You are on page 1of 6

Smart Cooling System for Milk Transportation in

Rural Areas
Tankiso A. Komako1, Ashleigh K. Townsend1, Immanuel N. Jiya2 and Rupert Gouws1
1
School of Electrical, Electronic and Computer Engineering, North West University
Potchefstroom 2520, South Africa
2
Department of Engineering and Science, University of Agder,
Grimstad 4879, Norway
ashleighktownsend2@gmail.com
2021 IEEE International IOT, Electronics and Mechatronics Conference (IEMTRONICS) | 978-1-6654-4067-7/21/$31.00 ©2021 IEEE | DOI: 10.1109/IEMTRONICS52119.2021.9422554

Abstract—In the dairy industry, road milk tankers intelligent milk tanks need to be developed in this case to
transport milk from one location to another. The milk inside lower the fuel costs and fuel related global warming effects,
the tanker needs to be kept between 3-5 ℃ to ensure that the associated with cooling of the milk tank [6].
quality of milk is always preserved. The tanker needs to be
kept running at all time with the case of sufficient energy Heat pumps are very efficient for heating and cooling
being continuously supplied to the cooling unit. The source of systems, they can significantly reduce the energy cost. They
energy normally used for this application is a typical keep energy cost as low as possible which is the most
generator which needs fuel to operate. This is expensive and important thing for any industry. The performance of the
is not environmentally friendly. To address this problem, heat pump can also be described by COP. This method of
generator as a source of energy needs to be replaced by solar cooling uses the refrigeration evaporator pipes or specially
energy to lower the costs associated with cooling of the tanker. designed flat pillow-shaped plates that are attached to the
In this research a small scale solar powered intelligent cooling bottom outer side of the tank containing milk. The heat of
system was developed. This system was designed to make use the milk is transferred through the walls of the tank to the
of thermoelectric cooler as a viable cooling unit and operating refrigerant. The refrigerant then absorbs the heat of the milk
it intelligently with a programmable logic controller. The inside the tank. The milk cooling process takes place inside
system was designed in a way that it can also display the the tank and normally an agitator is used to continuously
volume of milk inside the tanker and the system power mix the milk to prevent it from mixing at the bottom of the
consumption.
tank. Ice water cooling is another method used for the
Keywords—PLC, thermoelectric cooler, milk tanker, milk cooling of liquids in bulk tanks. The small compressors are
cooling, TECM normally used to build up a reserve of ‘coolth’ in the form
of ice over a long period of time. The ice is normally formed
I. INTRODUCTION on the copper pipes through which the refrigerant passes and
the ice is surrounded by the water close to freezing point [7].
Road milk tankers, transport raw milk from dairy farms
The water generally surrounds the outside of the tank while
to dairy processing factories where the milk is processed and
agitator is used to mix the milk inside the tank. The
utilized to produce dairy products like cheese, yoghurt etc.
[1]. To ensure that the quality of the milk from milked cows advantage of this method is that the ice can be made anytime
and not only during the time when content must be cooled.
is maintained during transportation, the temperature of the
This method is not as effective as a direct expansion method
milk is kept between 3-5 °C [2]. This implies that the milk
because the heat must be transferred several times (from ice,
tank, during transportation, needs to be kept running by
to water, to the milk). The other disadvantage of this method
ensuring that sufficient charge is provided to the cooling
is if the ice has melted, it must be made all over resulting in
unit of the tank. Road milk tank trucks make use of fuel-
based energy sources like DC generator to cool down and high electricity usage.
control the temperature of the milk during transportation. In this research a smart cooling system is proposed
The fuel-based energy machine is usually kept always based on the thermoelectric cooling module (TECM). A
running to provide sufficient charge to the cooling unit. The similar approach has been proposed in [8]. TECM, also
process to maintain the temperature of the milk is costly due known as Peltier cooler, because it is based on the Peltier
to the fuel being used as a source of energy [3]. effect is a semiconductor-based electronic component that
Rapid increase in price for fuel can have devastating functions by removing the heat from one side to the other
when a low DC power source (12 V) is applied. One side of
effects on the freight management companies, particularly,
the module is cooled while the opposite side is heated [9].
road milk trucks. The fuel price increase can also decrease
The working principle of the TECM is shown in [10]. The
the profit that dairy processing plants make [4]. The use of
heat flow out of the module has a significant impact on the
renewable energy sources could help reduce the high fuel
overall system performance. The larger temperature
costs associated with cooling of the milk tank. The petrol
difference that the module must work against, the smaller
cost associated with the cooling of the milk tank is high and
the quantity of the heat removed for the cold side. The
this causes milk trucking/logistics companies not to make
performance of TECM and any other cooling device can be
maximum profit due to petrol expenses. The fluctuation of
compared by determining their coefficient of performance
petrol price constantly has evolving effects on the milk price
(COP) [11]. The advantage that a TECM has over a
rates [5]. The petrol as a source of energy is not
compressor is that they have no moving parts and do not
environmentally free, and it contributes to global warming.
require the use of chlorofluorocarbons. This makes them
Environmentally friendly and renewable energy powered

