5 5.1 9.3 5.7
12.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.5 5.1 9.2 5.6
14.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.5 5.1 9.1 5.5
16.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.5 5.1 9.0 5.4
18.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.5 5.1 8.8 5.4
20.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.5 5.1 8.7 5.3
21.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.5 5.1 8.7 5.3
23.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.4 5.1 8.5 5.2
25.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.3 5.0 8.4 5.1
27.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.1 5.0 8.3 5.1
29.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 8.0 4.9 8.2 5.0
31.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 7.9 4.9 8.1 4.9
33.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.6 4.9 7.8 4.8 7.9 4.9
35.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.5 4.8 7.7 4.8 7.8 4.8
37.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.4 4.8 7.5 4.7 7.7 4.8
39.0 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.2 4.7 7.4 4.7 7.6 4.7
ED39226A

• VRV Systems • Indoor Units 7


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

4 Capacity tables
4-2 Heating capacity tables
FXDQ20,25,32P

Outdoor Indoor air temperature ƒCDB


Unit Size Nominal capacity air temperature 16.0 18.0 20.0 21.0 22.0 24.0
ƒCDB ƒCWB kW kW kW kW kW kW
20 2.5 -19.8 -20.0 1.5 1.5 1.5 1.5 1.5 1.5
4 -18.8 -19.0 1.5 1.5 1.5 1.5 1.5 1.5
-16.7 -17.0 1.6 1.6 1.6 1.6 1.6 1.6
-14.7 -15.0 1.7 1.7 1.7 1.7 1.7 1.7
-12.6 -13.0 1.8 1.8 1.8 1.8 1.8 1.8
-10.5 -11.0 1.9 1.9 1.9 1.9 1.9 1.9
-9.5 -10.0 1.9 1.9 1.9 1.9 1.9 1.9
-8.5 -9.1 2.0 2.0 1.9 1.9 1.9 1.9
