Material Submittals·
I I
Approval Stamp:

The document Acce(2tance Code

IA I !Approved IBI !Approved As Noted

lf.IJ Revise and Resubmit [[[]For Information Only

Signature: ...... ... ..... . ....... .. ... .... Date: I I


- ,

fi:I?'~
- h v I

Jlf..,,,f
,// -
f·t
"
rt~
i-

p
--
P A~
(.....--'
00 21-11-21 AM PH Issue For Approval
Rev. Date Prepared Reviewed Approved Description

Material Submittal

Chc111ical Trcat111cnt Systc111

( r. - w~tr.r)

Document Code:
Project Zone Trade Subtrade Originator Doc. Type Level Serial Nr. Rev.

lciGIMl-lxlxlxl-IMIEl-IAlci-IAITl-IMIAIRl-lxlxl-l 6 i 2 4 1°1°isl 1 ~
Improve your water
Improve your life

Client:Atrium
Thursday, Oct 14, 2021
Quotation #: 908
Address : District (8) Adjacent (1) Building (128) Apartment (21) Zayed
Tel/Fax. : 02-378853137/8
Mobile : 01122299044/01004258816/01114441999
Email : Info@cwater-eg.com – Adly@cwater-eg.com

City Gate Mall - BLDG "D"


Hyper Market - Alfa market

Prepared for

Atrium

Reviewed by
Chemist / Adly Hashad

C-Water Company

Submitted on
14/10/2021

QUALITY MEANS CONSCIENCE


2

STATEMENT OF CONFIDENTIALITY & NON –DISCLOSURE

This document contains proprietary and confidential information. All data submitted to in this submittalis
provided in reliance upon its content not to use or disclose any information contained herein exceptin the
context of its business dealing with C-Water Co. The recipient of this document agrees to inform present and
future employees of C-Water Co. who view or have access to its content of its confidential nature.

The recipient agrees to instruct each employee that they must not disclose any information concerning this
documents to others except to the exist that such matters are generally known to andare available for use by,
the public. The recipient also agrees not duplicate or distribute or permit others to duplicate or distribute any
material contained herein without C-Water Co.’s express written consent.

C-Water co. retains all tilts, ownership and intellectual property rights to the material and trademarks
contained herein, including all supporting documentation, files, marketing materials and multimedia.

BY ACCEPTANCE OF THIS DOCUMENT, THE RECIPENT AGREES TO BE BOUND BY THEAFOREMENTIONED


STATEMENT.

Water Treatment Prepared by C-Water Co. Confidential


3

EXECUTIVE SUMMARY
C-Water Co. is pleased to present this proposal for your system. We understand the water treatment
problems that you may face with recognize the unique opportunity to fulfill need. We believe that the water
market is in its maturing stage and that we are uniquely positioned to successfully treat your cooling system.

Having duly examined your requirements, we are confident that our proposed water treatment program
will effectively address your needs. Our goal is to protect your system from any corrosion,scale and
microbiological contamination by selection of the best water treatment program for your cooling system.
By implementing our solution, you will:

• Decrease water cost.

• Decrease Chemical treatment cost.

• Decrease electrical energy consumption.

• Decrease maintenance and repair cost.

Our unique ability to solve water problems and our successful track record makes us an enviablepartner
in this project. We look forward to forming a mutually rewarding relationship with your esteemed
company.

Cooling Tower Water system Goals


➢ Reduce Corrosion rate -
o Corrosion by Pitting should be not visible on the condenser inspection
o < 0,5 mpy on Coupon of Copper

➢ Scale Deposition –Visual inspection of condenser units surfaces


o Scale deposit free surfaces

➢ Measurement of total iron in the system


o < 0.2 ppm Fe

➢ Reduce Total number of bacterial count


o Free from pathogen
o Inhibit algae growth.

➢ Prevent legonalla growtho


Nil colony / ml.
o This sample shall be analyzed each 120 days

➢ Chemical consumption
o As per calculated amounts in treatment offer

Chilled system Goals

➢ Scale deposits –Visual inspection of chiller unit surface


o Scale deposit free internals
o Minimize suspended solids accumulation
➢ Corrosion rate – Measurement of total iron in the system
o < 0,7 ppm Fe in Chilled water system
o No pitting in Chiller unit internals
o Uniform al film layer on chiller internals
➢ Energy/Water consumption
o System should free from Microbiological fouling that affect heat transfer
o Reduction of maintain ace frequencies & chemical cleaning

Water Treatment Prepared by C-Water Co. Confidential


4

Service plan

As your water treatment consultant, C- WATER wants to become an integral part of your organization.In order
to have a successful water/process treatment program, it is necessary to set agreed-upon requirements and to
make sure that these requirements are strictly adhered to.