978-1-6654-4067-7/21/$31.00 ©2021 IEEE

Authorized licensed use limited to: San Francisco State Univ. Downloaded on June 17,2021 at 02:21:23 UTC from IEEE Xplore. Restrictions apply.
perfect for application since they are environmentally The density of the water was 1 kg/L, its heat capacity
friendly [12]. was 4.2 KJ/(kg*K). The heat load capacity of 50 L of water
is: 661.1 W. Considering the safety factor of 20%, cooling
II. PROPOSED DESIGN capacity of 50 L of water/milk is: 1.2 *661.1 = 793.3 W.
Fig. 1 shows the overview and operational analysis of The TECMs chosen, must be able to pump this amount of
the proposed system which describes the actions that the energy to cool 50 L of milk to 4 °C within the estimated time
end-user will have to perform in order to operate and of 3 hours.
monitor the system. Table I, shows the heat load for different levels of water.
The end user will at first, must switch the system on and It is evident that the heat load doubles whenever the quantity
check the alarm indications - whether all the components of of the milk doubles. The heat loads calculated using
the system are connected and functional. If the alarm system Equation (1) is only an estimate and something to work on
indicates certain components of the system are disconnected regarding choosing the right TECM for the research. The
or malfunctioning, the end user will have to replace or liquid cooled TECM (Laird Technologies LA-115-24-02-
connect them to the system and monitor the alarm system 0710) that was used is shown in Fig. 2.
again to verify that they all connected. When the alarm This module has the voltage rating of 24 V, current
system indicates positive results, the end user will have to rating of 5.8 A and power rating of 139 W. This Single
operate the controller with the aim to check/ monitor the Assembly, from our heat load capacity calculation of the
temperature and the level of the milk. The end user will also water/milk, would be able to cool 8 L of milk/water to a
monitor the power being consumed by the system. After the temperature of 4 °C within the period of 3 hours.
process of operating the system, the end-user will then have Approximately 7 of these TECM assemblies will be able to
to deliver the cooled milk inside the tanker to respective cool 50 L of water/milk. These approximations are only
dairy processing plants. The control unit will have the theoretical, and they do not account for the shape of the
buttons and screen through which the end-user will operate tanker and all other factors which might affect cooling
to view the status (level and temperature) of the milk inside process of the tanker.
the tanker.
Simulation was done later in SolidWorks® to estimate
The TECM from laird technology/TE technology Inc., the cooling capacity that is needed for 50 L of milk.
usually comes with heat sink and fan already assembled, Simulation results provided more accurate approximations
depending on the application for which they are needed. The because in this case other factors which can influence the
cooling capacity of the thermoelectric cooling system is cooling process were considered. The eTape liquid level
dependent on the operating temperature of the content sensor from the Milone Technologies Inc was selected for
desired for cooling, quantity of thermoelectric modules this research. This sensor output was used by the controller
used, the type of thermoelectric module used and the applied to calculate/determine the actual capacity of milk inside the
power. The Marlow guide [13], will be used in this case to tanker in L. The controller also used eTape results to
select the applicable TECM which will be compatible for determine the temperature sensors that must be activated
the research. Firstly, the heat load capacity of the milk needs and considered to calculate and ensure that accurate
to be determined to select the applicable TECM which will temperature results of the milk are displayed. eTape was
be able to provide cooling capabilities. As such, the selected placed in a vertical position inside the tanker and was in
TECM must be able to handle the temperature difference of contact with the liquid. The eTape used the radius/diameter
34 °C. The cooling capacity of the milk, in this case, is measurement of the tanker which was then used altogether
determined to select the right TECM for the application. with the tanker dimensions to determine and display the
Equation (1) can be used to estimate the heat load/capacity liters of the liquid inside the tanker.
of liquids [14].
QC = mC T t = VC T (1) TABLE I. HEAT LOADS FOR DIFFERENT QUANTITIES OF WATER
Liters (L) Qc heat load (W)
Where, 𝑚 is cooled substance mass (kg), 𝐶 is cooled
1.0 15.86
substance specific heat capacity (J/(kgK)), Δ𝑇 is cooling
temperature difference (K), 𝜌 is cooled substance density 3.0 47.80
(kg/L), 𝑉 is Volume of the cooled substance (dm3) and Δ𝑡 is 5.0 79.33
cooling time (s). Although our research was based on milk 10 159.67
cooling, water was used as a viable substance to cool. 20.0 317.33
30.0 476.00
40.0 634.67
Connect/replace
the components
unsuccessfully View the
50.0 793.33
connected/damag temperature
ed and level of
milk inside the
tank