-7.0 -7.6 2.0 2.0 2.0 2.0 2.0 2.0
-5.0 -5.6 2.1 2.1 2.1 2.1 2.1 2.1
-3.0 -3.7 2.2 2.2 2.2 2.2 2.2 2.2
0.0 -0.7 2.3 2.3 2.3 2.3 2.3 2.2
3.0 2.2 2.5 2.5 2.4 2.4 2.3 2.2
5.0 4.1 2.5 2.5 2.5 2.4 2.3 2.2
7.0 6.0 2.6 2.6 2.5 2.4 2.3 2.2
9.0 7.9 2.7 2.7 2.5 2.4 2.3 2.2
11.0 9.8 2.8 2.7 2.5 2.4 2.3 2.2
13.0 11.8 2.8 2.7 2.5 2.4 2.3 2.2
15.0 13.7 2.8 2.7 2.5 2.4 2.3 2.2
25 3.2 -19.8 -20.0 1.9 1.9 1.9 1.9 1.9 1.9
-18.8 -19.0 1.9 1.9 1.9 1.9 1.9 1.9
-16.7 -17.0 2.1 2.1 2.0 2.0 2.0 2.0
-14.7 -15.0 2.2 2.2 2.2 2.2 2.2 2.1
-12.6 -13.0 2.3 2.3 2.3 2.3 2.3 2.3
-10.5 -11.0 2.4 2.4 2.4 2.4 2.4 2.4
-9.5 -10.0 2.5 2.4 2.4 2.4 2.4 2.4
-8.5 -9.1 2.5 2.5 2.5 2.5 2.5 2.5
-7.0 -7.6 2.6 2.6 2.6 2.6 2.6 2.6
-5.0 -5.6 2.7 2.7 2.7 2.7 2.7 2.7
-3.0 -3.7 2.8 2.8 2.8 2.8 2.8 2.8
0.0 -0.7 3.0 3.0 3.0 3.0 3.0 2.8
3.0 2.2 3.1 3.1 3.1 3.1 3.0 2.8
5.0 4.1 3.3 3.2 3.2 3.1 3.0 2.8
7.0 6.0 3.4 3.4 3.2 3.1 3.0 2.8
9.0 7.9 3.5 3.4 3.2 3.1 3.0 2.8
11.0 9.8 3.6 3.4 3.2 3.1 3.0 2.8
13.0 11.8 3.6 3.4 3.2 3.1 3.0 2.8
15.0 13.7 3.6 3.4 3.2 3.1 3.0 2.8
32 4.0 -19.8 -20.0 2.4 2.4 2.3 2.3 2.3 2.3
-18.8 -19.0 2.4 2.4 2.4 2.4 2.4 2.4
-16.7 -17.0 2.6 2.6 2.6 2.6 2.6 2.5
-14.7 -15.0 2.7 2.7 2.7 2.7 2.7 2.7
-12.6 -13.0 2.9 2.8 2.8 2.8 2.8 2.8
-10.5 -11.0 3.0 3.0 3.0 3.0 3.0 3.0
-9.5 -10.0 3.1 3.1 3.1 3.1 3.0 3.0
-8.5 -9.1 3.1 3.1 3.1 3.1 3.1 3.1
-7.0 -7.6 3.2 3.2 3.2 3.2 3.2 3.2
-5.0 -5.6 3.4 3.4 3.4 3.4 3.4 3.4
-3.0 -3.7 3.5 3.5 3.5 3.5 3.5 3.5
0.0 -0.7 3.7 3.7 3.7 3.7 3.7 3.5
3.0 2.2 3.9 3.9 3.9 3.9 3.7 3.5
5.0 4.1 4.1 4.1 4.0 3.9 3.7 3.5
7.0 6.0 4.2 4.2 4.0 3.9 3.7 3.5
9.0 7.9 4.3 4.3 4.0 3.9 3.7 3.5
11.0 9.8 4.5 4.3 4.0 3.9 3.7 3.5
13.0 11.8 4.5 4.3 4.0 3.9 3.7 3.5
15.0 13.7 4.5 4.3 4.0 3.9 3.7 3.5
ED39226A