The most important element in meeting the requirements of monitoring and control is the system operator.
Our ability to work with your operators and train them to respond to changingsystem conditions and evaluate
parameters will be a major factor in the success of the process.

We address operator-training issues during service visits and by training seminars scheduled. Our goal is to
maintain a quality water treatment process and to keep that process in complete statistical control.

Thorough equipment inspection is important in determining the effectiveness of a water treatment process as
well as helping to uncover potential operational problems for a given system. It would be our intention to be
present during inspections of your condenser and chiller during plant outages and take pictures as possible to
document inspection results before & after starting treatment and give recommendations in form of a technical
report.

C-WATER SERVICE PROGRAM


C-WATER Company has the most advanced chemicals for water and process treatment. However, the greatest
asset we bring to our customers is the service program, which insures reliable operation. The real difference is
our commitment to our customer to:

• Provide analytical monitoring by our technician Rep.


• Interpretation of analytical results and recommendations by our Technical
Representative in a written Technical Service Report.
• Direct & coordinate corrective action, improvement recommendations and
troubleshooting.
• Hold formal and informal training sessions.
• Develop/update Operating Procedures with your staff.
• Support maintenance department in all equipment inspections/analyses with writtenreport.
• Management reviews to determine the return on investment of C-WATER Treatment
Programs on an annual basis and discuss/plan future improvement projects.

Water Treatment Prepared by C-Water Co. Confidential


25

Chilled Water System

Water Treatment Prepared by C-Water Co. Confidential


26

CLOSED SYSTEM OPERATING PARAMETERS

Parameter Value

No. of Closed Systems 1

Closed System Volume (m3) 20

Make-up water quality City water

CLOSED SYSTEM CONTROL PARAMETERS

Parameter CHILLED WATER


pH +9

Nitrite (chemical Residual) 800 - 1000 ppm

Iron 0.5 max.

Cu Nil

Water Treatment Prepared by C-Water Co. Confidential


27

Method Of Statement

Water Treatment Prepared by C-Water Co. Confidential


28

CHILLED SYSTEM TREATMENT PROGRAM

A. Chilled Water Cleaning Process.


Pre commission detergent/specific to remove organic soil, hydrocarbons, flux, pipe mill
varnish, Pipe compound, iron oxide, and like deleterious substances, suitable forsystem-
wetted metals without deleterious effects.

A.1. System preparation & Pre-Cleaning checking:

a) Checking the strainers in all circulation pumps and preparing smaller mesh size wire in
the strainers so as to start by removing large particles, then gradually remove smaller
particles.

b) A suitable number of staff must be available for changing the strainer (also suitable tools,
accessories must be available). Normally, all pumps must be in manual operation when
undergoing strainer changing of mesh size and cleaningplus checking the availability of
strainer gaskets.

c) Checking the Air vent availability and working mechanisms.

d) Checking drain valves.

e) Recording the pressure gauge reading in the network in each section showing the
pressure in the discharge side of the main circulation pumps.

f) Checking the available thermometers and get the actual temperature reading in the
points.

g) Checking the connection of the dosage pot for ideal operation.

Note: the above-mentioned steps shall be applied after the hydraulic pressuretest for
all the system.

Water Treatment Prepared by C-Water Co. Confidential


29

A.2. Pre flushing:


System must be flushed with fresh water, maintaining the maximum pumping flow to
achieve the highest velocity at the different branches. This can be applied by manually
putting all pumps in operation including the standby ones or by closing some of the
branches lines to increase the velocity.

It is recommended to perform balance make-up and drain to minimize the load on cleaning
step by allowing the loose particles to be removed, saving the cleaner for the hard
particles.

The ideal point of drain is on the return line just before the point of the make-up to
guarantee including the maximum circuit surface in the cleaning also it is useful todrain
from the lowest point in each building or in each riser. This Pre-flushing must run
continuously achieving clear water from all draining point.