Switch the Check Operate Deliver the


system ON alarm control unit milk
indications

View power
consumption
information

Fig. 1. Operational flow diagram of proposed system. Fig. 2.Utilized liquid cooled TECM.

Authorized licensed use limited to: San Francisco State Univ. Downloaded on June 17,2021 at 02:21:23 UTC from IEEE Xplore. Restrictions apply.
A thermocouple was selected as the temperature sensor Start
to be used for the research. Three thermocouples were
placed at different levels inside the tanker and their output
was connected to the controller. The controller was
programmed to only display the average temperature sensed Input solar power
measurements (P)

by the thermocouples in contact with the liquid. One


thermocouple was used to sense the temperature No

surrounding the tanker. Four thermocouples were needed Use battery No


Solar power
sufficient?
Yes
Use so lar energy
directly

for this for the research. The thermocouple sensor had the
Yes

requirement of being able to measure the minimum


Solar power st ill
temperature of -5 °C and maximum of 40 °C, as the available?

temperature ranges of the liquid sensed were within this


range. The controller also used the imbalance of 10% Yes
Battery fully Charge battery
No
charged?

(within the sensors placed inside the tanker) to activate the


mixer to ensure that temperature of the milk was distributed Fig. 3. Implemented control flow diagram.
and accurately displayed. Type K thermocouple sensor from When the measured liquid level was between the
RS-pro was used. This industrial manufactured sensor has a minimum level and the median level (L2), only the first
temperature range of -50 to +400 °C [54], which was viable thermocouple (T1) measurement was considered. T1 and T2
for the research. were considered when the water level was between L2 and
The alarm system for the research consisted of light L3 (maximum level).
emitting diodes (LEDs) which indicated the status of the T3 together with T1 and T2 were considered when the
system components such as photovoltaic (PV) (1st Power liquid level was above L3. The average temperature (Tavg)
Supply), the battery (2nd power supply) and the state of the sensed by the thermocouples, was calculated together with
mixing unit. The green LED was used for indicating the their temperature deviation (Tdev). When the average
connection of the PV panel to the system, yellow LED was temperature of the liquid was greater than 4 °C, the cooling
used for indicating the presence of the battery in the system units continued to be in activation state until the average
and lastly the blue LED and red LEDs were used for temperature was less than 4 °C. The mixer was activated
indicating the status of the mixing unit. The blue LED was when the temperature deviation was greater than 10% and
activated when the mixing unit was in operation and the red deactivated when the temperature deviation was less than
LED was used to indicate the off state of the mixing unit. 10%.
The operator (driver) was able to view the status of the
components and able to make informed decisions thereafter. The energy management control flow (shown in Fig. 4)
The alarm system also indicated whether the control system was implemented on the PLC controller. Table II
was supplied through the PV or the battery and this was summarizes the abbreviations used in Fig. 4.
indicated by means of green and yellow LEDs, respectively. Start