8 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

4 Capacity tables
4-2 Heating capacity tables
FXDQ40,50,63NA 3
Outdoor Indoor air temperature ƒCDB
Unit Size Nominal capacity air temperature 16.0 18.0 20.0 21.0 22.0 24.0
ƒCDB ƒCWB kW kW kW kW kW kW
40 5.0 -19.8 -20.0 3.0 2.9 2.9 2.9 2.9 2.9
-18.8 -19.0 3.0 3.0 3.0 3.0 3.0 3.0 4
-16.7 -17.0 3.2 3.2 3.2 3.2 3.2 3.2
-14.7 -15.0 3.4 3.4 3.4 3.4 3.4 3.4
-12.6 -13.0 3.6 3.6 3.6 3.5 3.5 3.5
-10.5 -11.0 3.7 3.7 3.7 3.7 3.7 3.7
-9.5 -10.0 3.8 3.8 3.8 3.8 3.8 3.8
-8.5 -9.1 3.9 3.9 3.9 3.9 3.9 3.9
-7.0 -7.6 4.0 4.0 4.0 4.0 4.0 4.0
-5.0 -5.6 4.2 4.2 4.2 4.2 4.2 4.2
-3.0 -3.7 4.4 4.4 4.4 4.4 4.4 4.4
0.0 -0.7 4.7 4.6 4.6 4.6 4.6 4.4
3.0 2.2 4.9 4.9 4.9 4.8 4.7 4.4
5.0 4.1 5.1 5.1 5.0 4.8 4.7 4.4
7.0 6.0 5.2 5.2 5.0 4.8 4.7 4.4
9.0 7.9 5.4 5.3 5.0 4.8 4.7 4.4
11.0 9.8 5.6 5.3 5.0 4.8 4.7 4.4
13.0 11.8 5.6 5.3 5.0 4.8 4.7 4.4
15.0 13.7 5.6 5.3 5.0 4.8 4.7 4.4
50 6.3 -19.8 -20.0 3.7 3.7 3.7 3.7 3.7 3.7
-18.8 -19.0 3.8 3.8 3.8 3.8 3.8 3.8
-16.7 -17.0 4.1 4.0 4.0 4.0 4.0 4.0
-14.7 -15.0 4.3 4.3 4.3 4.2 4.2 4.2
-12.6 -13.0 4.5 4.5 4.5 4.5 4.5 4.5
-10.5 -11.0 4.7 4.7 4.7 4.7 4.7 4.7
-9.5 -10.0 4.8 4.8 4.8 4.8 4.8 4.8
-8.5 -9.1 4.9 4.9 4.9 4.9 4.9 4.9
-7.0 -7.6 5.1 5.1 5.1 5.1 5.1 5.1
-5.0 -5.6 5.3 5.3 5.3 5.3 5.3 5.3
-3.0 -3.7 5.5 5.5 5.5 5.5 5.5 5.5
0.0 -0.7 5.9 5.9 5.8 5.8 5.8 5.5
3.0 2.2 6.2 6.2 6.2 6.1 5.9 5.5
5.0 4.1 6.4 6.4 6.3 6.1 5.9 5.5
7.0 6.0 6.6 6.6 6.3 6.1 5.9 5.5
9.0 7.9 6.8 6.7 6.3 6.1 5.9 5.5
11.0 9.8 7.0 6.7 6.3 6.1 5.9 5.5
13.0 11.8 7.1 6.7 6.3 6.1 5.9 5.5
15.0 13.7 7.1 6.7 6.3 6.1 5.9 5.5
63 8.0 -19.8 -20.0 4.7 4.7 4.7 4.7 4.7 4.7
-18.8 -19.0 4.9 4.9 4.8 4.8 4.8 4.8
-16.7 -17.0 5.1 5.1 5.1 5.1 5.1 5.1
-14.7 -15.0 5.4 5.4 5.4 5.4 5.4 5.4
-12.6 -13.0 5.7 5.7 5.7 5.7 5.7 5.7
-10.5 -11.0 6.0 6.0 6.0 6.0 6.0 5.9
-9.5 -10.0 6.1 6.1 6.1 6.1 6.1 6.1
-8.5 -9.1 6.3 6.3 6.2 6.2 6.2 6.2
-7.0 -7.6 6.5 6.5 6.4 6.4 6.4 6.4
-5.0 -5.6 6.8 6.7 6.7 6.7 6.7 6.7
-3.0 -3.7 7.0 7.0 7.0 7.0 7.0 7.0
0.0 -0.7 7.5 7.4 7.4 7.4 7.4 7.0
3.0 2.2 7.9 7.8 7.8 7.7 7.5 7.0
5.0 4.1 8.1 8.1 8.0 7.7 7.5 7.0
7.0 6.0 8.4 8.4 8.0 7.7 7.5 7.0
9.0 7.9 8.7 8.5 8.0 7.7 7.5 7.0
11.0 9.8 8.9 8.5 8.0 7.7 7.5 7.0
13.0 11.8 9.0 8.5 8.0 7.7 7.5 7.0
15.0 13.7 9.0 8.5 8.0 7.7 7.5 7.0
ED39226A

• VRV Systems • Indoor Units 9


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

5 Dimensional drawing & centre of gravity


5-1 Dimensional drawing

FXDQ20,25,32P

300 or more 700 300 or more 620


(Service space of installation (Service space)
box for adaptor PCB)

300
20 or more
400 or more
(In case of
bottom suction)
5

(Suspension bolt pitch)

20 or more

240 or more
500
620

700
Ceiling


(All around) < Service space >

300
60
16 - Ø 4.7 hole
5 x P100 = 500
740
(Suspension bolt pitch) Allow view ⺑
Inspection door
(Ceiling opening)

