Digital Speed Controller

Instruction Manual
YTMC-6318V2

EUNTAY ELECTRIC CO., LTD


TEL: 886-2-8209817 FAX: 886-2-82090327

E-mail:inter-service@euntay.tw
http://www.euntay.tw

EUNTAY ELECTRIC CO., LTD. -1- Mar. 17, 2010


1. Operation Panel Explanation

(9) Speed Display

(2) High Limit Indication (10) Proportion Setting Value


(1) Operation Lamp (4) Abnormal State Lamp
(3) Low Limit Indication

(5) Setting & Input Key (8) Parameter Selection Key


(6) Value-decrease Key (7) Value-increase Key

2. Operation Setting

Press T S key, modifying After setting, pressing SET Key,


“proportion” setting, then the the “proportion” setting is
setting value will be flashing completed

Parameter Setting Method

Press SET P key at the Press SET Key, making Press T S Key, After setting, pressing SET
same time, going to “parameter” be flashing. modifying “parameter” Key, the “parameter” is
“parameter” setting content completed

Pressing T or P key if If there are no keys to


don’t modify, jumping to the press, the “parameter”
reserved parameter setting will be exited
automatically after 10 sec.

EUNTAY ELECTRIC CO., LTD. -2- Mar. 17, 2010


3. Parameters Table
Symbol Default Setting
(Communication Symbol Description Explanation
Address) Value Range
When “0200H” = 1, data will be
(0200H) EEPROM WRITE 0 0~255
written into EEPROM
(0202H) Ratio (in the panel, SV) 100.00% 0 ~ 500.00% Ratio (%, SV)
When the panel ratio (%) =
RA1 Proportion Gain of line 100.0, adjusting this
100.00% 0~500.00%
(0204H) speed input 1 parameter, which make the
ratio of line speed be 1:1
CENT The central point The central point could be set
setting of potential 0° -180° ~ +180° within the range (-180° ~
(0206H) meter +180°)
HI-1 Positive angle
“CI-1” integral start point
correction, the first +30° -180° ~ +180°
(0208H) (deceleration)
section
HI-2 Positive angle
“CI-2” integral start point
correction, the second +100° -180° ~ +180°
(020AH) (deceleration)
section
LO-1 Negative angle
“CI-1” integral start point
correction, the first -30° -180° ~ +180°
(020CH) (acceleration)
section
LO-2 Negative angle
“CI-2” integral start point
correction, the second -100° -180° ~ +180°
(020EH) (acceleration)
section
When potential meter’s
HIPO Positive angle relay feedback signal exceed
+150° 0 ~ +180°
(0210H) (High) active point positive angle, “HI” relay is
active
When potential meter’s
LOPO Positive angle relay feedback signal is lower than
-150° 0 ~ -180°
(0212H) (Low) active point positive angle, “LO” relay is
active
LBAS Basic correction of When line speed = 0, the
potential meter’s 20.0% 0 ~ 100.0% feedback value multiplied by
(0214H) feedback signal “LBAS” for correcting deviation
BIAS
Offset voltage setting 0V -5V ~ +5V The voltage of start point
(0216H)
The correction of
CP potential meter The compensation for the
feedback signal’s 30% 0 ~ 300% deviation of potential meter’s
(0218H) deviation for positive central point
angle
Exceeding angle of the first
CI-1 Positive angle
section, this constant will be
correctional integral of 300 0 ~ 1000
(021AH) used for ascending or
the first section
descending
Exceeding angle of the second
CI-2 Positive angle
section, this constant will be
correctional integral of 30 0 ~ 1000
(021CH) used for ascending or
the second section
descending

EUNTAY ELECTRIC CO., LTD. -3- Mar. 17, 2010


The correction of
- CP potential meter The compensation for the
feedback signal’s 30% 0 ~ 300% deviation of potential meter’s
(021EH) deviation for negative central point
angle
- CI-1 Exceeding angle of the first
Negative angle
section, this constant will be
(0220H) correctional integral of 300 0 ~ 1000
used for ascending or
the first section
descending
- CI-2 Exceeding angle of the second
Negative angle
(0222H) section, this constant will be
correctional integral of 30 0 ~ 1000
used for ascending or
the second section
descending

CI-R The limit of maximum slip


The maximum Slip 10.0V 0 ~ 10.0V (positive slip is same as
(0224H) negative slip)
0: OUT1
1: IN1
SRC 2: Angle of potential meter
The display source
0 0~5 3: Slip
(0226H) selection on PV
4: Diameter display
5: OUT1 (it doesn’t display
UART)

SPR The production speed is


Display ratio of OUT1 1.0 1.0 ~ 999.9 10V*SPR in 10V, it is only
(0228H) available when “SRC” = 0