This controller was used to implement the temperature No


control unit and energy management unit of the system. The END

PLC read the information, gathered through the sensors Yes


Measure liquid No

discussed, and took control steps to meet the specifications


System off? level (L)

of the research, such as maintaining temperature of the L > L 1? No


TECM
activated?
Yes
Deactivate
TECM

liquid between 3-4 °C. In the temperature control unit, the


Yes
TECM Activate
No TECM
PLC used the temperature sensors in contact with the fluid
activated?
Deactivate No Yes
Mixer Yes

and displayed their average sensed results. The PLC No Yes L > L 3? No L2< L < L3? No L1 < L < L2?

required level measurements from eTape to decide which Activate Mixer Yes Yes TECM
Mixer activated? Measure T1, Measure T1 No deactivated?
Yes Measure T1
T 2, T 3 & T2
temperature sensor to consider. In the energy management No
Mixer
No
Tdev > 10%? Yes
activated Yes Calculate
unit, the PLC decided on the energy source that needed to Tavg

be used depending on weather conditions. The PV was the Tavg > 4°C?

primary source while the battery was the secondary source. Fig. 4. Energy management control flow diagram.
The battery was utilized when there was insufficient energy
from the PV due to weather conditions. The PV charged the TABLE II. SUMMARY OF ABBREVIATIONS USED IN FIG.4
battery and supplied the system when there was sufficient
energy during sunny days. The PLC also managed the alarm Abbreviation Description
system of the research by sending the switching instructions L Measured liquid level
to the LEDs depending on the input information it received L1 Minimum liquid level of the tanker
from the system’s components. L2 Medium liquid level of the tanker
L3 Upper Liquid level of the tanker
Fig. 3 shows the suggested control flow diagram that T1 Temperature sensor placed at minimum liquid level
was implemented. In this flow diagram, the system first T2 Temperature sensor placed at medium liquid level
determines the amount of milk that is inside the tanker. The sensor
system uses the minimum level (L1) as the level at which the T3 Temperature sensor placed at the upper liquid level
cooling occurs, as to avoid wasting energy during the time TECM Thermoelectric cooling unit
when the tanker was empty. TECM started to be activated Mixer Agitator
when the water level was above the minimum level. Tavg & Tdev Average temperature and temperature deviation