A.3. Cleaning
The cleaner and pre-commission cleaner C-110 (2 kg per cubic meter) will react and
dislodge the corrosion products, mill scale, cutting oil, pipe thread compound and other
construction debris on the metal surface, which can be easily flushed outof system during
its chemical interaction products.

The efficiency of the cleaner and pre-commissioning cleaner will be replenished by


injection enough chemicals rates specified by C-Water at all times during the cleaning
step. This includes the system volume and balance make-up during the balance bleed and
make-up, which ensure that the debris generated is removed from the system via the
drain to prevent the some from re-depositing within the system in low flow areas and
chiller tubes. Experience shows the advantage of balance drain and refill, wherein
considerable debris has been removed from the system. Air must be prevented from
entering the system by avoiding blow of the system completely in order to prevent air
from entering the system and the aggressive attack of atmospheric oxygen on the clean
surface.

A.4. Flushing
In this step, the system must be flushed with any or both flushing mechanisms. Blowdown
the system or balance bleed and make-up i.e. water is drained from more thanone point i.e.
the lowest points in the network and the last point in the return line justbefore the make-up
points, until getting clear .

Water Treatment Prepared by C-Water Co. Confidential


30

B.PASSIVATION AND CORROSION INHIBITORFOR


CHILLED WATER CLOSED SYSTEM
For closed water system. Passivation and inhibitor chemicals C-101 (3 kg per cubic meter) will
promote the formation of a uniform impervious gamma layer film to stifle the corrosion
immediately. When this film is established, continuous treatment levels will maintain the film
intact. Continuous checking is required for monitoring the corrosion inhibitor concentration.

Dosing Consumption
Product Dose (ppm)
Criteria (Kg/Yr.)

C-101 3 kg per cubic meter Shock 60 kg

C-110 2 kg per cubic meter Shock 40 kg

Protec-10 1 kg per cubic meter Shock 20 kg

Nitrite-based anodic/cathodic corrosion inhibitor designed for use in closed chilled systems.Its
beneficial features are:
ü It gives both effective corrosion and scale control.
ü It is designed to be used in alkaline pH water environments, which buffers against pHupsets,
when used with specific stabilizing polymer.
ü It can be used over a wide variety of water hardness conditions, also in an alkaline
environment.
ü It is excellent for systems with long holding times and high-water temperatures.
It is acceptable in most cases from the pollution point of view

Water Treatment Prepared by C-Water Co. Confidential


C-101
PRODUCT DATA
Corrosion Inhibitor for Closed Water Circulating Systems

Description and Use

C-101 is a nitrite based corrosion inhibitor containing an additional organic inhibitor to protect steel, copper
and other non-ferrous metals. As such C-101 is an ideal treatment for closed chilled water and low pressure
heating systems.

C-­‐101  contains  a  pH  indicator  to  help  with  control  of  the  dosage.

C-101 is not intended for use in systems containing Aluminium.

Dosing

C-101 should be dosed at 3 - 5 kg/m3 in order to give an active reserve of 1200 ppm of sodium nitrite.

Typical Properties

Appearance – red or green coloured solution


Non-volatile, non-inflammable

Safety
See overleaf

Packing
Supplied in 25 kg poly drums

                   C-­‐Water  Chemicals  
                           Pharaonic  Water  Treatment  
Safety and Handling Precautions 

Product  name  C‐101   

Normal Use   closed circuit systems ‐ corrosion inhibitor and antifoulant. 

Fire/Explosion Risks  Slight ‐ contains oxidising agent. 

Health Hazards 

Toxic if swallowed.
Irritating to skin and eyes.
Toxic to aquatic organisms and may cause long-term adverse effects in the aquatic environment. 

First Aid 

Skin  Exposure:  Drench affected area with water, remove contaminated clothing, wash with soap
and water. If irritation develops, seek medical advice.

Eye  Exposure:  Irrigate with copious amounts of water or saline eye wash solution for at least
10 minutes. Obtain medical attention. 

Ingestion:  Wash  out  mouth  with  water  and  give  plenty  of  water  to  drink.    Do  not induce 
Vomiting  Obtain  medical  attention. 

Storage 
Keep container tightly closed and in a cool place. 
Keep away from combustible material. 
Keep away from cyanides and readily oxidisable materials. 

Handling 
Avoid contact with skin or eyes. 
Wear suitable protective clothing, gloves and eye protection. 

Spillage 
Flush spillage with plenty of water and wash to waste. 