Adjustable (0-600)
Suspension bolt 300 or less

550
4 - M8 ~ M10 680
660 130 63 16-M5 Holes
12.5

57.5

4 x P150 = 600
47
90

50
20
10
21

(All around)

170
100
200
170
153
80

100
160
180
50
23

30 280 140 5 x P100 = 500


14 - M4 Holes
(All around) 33 330 100 580
90 600
80 620
< In case of back-suction>

Nr Part name Description NOTES


1 Liquid pipe connection ø 6.4 (Flare connection)
2 Gas pipe connection ø 12.7 (Flare connection) 1 In case of back-suction, mount chamber cover to bottom side
200
180
160
100

3 Drain pipe connection VP20 (O.D. ø 26 / I.D. ø 20) of the unit.


4 Drain hose (Accessory) I.D. ø 25 (Outlet) In case of bottom-suction, mount chamber cover to back side
5 x P100 = 500 140
10
20
50

580 100 5 Control box


16 - M4 Holes
(All around) 600 90
6 Transmission wiring connection of the unit.
620 80
< In case of bottom-suction > 7 Power supply connection 2 Location of unit’s name plate: control box cover.
8 Suspension bracket 3 Mount the air filter at the suction side.
9 Inspection door (Select its colorimethod (gravity method) 50% or more).
10 Socket for drain
11 Protection for drain It can not be equipped with air filter (accessory) when
12 Air filter (Accessory) connecting duct to suction side.

3D049799A

FXDQ40,50NA

300 or more 900 300 or more 620


(Service space of (Service space)
installation box for
adaptor
300

50 or more
20 or more

PCB)
(Suspension bolt pitch)

20 or more

20 or more
620

500

900

Ceiling
A
(Service space)
(All around) 22 - Ø 4.7 hole
60

8 x P100 = 800
300

940
(Suspension bolt pitch)
Adjustable (0~600)

300 or less Allow view A


Suspension bolt
Inspection door
550

4 - M8 ~ M10 880
(Ceiling opening)
860 130 63 20-M5 Holes
12.5

57.5

4 x P150 = 600
21

90 90
47
90

50
20
10

(All around)
170
200
170
153

100

100
160
180
80

50
23

18 - M4 Holes 30 280 150 7 x P100 = 700


33 330 100 780
(All around)
90 800
80 820
(In case of back-suction)

20 - M5 Holes Nr Part name Description NOTES


(All around)
1 Liquid pipe connection port ø 6.4 Flare connection
2 Gas pipe connection port ø 12.7 Flare connection 1 In case of back-suction, mount chamber cover to bottom side
200
180
160
100

3 Drain pipe connection port IVP20 (O.D. ø 26 / I.D. ø 20) of the unit.
7 x P100 = 700 130 4 Drain hose (Accessory) I.D. ø 25 (Outlet)
10
20
50

780 100 In case of bottom-suction, mount chamber cover to back side


800 90 5 Control box
820
(In case of bottom-suction)
80
6 Transmission wiring connection of the unit.
7 Power supply connection 2 Location of unit’s name plate: control box cover.
8 Suspension bracket 3 Mount the air filter at the suction side.
9 Inspection door (Select its color (gravity method) 50% or more).
10 Socket for drain
11 Air filter (Accessory) It can not be equipped with air filter (accessory) when
connecting duct to suction side.