Authorized licensed use limited to: San Francisco State Univ. Downloaded on June 17,2021 at 02:21:23 UTC from IEEE Xplore. Restrictions apply.
In the flow diagram, it is seen that the energy of the PV The TECM was operated outside the tanker with copper
was first determined/measured and decided if it’s enough to coils placed inside, for direct contact with the milk/water.
power the system. This required both the voltage sensor and The purpose thereof, was to see how the temperature was
current sensor be implemented to determine and monitor the distributed within the milk upon the placement of the copper
power from the PV. During sunny days, the energy of the coil to the relevant place inside the tanker. Only one TECM
PV is likely to be enough to power the system and was available for the research and the SolidWorks®
simultaneously charge the battery. During the night or bad simulation was done to investigate the effect of this module
weather conditions, the energy from PV is likely insufficient inside the tanker. The minimum temperature of the provided
to power the system directly, hence a battery was needed as cooling module was -10 °C. Ethanol was chosen as the
a backup source. The power measurement from the PV circulating liquid which will flowed through the heat
allowed the controller to determine which power source to exchanger of the TECM. In the simulation, the temperature
use between the PV and the battery. The voltage sensor of the ethanol entering the copper coil was set at -10 °C. Fig.
(voltage divider) was also used to sense the voltage capacity 5 shows the temperature results of our analysis. It was
of the battery to determine or monitor its energy capability. considered that the coils were placed at the minimum level
This sensor was connected to the analog input of the PLC to of the tanker to allow cooling when the liquid level is at that
allow the implementation of flow diagram shown in Fig. 3. point.
Since there three sensors were used to implement the energy
management unit, three analog inputs of the PLC were used The surrounding temperature of the tanker was set at 25
°C since this was the temperature regarded as room
for this purpose.
temperature and the water was used as a liquid to be cooled
For current sensing measurements, the shunt resistor, with an initial temperature of 38 °C. In Fig. 5, the copper coil
together with the current sense amplifier, was used to take only managed to cool the liquid near it and as such, the
the current measurements from the PV. The power of the agitator was needed to mix the liquid and ensure that the
PV was then determined from the current and voltage temperature of the liquid was well distributed. This setup of
measurement of the PV. This power calculation was then the tanker required that the agitator be placed in the parallel
used to determine if the PV is able to supply sufficient position to the tanker to allow the movement of the cooled
power or not. Fig. 5-Fig. 7 shows the temperature analysis of liquid to mix with the hot liquid as seen in Fig. 5(a).
the tanker.
The thermocouples for this scenario, had to be placed at
different levels of the tanker. One thermocouple was placed
at the bottom level of tanker, the second thermocouple was
placed in the middle of the tanker and the third
thermocouple in the top level of the tanker. The fourth
thermocouple sensor was placed outside of the tanker to
read the outside temperature. This setup in Fig. 5, was
implemented as there was only one available TECM. The
tests on the tanker were conducted to evaluate the cooling
capability of this cooling module.
Fig. 6 shows the thermal analysis of the tanker when there
Fig. 5. Temperature analysis with one TECM placed at lowest level in is multiple liquid cooled thermoelectric cooling modules.
tanker. The position placement of three TECMs was investigated in
this regard, to determine how the liquid was cooled in these
scenarios. In Fig. 6, the tanker was connected to three
TECMs whose coils are placed perpendicular to each other.
This set up of coil placements is not proper since the
temperature at the top is not cooled. The liquid at the bottom
of the tank will also freeze due to high concentration of
cooling happening at the bottom. Hence the choice of
placing the cooling coils in this manner is not proper. In Fig.
7, the three TECM copper coils are placed in a parallel in
accordance with the levels of the tank. The cooling in this
Fig. 6. Temperature analysis with three TECMs placed along sides of the case happens much better that in Fig. 6. The temperature of
tanker. the water in Fig. 7 is mostly seen to be around 3-7 °C. This
proves the setup in Fig. 7 is better than the setup in Fig. 6.
III. RESULTS
The subsystems discussed above were all integrated to
realize the intelligent solar powered TECM road milk tanker
shown in Fig. 8. This figure shows the setup of the research
where 8.91 L of water was inside the tanker as indicate on
the LCD screen. The LCD screen also displays power
consumption. The PLC recorded the temperature to be 7℃
a) 2 TECMs b) 3 TECMs inside the tanker and the surrounding temperature was 18
Fig. 7. Temperature analysis with TECMs placed parallel to bottom of ℃.
tanker.