SVSP The ascending and The setting of ascending and


descending time of 30 0 ~ 500 descending time of Ratio (in
(022AH) Ratio (in the panel) the panel)
PV-T The speed variation of
1.0 0. ~ 5.0 Timing setting of PV display
(022CH) PV display

CONN TB: Terminal Control


The source selection of
TB TB, RS485 RS485: Communication
(0240H) operation instruction
Control
TB: Terminal Control
RS485: Communication
SING TB,
The source selection of Control
TB RS485,
(0242H) analog signal RS-TB: Terminal Control, but
RS-TB
“SV” is controlled by
RS-485
SERI The setting of
communication 0 0 ~ 31 0 ~ 31
(0244H) address
BAUD Transmission speed could be
The setting of 4800, 9600,
9600 set as:
(0246H) transmission speed 19200
4800, 9600, 19200
PARI NO NO: Non-parity
Parity setting Even Even Even: Even-parity
(0248H) Odd Odd: Odd-parity

DSEC The setting of The delay time between


communication delay 15ms 5 ~ 65ms command message and reply
(024AH) time message

EUNTAY ELECTRIC CO., LTD. -4- Mar. 17, 2010


0: Communication abnormal
format and communication
interrupt overtime, controller
stop running
1: Communication format is
not correct, controller stop
The corresponding
SALN running; communication
action’s setting for
1 0~2 format is correct, but
(024CH) abnormal
interrupt time is over 3 sec.,
communication
controller stop running
2: Communication format is
abnormal and
communication interrupt is
over-time, controller
continue to run

YUNN 1234: Reset to default


Parameter cipher 0 0 ~ 9999 1 ~ 9999: Can’t change
(024EH) parameter
(0280H) BIT0: 1: P1 connect to COM
The control state of
BIT1: 1: P2 connect to COM
communication writing 0 0 ~ FFH
BIT2: 1: P3 connect to COM
(WRITE only)
BIT3~BIT7: Spare
“IN1” value, which is
sent from the
(0282H) communication 0 0 ~ 4095 2 Bytes (0 ~ 4095)
receiving host (WRITE
only)
“IN2” value, which is
sent from the
(0284H) communication 0 0 ~ 4095 2 Bytes (0 ~ 4095)
receiving host (WRITE
only)
BIT0: Communication check
code ERROR
0: Normal
1: Check code ERROR
BIT1: Communication format
ERROR
0: Normal
1: Format ERROR
BIT2: Communication interrupt
without reply
0: Normal
The address 1: Host can’t complete
The address of storing
of monitoring transmission within
(0290H) abnormal state (READ 0
data register 0.2 sec.
only)
(READ only) BIT3: Communication
read/write address
ERROR
0: Normal
1: Address ERROR
BIT4: Function code ERROR
0: Normal
1: Function code
ERROR
BIT5: Communication interrupt
over-time
0: Normal

EUNTAY ELECTRIC CO., LTD. -5- Mar. 17, 2010


1: Host doesn’t re-send
the communication
request over 5 sec.
BIT6: Spare
BIT7: Spare
The address
The address of storing BIT0: 1: RELAY_LO ON
of monitoring
(0291H) control and abnormal 0 BIT1: 1: RELAY_HI ON
data register
state (READ only) BIT2~BIT7: Spare
(READ only)
Communication for
(0292H) sending SV display 0 2 Bytes, SV display data
value (READ only)
Communication for
(0294H) sending PV display 0 2 Bytes, PV display data
value (READ only)
OUT1, which is sent
(0296H) from communication 0 0~4095 2 Bytes, (0- 4095)
(READ only)
OUT2, which is sent
(0298H) from communication 0 0~4095 2 Bytes, (0- 4095)
(READ only)

※Communication is option (MODEL:YTMC-6318-V2-…-RS)

EUNTAY ELECTRIC CO., LTD. -6- Mar. 17, 2010


4. Wiring Diagram

YTMC-6318V2 Wire Connection

Communication
Power Source RS485
AC220V

High/Low Limit Without function


Contact Output

RUN / STOP
(P.I enable/
Proportion is available) Without function
YTMC-6318V2
The acceleration &
deceleration direction
LINE SPEED Input
are reversed
0 ~ +10Vdc
Integral is out of 60
30
0
30
60

function & the roll’s Potential Meter


90

120
90

120

diameter is reset (2k/5k ohms)


_ 150
+ 150

feedback
YTM-01 signal

SPEED OUT for


Parameter Lock Inverter control
0 ~ +10Vdc

SPEED OUT for


Diameter Control
0 ~ +10Vdc
0V

5. Dimension