Professional Documents
Culture Documents
• Vacuum Pumps.
• Vacuum Breaker.
• Buffer Hoppers.
• Bag Filters.
• Switch Valves.
• Vacuum Conveying.
• D pumps.
Vacuum Pump Seal Water Valve: Valve will operate from start command of corresponding
vacuum pump when the pump selected for operation.
Buffer hopper / bag filter end vacuum line valve and Vac pump end vacuum line valve:
Valve will operate & align automatically as soon as that buffer hopper and corresponding
vacuum pump selected for operation.
Vacuum Breaker at vacuum pump end and at buffer hopper end:
For each vacuum conveying line one number vacuum breaker is at suction side of vacuum
pump and one number vacuum breaker at buffer hopper end.
Closing of Vacuum breaker: The vacuum breaker will be closed (under both “Auto” and
“Manual” operation) through’ actuation of “SYSTEM START” command for the conveying
stream connected with the said conveying path.
Close permissive conditions: All conditions listed below shall be satisfied:
1) Associated Vacuum conveying path is through.
2) Selected vacuum pump is running.
3) Vacuum level (VAC-LL) achieved in line.
Protection open conditions: Breaker will trip/open if any of the conditions listed below
occurs:
1) Activate system stop command.
2) Associated Vacuum Conveying Path is not through.
3) Operating Vacuum pump is tripped/OFF.
Auto close conditions:
1) System Start initiation from HMI.
BAG FILTER:
Fly Ash air mixture conveyed by each fly ash conveyor under vacuum system separates in
dry form in bag-filter, and gets stored temporarily in the buffer hopper directly below the bag
filter. There are four (04) sets of bag filter and buffer hoppers corresponding to four streams
of each unit. Every pass of dry collection is associated with one such bag filter assembly.
Each bag filter is fitted with Solenoid valves. Each solenoid will purge the air for 100 millisec
(approx.) and time gap between two solenoids shall be 10 sec. (approx.). Once all the
Solenoids have purged in sequence i.e. one cycle is completed, another cycle of purging will
start only after a time gap of 40 sec. (approx.).
The pulse jet cycle of the selected buffer hopper / bag filter will START with the selection of
corresponding bag filter / buffer hopper and the same shall stop automatically (after a pre-set
time) with actuation of “SYSTEM STOP”.
• Line Vacuum Permissive-330 mm Hg -Air Intake Valve Open. Air Intake Valve
Close when Line Vacuum -270 mm Hg.
Operation Sequences:
1. Branch header valve of first branch will open in auto. In manual mode the branch header
valve of selected branch will open. Fluidizing valve of corresponding branch will also open
with the open of header valve.
2. Vacuum Pump Starts & one ON delay Timer (5-10 Secs) Starts. On expiry of timer closes
the Vacuum Breakers of vacuum pump end and buffer hopper end. When line vacuum goes
up to 170mmHg VAC-P for around 30 secs it means Line Vacuum OK and system is ready to
take fly ash in line.
3. When vacuum level (VAC-P) reaches, ESP 1st field ash intake dome valve of selected first
Branch is opened.
4. Now fly ash is being conveyed from hopper through Fly ash line to the selected Buffer
Hopper.
5. Conveying from hopper will continue until line vacuum falls below VAC-L (115 mmHg)
and persists for a preset time (approx. 5 sec adjustable). This condition implies “HOPPER
EMPTY” status and respective ash intake valve will close & the same ,results vacuum build
up in vacuum line. A vacuum low preset timer also starts at the same time.System will recheck
again by opening MHV and vacuum fall below VAC-L.
6. If Vacuum low timer expires & Vacuum doesn’t reaches the permissive level (VAC-P) then
“Vacuum Low Alarm” will come.
7. When Vacuum reaches line running permissible level VAC-P (130mmHg) then Sequence
will jump to the next selected hopper of the branch and further sequencing will be same as in
case of Ist hopper.
8. After the fly ash hoppers of Ist branch are cleaned, the sequence will jump to next branch
and its branch header valve will open. The branch header valve of first branch will close with
the opening of branch header valve of next branch. In manual mode branch selection are to
be done manually and header valves opens based on branch selection.
9. Opening / closing of fluidizing air valves will be in correlation with branch header valves.
However, when no branch header valves are opened, this will be in timer mode.
10. If, required, at any point of time of ash evacuation through a particular hopper, the
sequence can be shifted to next selected hopper by pressing “ JOG PB” from screen. This will
close the ash intake valve of present hopper and shift the sequence to next selected hopper.
This PB is applicable for auto mode.
11. In auto mode - with the Actuation of “SEQUENCE STOP” push button the ash intake
valve of current hopper will close and sequence will retain at that hopper. Sequence will
resume from that hopper when sequence start is again pressed.
12. When SYSTEM STOP is pressed, purging of vacuum line starts for a preset time and them
the vacuum breakers opens and branch header valves closes to conclude that fly ash vacuum
system operation is over.
13. When line vacuum reaches to VAC-N (330mmHg) Air intake valve of the selected branch
will open. This will help in fast evacuation of ash and maintain the line vacuum with in limits.
Air intake valve closes when vacuum returns to 270mmHg.
14. If line vacuum keeps on rising and reaches VAC-H (340mmHg), comman VB will open
and when vacuum falls below (320 mm Hg) VB closes.
15. If vacuum level rises above a preset vacuum level VAC-HH (500mmHg) during the
process of evacuation of material through any hopper of selected branch, then this signifies
that Line is getting chocked and VB will open.
16. Shutdown Sequence / purge sequence:
All hopper selected in the system has been evacuated, then purge the line,after that system go
to shutdown mode.
• Vacuum breaker opens and the system goes to shutdown mode.
OPEARTION:
In case outlet dome valve & balance dome valve Seal pr. of one vessel are OK but any other
enabling conditions are not OK then the other Vessel can be started for feeding the material.
OPERATION CYCLES OF A D PUMP VESSEL
It divided in 4 operating groups:
i) System Selection / Start Up
ii) Transfer / Filling and Conveying Cycle
iii) Routine Shut down Mode
iv) Shut Down Mode
Prepared By Approved By
Prashant Chandankhede DP Patra
DGM(operation) AGM(operation)