Authorized licensed use limited to: San Francisco State Univ. Downloaded on June 17,2021 at 02:21:23 UTC from IEEE Xplore. Restrictions apply.
The cooling test results from Fig. 9 indicate linearity
hence the trend line was drawn. With these results, we were
able to estimate after how long the system will be able to
cool the liquid to the temperature of 4℃. These results
shows us that the cooling unit (TECM) had insufficient
cooling capacity for this tanker. The TECM that was used
in this research has a cooling capacity of 113 W which is
insufficient to ensure that the temperature of the liquid is
cooled and maintained up to the temperature of 4℃ within
the period of 3 hours. The heat load for specific amounts of
water were calculated and estimated in Table I. From this
table, this cooling unit was to cool 7 L content to 4 °C within
3 hours. Because of the surrounding factors which dissipate
Fig. 8. Integrated intelligent solar powered TECM road milk tanker. heat, like the electric fuel pump, this was not realized. From
Fig. 9, it is safe to conclude that two of these TECMs should
Two tests were performed in order to evaluate the be able to cool down 7 L of water from initial temperature
system performance and determine the efficiency of the of 38 ℃ to the final temperature of 4 ℃ within 3 hours.
system. The results were used in order to draw a conclusion
on how, on the big scale, the system performed. The ability
of TECM as a cooling unit was evaluated and tested as to B. Test 2: Temperature control
predict how many TECMs were needed to ensure that the
system becomes more efficient in terms of cooling. The The objective of this test was to determine the ability of
ability of the tank to preserve and maintain the cooled the tanker to maintain the temperature of the liquid between
temperature will be discussed. The critical tests that were 3 and 5 ℃. The ice cubes were filled inside the tanker so
conducted were the cooling ability and the temperature that the temperature of water can initially be below 4 ℃. Ice
control. cubes were added to the 7 L of water that was tested for
cooling. The water capacity after the ice cubes were filled
A. Test 1: Cooling ability changed to an average water capacity of 9 L. The critical
sensor, which in this case is sensor number one, initially
This test determined the ability of the tanker to cool the
registered a temperature of 2 ℃ as can be seen in Fig. 10.
milk. Water was used as a viable liquid that was cooled and
tested even though the objective of this research was to The system was then off for a period of 40 minutes. The
design the tanker which will be able to cool the temperature system turned on when the temperature of 4 °C was
of the milk from 38℃ to 4 ℃ within a time period of 3 exceeded. This is indicated by the profile of current
hours to ensure that the quality of the milk is preserved. 7 measurements plotted in Fig. 10. The temperature of water
L and 21 L of water were externally heated up to a continued to rise even when the system cooling unit was
temperature of 38 ℃. 7 L of this hot water was filled inside activated. The temperature of 9 L of water continued to rise
the tanker first and the test was performed. 21 L of hot until it settled at 7 ℃ after 120 minutes. The temperature of
the liquid continued to be between 6 and 7 °C for the
water was filled secondly, and the cooling test was
remaining period of 1 hour. The behavior of current when
conducted. The temperature measurements of the critical
this happened is shown in Fig. 10. During the time when the
sensors were recorded and noted while the system was system was off, the temperature of liquid inside the tanker
being operative for 3 hours for both cases of 7 L and 21 L. changed from 2 ℃ to 4 ℃ within the space of 40 min.
Fig. 9 shows the cooling test results for both the cases. The
system managed to cool down 21 L of water from a
temperature of 33 ℃ to a temperature of 19℃ within the
period of 3 hours. On the other hand, the system only
managed to cool down the temperature of 7 L of water from
the temperature of 30 ℃ to the final temperature of 13 ℃.

Fig. 10. Results for temperature control test.

Fig. 9. Liquid cooling test results for 7 L and 21 L, repsectively.

