Energy Efficiency Certificate

Drive efficiency according to IEC/EN 61800-9-2 (supersedes EN 50598-2)

Efficiency data for the Drive


Series : GD350A-055G/075P-4 Nominal current :115A
Nominal voltage : AC 3PH 380V Nominal apparent power :75.7kVA
Nominal power :55kW Nominal frequency :50Hz
Overload :Heavy Duty

Efficiency data for the Drive


Standby losses: 22W
Relative
Torque / %
955W 1116W 1059W
100 1.26% 1.47% 1.40%
91.02% 96.99% 98.33%

Losses
519W 672W 669W Relative losses
50 0.69% 0.89% 0.88% Drive Efficiency
89.96% 96.64% 98.09%

386W 540W 504W


25 0.51% 0.71% 0.67%
87.91% 95.90% 97.79%

0 10 50 90 Relative
Speed / %

Efficiency data for the Drive + motor (standard IE2 reference motor)

Relative
Torque / %
3320W 4196W 5943W
100 6.03% 7.62% 10.80%

Losses
50 1454W 2157W 3199W Relative losses
2.64% 3.92% 5.81%

25 991W 1695W
1.80% 3.08%

0 10 50 90
Relative
Speed / %