3D045494

10 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

5 Dimensional drawing & centre of gravity


5-1 Dimensional drawing

FXDQ63NA
3
300 or more 1100 300 or more
620
(Service space of (Service space)
installation box for
adaptor
PCB)

300
20 or more
50 or more

(Suspension bolt pitch)

20 or more

20 or more
500
620

900
Ceiling
A
(Service space)

60
(All around) 26 - Ø 4.7 hole
10 x P100 = 1000
1140

300
(Suspension bolt pitch)

Adjustable (0~600)
Suspension bolt 300 or less
4 - M8 ~ M10 Allow view A

550
1080 Inspection door
1060 130 63 20-M5 Holes (Ceiling opening)
12.5

57.5
21

47
6 x P150 = 900
90

50
20
10
(All around)
200
170
153

100

170

100
160
180
80

50
23

18 - M4 Holes 30 280 150 9 x P100 = 900


(All around) 33 330 100 980
90 1000
80 1020
(In case of back-suction)

20 - M5 Holes
(All around) Nr Part name Description NOTES
1 Liquid pipe connection port ø 6.4 Flare connection
200
180
160
100

2 Gas pipe connection port ø 12.7 Flare connection 1 In case of back-suction, mount chamber cover to bottom side
9 x P100 = 900 130 3 Drain pipe connection port VP20 (O.D. ø 26 / I.D. ø 20) of the unit.
10
20
50

980 100
1000 90 4 Drain hose (Accessory) I.D. ø 25 (Outlet) In case of bottom-suction, mount chamber cover to back side
1020 80
5 Control box
(In case of bottom-suction)
6 Transmission wiring connection of the unit.
7 Power supply connection 2 Location of unit’s name plate: control box cover.
8 Suspension bracket 3 Mount the air filter at the suction side.
9 Inspection door (Select its color (gravity method) 50% or more).
10 Socket for drain
11 Air filter (Accessory) It can not be equipped with air filter (accessory) when
connecting duct to suction side.

3D045496

• VRV Systems • Indoor Units 11


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

5 Dimensional drawing & centre of gravity


5-2 Centre of gravity

FXDQ20,25,32P

4D049300A

FXDQ40,50NA

4D043886B

12 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

5 Dimensional drawing & centre of gravity


5-2 Centre of gravity

FXDQ63NA
3

4D043887B

• VRV Systems • Indoor Units 13


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

6 Piping diagram

FXDQ20,25,32P - FXDQ40,50,63NA

Gas side
6
Liquid side

Electronic expansion valve

Filter Filter

Fan

Indoor heat exchanger

4D043864F

14 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

7 Wiring diagram
7-1 Wiring diagram

FXDQ20,25,32P - FXDQ40,50,63NA
3

Power supply Note 3


220-240V 220V Input from
~ ~ outside
50Hz 60Hz Transmission
wiring central
remote control
Note 1

Wired remote
control

Control box

A1P Printed circuit board T1R Transformer (220V/22V)


C1 Capacitor (M1F) V1TR Phase control circuit
F1U Fuse (F5A/250V) X1M Terminal block
HAP Light emitting diode (Service monitor-green) X2M Terminal block
KPR Magnetic relay (M1P) Y1E Electronic expansion valve
M1F Motor (Indoor fan) Z1C • Z2C Noise filter (Ferrity core)
M1P Motor (Drain pump) Wired remote control
Q1M Thermal protector (M1F embedded) T1T Thermistor (Air)
R1T Thermistor (Air) SS1 Selector switch (Main/Sub)
R2T Thermistor (Coil-1) Connector for optional parts
R3T Thermistor (Coil-2) X16A Connector (Adaptor for wiring)
S1L Float switch X18A Connector (Wiring adaptor for electrical appendices)

: Terminal COLORS : BLK : Black BLU : Blue


GRN : Green GRY : Grey
: Connector ORG : Orange PNK : Pink
PRP: Purple RED : Red
: Field wiring
WHT : White YLW : Yellow

NOTES

1 In case using central remote control, connect it to the unit in accordance with the attached installation manual
2 Remote control model varies according to the combination system, confirm engineering materials and catalogs, etc. before connecting.
3 When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control. In details, refer to the installation manual attached the unit.