Disposal 
Wash out empty container thoroughly with water before disposal. 
C-110
Chemical Cleaning Agent
PRODUCT DATA
Description

C-110 is a non-acid blend of sequestering and dispersing agents for the removal of iron oxide,
other metallic oxides and scale deposits from open and closed systems.
It may also be used continuously at low levels to prevent deposits forming.
C-110 is a safe, non-toxic alternative to ammoniated citric acid for pre-commission cleaning and
poses minimal effluent disposal problems.

Use

For pre-commission cleaning a concentration of 0.2-2% by volume should be used and circulated
For a minimum of 2 days and a maximum of 7 days.
For restoration cleaning a concentration between 2.5-5% is normally required, dependent on the
degree of fouling. The length of time required to affect a clean will again depend on the degree
of fouling and the progress of chemical reactions can be monitored by simple on-site test methods
or by postal samples to the C-Water Laboratory.

Warning

Whilst not aggressive to the parent metal C-110 is a powerful penetrant and will find any
weakness in pipe work or joints which is simply sealed by a layer of corrosion products. It is
recommended therefore that in the restoration of old systems that an initial concentration of 1%
only be added and circulated for 2 days to ensure system is sound before proceeding further.
When cleaning system containing Aluminum in conjunction with Copper a supplementary
treatment C-110 should also be added at the rate of 4-6 liter/cubic meter of system capacity.

Typical Properties

Appearance ............................................... Light yellow to white liquid


Flash Point ................................................ NONE

Safety and Handling

See overleaf

Packaging

C-110 is available in 22 kg drums.

C-­‐Water  Chemicals  
                       Pharaonic  Water  Treatment  
Safety and Handling Precautions 

Product Name     C‐110         IRRITANT 


Normal Use   As a precommission cleaning agent. 
Fire/Explosion Risks  None 

Health Hazards 

May cause skin irritation. 

First Aid 

Skin Exposure: Wash affected area with plenty of water, remove contaminated 
clothing, wash with soap and water. If irritation develops, seek medical advice.

Eye Exposure: Flush with clean flowing water for at least 15 minutes. Seek medical
advice.

Ingestion: Wash out mouth with water and give plenty of water to drink. Do not
Induce vomiting. Obtain medical attention.

Inhalation: Remove from exposure. Keep warm and at rest. Obtain medical attention
immediately. 
Storage 
Keep container tightly closed. 
Keep from freezing. 

Handling 
Avoid contact with skin and eyes. 
Wear suitable protective clothing, gloves and eye  protection. 

Spillage 
Flush spillage with plenty of water and wash to waste 

Disposal 
Wash out empty container thoroughly with water before disposal. 
Protec-10
PRODUCT DATA
Treatment for Corrosion Control of Drinking Water Lines

Description and Use

Protec-10 is a clear, odorless and tasteless corrosion inhibitor for the protection of drinking water and
domestic water systems which is quite harmless at normal use levels. It is effective in controlling corrosion
in pipe lines and storage tanks, particularly where supply water is either softened or naturally low in
alkalinity, resulting in ‘Red Water’ and general corrosion, which can be particularly troublesome in
Hospitals and Hotels.

Specifications

Appearance ............................................... Clear viscous liquid


Odor............................................................ None
Flash point ................................................ None

Dosing

Protec-10 will not effect the appearance or taste of water in any way. It is approved by the UK Drinking
Water Inspectorate for treatment of potable water.

Application

Protec-10 treatment should be continuously dosed to maintain a silica level of 8-10 ppm above the raw
water silica content. For automatic proportional dosing the use of a packaged water meter controlled dosing
set is advised.

Safety
See overleaf

Packing
Supplied in 25 kg poly drums

C-Water Chemicals
Pharaonic Water Treatment
Safety and Handling Precautions

Product Name Protec-10 IRRITANT


Normal Use Potable water corrosion inhibitor
Fire/Explosion Risks None

Health Hazards

May cause skin irritation.

First Aid

Skin Exposure: Wash affected area with plenty of water, remove contaminated
Clothing, wash with soap and water. If irritation develops, seek medical advice.

Eye Exposure: Flush with clean flowing water for at least 15 minutes. Seek medical
advice.

Ingestion: Wash out mouth with water and give plenty of water to drink. Do not
Induce vomiting. Obtain medical attention.