Authorized licensed use limited to: San Francisco State Univ. Downloaded on June 17,2021 at 02:21:23 UTC from IEEE Xplore. Restrictions apply.
This result proves that the tanker was not efficient REFERENCES
enough to hold and maintain the temperature of the liquid [1] M. Frazer, K. Som, B. Anthony, B. T. Tek, and M. G. Sonnet,
for an extended time. This is not surprising since the tanker Technical and investment guidelines for milk cooling centres.
did not have insulation between the outside part of the Rome, Italy: FAO, 2016.
tanker interacting with the environment and the inside of the [2] T. Abebe and T. Markos, Hygienic milk processing: clean
tanker which interacts with the liquid. This means that environment, clean utensils | FAO. International Center for
Agriculture Research in the Dry Areas (ICARDA), 2009.
insulations needs to be applied to this tanker. The tanker can [3] S. Monteleone, M. Sampaio, and R. F. Maia, “A novel
store 50 L of milk, as such this required a cooling unit with deployment of smart Cold Chain system using 2G-RFID-Sys
minimum cooling capacity of approximately 800W temperature monitoring in medicine Cold Chain based on
according to Table I. Taking into account environmental Internet of Things,” in 2017 IEEE International Conference on
factors, it would be safe to use a cooling unit with cooling Service Operations and Logistics, and Informatics (SOLI), Sep.
2017, pp. 205–210, doi: 10.1109/SOLI.2017.8120995.
capacity of 1200 W. Using TECM as a cooling unit, 12 will [4] W. Jacobs, M. R. Hodkiewicz, and T. Bräunl, “A Cost-Benefit
be required. For an actual tank of 8000 L, the cooling unit Analysis of Electric Loaders to Reduce Diesel Emissions in
used shall require a cooling capacity of 192 kW. This will Underground Hard Rock Mines,” IEEE Trans. Ind. Appl., vol.
require 1920 TECMs. 51, no. 3, pp. 2565–2573, 2015, doi:
10.1109/TIA.2014.2372046.
[5] W. A. Bisschoff, I. N. Jiya, and R. Gouws, “Novel Intelligent
Energy Management System for Residential PV Systems in
IV. CONCLUSION Non-feed-in Tariff Countries,” Int. J. Appl. Eng. Res. ISSN
0973-4562, vol. 13, no. 10, pp. 8457–8466, 2018.
This research was based on designing and implementing [6] B. K. Bose, “Global Warming: Energy, Environmental
a small scale intelligent TECM road milk tanker. The Pollution, and the Impact of Power Electronics,” IEEE Ind.
proposal was drafted and a brief background about the Electron. Mag., vol. 4, no. 1, pp. 6–17, Mar. 2010, doi:
research was presented. The problem stated that an 10.1109/MIE.2010.935860.
intelligent solar powered road milk tanker needed to be [7] I. Saritas and M. Okay, “Design of portable medical cooler with
artificial intelligent control,” in International Conference on
developed to lower the cost associated with cooling of the challenges in IT, Engineering and Technology (ICCIET’2014),
milk. Research was compiled on available solutions which 2014, pp. 39–44, doi: 10.15242/IIE.E0714028.
can be used in order to implement the research. All the [8] R. Foster et al., “Direct Drive Photovoltaic Milk Chilling
critical subsystems like liquid measuring, power monitoring Experience in Kenya,” in 2017 IEEE 44th Photovoltaic
and temperature control of the research were integrated and Specialist Conference (PVSC), Jun. 2017, pp. 2014–2018, doi:
10.1109/PVSC.2017.8366541.
found to be working accordingly. Two types of tests were [9] N. Zabihi and R. Gouws, “Verifying the cooling capacity and
performed to determine the cooling ability of the tanker. It power consumption of thermoelectric cooling holders for
was found that the cooling of the tanker was not efficient as vaccine storage,” in 2015 International Conference on the
the temperature of 4 ℃ could not be reached by the Domestic Use of Energy (DUE), Mar. 2015, pp. 115–119, doi:
minimum capacity of the tanker in a period of 3 hours. It 10.1109/DUE.2015.7102970.
[10] Laird-Technologies, “LA PowerCool Series, LA-115-24-02
was decided that the cooling capacity of the TECM is not Thermoelectric Assembly,” 2010.
sufficient to realize the objectives of cooling the liquid to [11] H. Eilers, “Thermoelectric (TECM) Cooling Holder,” North
temperature below 4 ℃. The temperature control of the West University, Potchefstroom, 2012.
tanker was also not efficient due to the fact that the [12] W. Salah, S. Taib, and A. Al-Mofleh, “Development of TEC
temperature of 9 liters of water was not controlled at the System for Commercial Cooling Applications,” Mod. Appl. Sci.,
required set point for the period of 1 hour. It was suggested vol. 3, no. 4, p. p203, Mar. 2009, doi: 10.5539/mas.v3n4p203.
[13] H. Buitendach, I. N. Jiya, and R. Gouws, “Solar powered peltier
cooling units with sufficient cooling capacity be used cooling storage for vaccines in rural areas,” Indones. J. Electr.
instead. Comment was made regarding how many of these Eng. Comput. Sci., vol. 17, no. 1, pp. 36–46, 2020, doi:
TECMs were needed and what can be done to improve the 10.11591/ijeecs.v17.i1.pp36-46.
tanker. [14] J. Tsado, M. K. Mahmood, A. G. Raji, A. U. Usman, and I. N.
Jiya, “Solar Powered DC Refrigerator with a Monitoring and
Control System,” in 2018 IEEE PES/IAS PowerAfrica, Jun.
2018, pp. 591–594, doi: 10.1109/PowerAfrica.2018.8521158.

Authorized licensed use limited to: San Francisco State Univ. Downloaded on June 17,2021 at 02:21:23 UTC from IEEE Xplore. Restrictions apply.

You might also like