3D045500C

• VRV Systems • Indoor Units 15


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

8 Sound data
8-1 Sound pressure spectrum

FXDQ20P 4D052164 FXDQ25P 4D052165

8
Ocatve band sound pressure level dB (0dB=0.0002µ bar)

Ocatve band sound pressure level dB (0dB=0.0002µ bar)


H H

L L
Approximate Approximate
treshold hearing for treshold hearing for
continuous noise continuous noise

Ocatve band center frequency (Hz) Ocatve band center frequency (Hz)

NOTES NOTES

1 Over all (dB): Scale Air flow rate 1 Over all (dB): Scale Air flow rate
(B, G, N is already rectified) Hi Low (B, G, N is already rectified) Hi Low
A 33 29 A 33 29
2 Operating conditons: C 39 36 2 Operating conditons: C 39 36
• Power source: 220-240V 50Hz / 220V 60Hz • Power source: 220-240V 50Hz / 220V 60Hz
• Cooling: Return air temperature: 27ƒC DB, 19ƒC WB; Outdoor temperature: 35ƒC DB, 24ƒC WD • Cooling: Return air temperature: 27ƒC DB, 19ƒC WB; Outdoor temperature: 35ƒC DB, 24ƒC WD
• Heating: Return air temperature: 20ƒC DB, 15ƒC WB; Outdoor temperature: 7ƒC DB, 6ƒC WB • Heating: Return air temperature: 20ƒC DB, 15ƒC WB; Outdoor temperature: 7ƒC DB, 6ƒC WB
3 Measuring place: Anechoic chamber 3 Measuring place: Anechoic chamber
4 Location of microphone 2m 1m 4 Location of microphone 2m 1m

Discharge Duct Duct Suction Discharge Duct Duct Suction

1.5 m
1.5 m

Microphone Microphone
5 The operating condition is external static pressure 10Pa. Operation noise differs with operation and ambient 5 The operating condition is external static pressure 10Pa. Operation noise differs with operation and ambient
conditions. conditions.

FXDQ32P 4D052166 FXDQ40NA 4D046284


Ocatve band sound pressure level dB (0dB=0.0002µ bar)
Ocatve band sound pressure level dB (0dB=0.0002µ bar)

H H

L L
Approximate Approximate
treshold hearing for treshold hearing for
continuous noise continuous noise

Ocatve band center frequency (Hz) Ocatve band center frequency (Hz)

NOTES NOTES

1 Over all (dB): Scale Air flow rate 1 Over all (dB): Scale Air flow rate
(B, G, N is already rectified) Hi Low Hi Low
A 33 29 A 34 30
2 Operating conditons: C 39 36 2 Operating conditons:
• Power source: 220-240V 50Hz / 220V 60Hz • Power source: 220-240V 50Hz / 220V 60Hz
• Cooling: Return air temperature: 27ƒC DB, 19ƒC WB; Outdoor temperature: 35ƒC DB, 24ƒC WD • Cooling: Return air temperature: 27ƒC DB, 19ƒC WB; Outdoor temperature: 35ƒC DB, 24ƒC WB
• Heating: Return air temperature: 20ƒC DB, 15ƒC WB; Outdoor temperature: 7ƒC DB, 6ƒC WB • Heating: Return air temperature: 20ƒC DB, 15ƒC WB; Outdoor temperature: 7ƒC DB, 6ƒC WB
3 Measuring place: Anechoic chamber 3 Measuring place: Anechoic chamber
4 Location of microphone 2m 1m 4 Location of microphone 2m 1m

Discharge Duct Duct Suction Discharge Duct Duct Suction


1.5 m

1.5 m

Microphone Microphone
5 The operating condition is external static pressure 10Pa. Operation noise differs with operation and ambient 5 The operating condition is external static pressure 15Pa. Operation noise differs with operation and ambient
conditions. conditions.

16 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

8 Sound data
8-1 Sound pressure spectrum
FXDQ50NA 4D046285 FXDQ63NA 4D046286
3

Ocatve band sound pressure level dB (0dB=0.0002µ bar)


Ocatve band sound pressure level dB (0dB=0.0002µ bar)

H H

L L
Approximate Approximate
treshold hearing for treshold hearing for
continuous noise continuous noise

Ocatve band center frequency (Hz) Ocatve band center frequency (Hz)

NOTES NOTES

1 Over all (dB): Scale Air flow rate 1 Over all (dB): Scale Air flow rate
Hi Low Hi Low
A 35 31 A 36 32
2 Operating conditons: 2 Operating conditons:
• Power source: 220-240V 50Hz / 220V 60Hz • Power source: 220-240V 50Hz / 220V 60Hz
• Cooling: Return air temperature: 27ƒC DB, 19ƒC WB; Outdoor temperature: 35ƒC DB, 24ƒC WB • Cooling: Return air temperature: 27ƒC DB, 19ƒC WB; Outdoor temperature: 35ƒC DB, 24ƒC WB
• Heating: Return air temperature: 20ƒC DB, 15ƒC WB; Outdoor temperature: 7ƒC DB, 6ƒC WB • Heating: Return air temperature: 20ƒC DB, 15ƒC WB; Outdoor temperature: 7ƒC DB, 6ƒC WB
3 Measuring place: Anechoic chamber 3 Measuring place: Anechoic chamber
4 Location of microphone 2m 1m 4 Location of microphone 2m 1m

Discharge Duct Duct Suction Discharge Duct Duct Suction


1.5 m

1.5 m

Microphone Microphone
5 The operating condition is external static pressure 15Pa. Operation noise differs with operation and ambient 5 The operating condition is external static pressure 15Pa. Operation noise differs with operation and ambient
conditions. conditions.

• VRV Systems • Indoor Units 17


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

9 Fan characteristics

FXDQ20,25P 3D052156 FXDQ32P 3D052157

(mmH2O) (Pa) (mmH2O) (mmH2O) (Pa) (mmH2O)


6 60 6 6 60 6
9
5 50 5 5 50 5

40 40

External static pressure


4 High 4 4 High 4
l
rna

l
rna
(high ESP) (high ESP)
SP) ure xte

SP) ure xte


h E ress of e

h E ress of e
External static pressure

(hig atic p limit

(hig atic p limit


st pper

st pper
U

U
3 30 Low 3 3 30 Low 3
(high ESP) (high ESP)

al
al tern
2 20 al of ex
tern 2 2 20 it o
f ex 2
xtern r limit r lim ressure P) al
of e Lowe c pressure p e of ext
ern
mit stati h ESP) Up atic p rd ES r limit
er li ssure st tanda Lowe c pressure
Upp tic pre ESP) (hig
sta andardHigh (s
High stati h ESP)
(st (hig
(standard ESP) (standard ESP)
1 10 1 1 10 1
Low Low
(standard ESP) (standard ESP)
(Pa) (Pa)
(mmH2O) 6 7 8 9 (mmH2O) 6 7 8 9
Air flow rate (m3/min) (mmH2O) (mmH2O)
Air flow rate (m3/min)

NOTES NOTES

1 The remote control can be used to switch between “high” and 1 The remote control can be used to switch between “high” and
“low”. “low”.
2 The air flow is set to “standard” before leaving the factory. 2 The air flow is set to “standard” before leaving the factory.
It is possible to switch between “standard ESP” and “high ESP” by It is possible to switch between “standard ESP” and “high ESP” by
the remote control. the remote control.

FXDQ40NA 3D046299 FXDQ50NA 3D046300

(mmH2O) (Pa) (mmH2O) (mmH2O) (Pa) (mmH2O)


60 7 70 7
6 6

6 60 6
5 50 5
ESP) ure rnal
(hightic press it of exte

High
(high ESP)
al
sta per lim

(hightic pressu of extern

5 50 5
Up

High
40
ESP) re
External static pressure

(high ESP)
External static pressure

sta per limit

4 4
Up

Low
(high ESP)
4 40 High
4
(standard ESP)
3 30 3
High
(standard ESP)
30 rnal
3 of e
xte 3
mit e
al er li ssur
a l extern Lowatic preSP)
tern it of
l
a

20 st igh E
ern

2 f ex er lim sure 2
rd sure ext

(h
it o Low tic presP)
lim ssure )
nda res of
(sta tatic p r limit

per ic pre rd ESP sta h ES 2 20 2


)
ESP

p (hig
s ppe

U tat da
U

s tan
(s
Low
1 10 nal 1 (high ESP)
it of exter
Lower limessure
1 10 1
external
static pr ESP) Lower limit ofre
Low (standard static pressu )
(standard ESP) Low (standard ESP
(standard ESP)
(Pa) (Pa)
(mmH2O) 7 8 9 10 11 12 13 (mmH2O) (mmH2O) 8 9 10 11 12 13 14 15 (mmH2O)
Air flow rate (m3/min) Air flow rate (m3/min)

NOTES NOTES

1 The remote control can be used to switch between “high” and 1 The remote control can be used to switch between “high” and
“low”. “low”.
2 The air flow is set to “standard” before leaving the factory. 2 The air flow is set to “standard” before leaving the factory.
It is possible to switch between “standard ESP” and “high ESP” via It is possible to switch between “standard ESP” and “high ESP” via
the remote control. the remote control.

18 • VRV Systems • Indoor Units


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

9 Fan characteristics

FXDQ63NA 3D046301
3
(mmH2O) (Pa) (mmH2O)
7 70 7

60
9
6 6

5 50 5
rnal

High
h ES ssure exte
External static pressure

(high ESP)
(hig tic pre mit of
sta per li
P)
Up

4 40 4

3 30 High 3
(standard ESP) al
tern
of ex
r limit re
Lowetic pressu
rnal sta h ESP)
2 20 exte (hig 2
it of
p e r limressure P) Low
Up tic p rd ES (high ESP)
sta anda
(st

1 10 rnal
1
Lower limit of exte
Low static pressure
(standard ESP) (standard ESP)

(Pa)
(mmH2O) 11 12 13 14 15 16 17 18 19 (mmH2O)
Air flow rate (m3/min)

NOTES

1 The remote control can be used to switch between “high” and


“low”.
2 The air flow is set to “standard” before leaving the factory.
It is possible to switch between “standard ESP” and “high ESP” via
the remote control.

• VRV Systems • Indoor Units 19


• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE

9 Fan characteristics

20 • VRV Systems • Indoor Units


"The present publication is drawn up by way of ISO14001 assures an effective environmental Daikin units comply with the European
information only and does not constitute an offer management system in order to help protect regulations that guarantee the safety of
binding upon Daikin Europe N.V.. Daikin Europe N.V. human•health•and the environment from the potential the product.
has compiled the content of this publication to the impact of our activities, products and services and to
best of its knowledge. No express or implied warranty assist in maintaining and improving the quality of
is given for the completeness, accuracy, reliability or the•environment.
fitness for particular purpose of its content and the VRV products are not within the scope of
products and services presented therein. Specifications the Eurovent certification programme.
are subject to change without prior notice. Daikin
Europe N.V. explicitly rejects any liability for any direct Daikin Europe N.V. is approved by LRQA for its Quality
or indirect damage, In the broadest sense, arising from Management System in accordance with the ISO9001 Daikin equipment is designed for comfort
or related to the use and/or interpretation of this standard. ISO9001 pertains to quality assurance regarding applications. For use in other applications,
publication. All content is copyrighted by Daikin design, development, manufacturing as well as to services please contact your local Daikin
Europe N.V.." related to the product. representative.
Prepared in Belgium by Lannoo
EEDE06-2 • 03/2006

Zandvoordestraat 300
B-8400 Ostend - Belgium
www.daikineurope.com

ÉEEDE06-2~ËÍ

You might also like