Inhalation: Remove from exposure. Keep warm and at rest. Obtain medical attention
Immediately.
Storage
Keep container tightly closed.
Keep from freezing.

Handling
Avoid contact with skin and eyes.
Wear suitable protective clothing, gloves and eye protection.

Spillage
Flush spillage with plenty of water and wash to waste

Disposal
Wash out empty container thoroughly with water before disposal.
31

Equipment
for
Closed System

Water Treatment Prepared by C-Water Co. Confidential


32

Pot feeder

Water Treatment Prepared by C-Water Co. Confidential


42

A- Pot feeder

The Shot feeder consists of a pressure- rated chemical tank installed across a pressure
differential, which can be from the discharge side to the suction side of apump.

Operation

The tank is charged with chemicals, and the valves arranged to allow water flow fromthe
high to low pressure side.
The flow of water through the chemical tank sweeps it clean, thereby injection the
chemicals.

Installation

The feeder should be installed in an accessible position close to the main feed line tokeep
connecting pipe work to a minimum.

The unit must be securely fixed to a wall or be floor mounted it must be supported
from the connecting pipe work, in all cases a suitable drainage point must be provided.

The advantage of this feeder is

ü Inexpensive
ü Easy to install
ü Simple to operate
ü Minimum maintenance.

Water Treatment Prepared by C-Water Co. Confidential


Fi11 ing funnel

1 112 " \.rcil ve


Ar vent

3/4
1
1 \.rcilve

Supply from chi11 ed system

Return to chilled system

3/4 \.rcil ve
11

To drain
! 3/4" ¼Ive

By Pass Feeder
System Installation Diagrams
32

Automatic Dosing System

Water Treatment Prepared by C-Water Co. Confidential


2- Automatic Dosing System for closed system.

Dosage and Control Arrangements

The chemicals will be dosed via chemical injection set to the system to allow the pH
in the recommended control limits 9+ and the chemical residual in the limit 1000 –
1200 to avoid system corrosion.

This system ensures the control of the associated chemical dosing pump and
determines dosing rate in direct proportion to water make up.

The system comprises of :

1- Dosing pump

Maximum Capacity : 5 liter per hour

Maximum Pressure : 5 bar

Origin : Italy

Brand : Etatron

2. Water meter

3. Control unit

4. 100 liter polyethylene tank


PKX THE GENUINE COMPACT DOSING

Solenoid driven dosing pump


Pompa dosatrice elettromagnetica

PKX series
Pompe doseuse électromagnétique
Elektromagnetische Dosierpumpe
Bomba dosadora electromagnética
Bomba dosificadora electromagnetica
Соленоидный дозирующий насос
106 143 106 143

158.4
188

Foot mounting Wall mounting


Montaggio a basamento Montaggio a parete
Montage sur pied Montage mural
Bodenmontage Wandmontage
Instalación a pared Instalación a pié
Montagem em base Montagem em parede
Горизонтальное крепление На тенное крепление

Curves flow rate vs. pressure bar


Curve caratteristiche portata-pressione
Courbes debit - pression
Förderleistung abhängig vom Druck
Curvas caudal-presión
Curvas de vazão x pressão
Кривая зави и о ти от противо авления 5

i.v.p
0
0 5 10 I/h

TECNICNICAL CARACTERISTICS/ CARATTERISTICHE TECNICHE

Type Max flow Max press Max imp./min. Output per stroke Stroke Suction height Standard power supply Power comp. Current comp. Net weight
Tipo Portata max Pressione max Max imp./min. Dosaggio per imp. Corsa Altez. aspiraz Aliment. elettr. standard Potenza ass. Corrente ass. Peso netto
I/h bar ml mm m Vollts - Hz Watts Ampere kg
1-5 1 5 120 0.14 0.80 2.0 220/240 V 50-60 Hz 32 0.14 1.9
2-6 2 6 120 0.28 0.80 2.0 220/240 V 50-60 Hz 32 0.14 1.9
5-5 5 5 120 0.69 1.10 2.0 220/240 V 50-60 Hz 32 0.14 1.9
7-2 7 2 120 0.97 1.30 2.0 220/240 V 50-60 Hz 32 0.14 1.9
10 - 1 10 1 120 1.39 1.30 2.0 220/240 V 50-60 Hz 32 0.14 1.9
HYDRAULIC PARTS/CONFIGURAZIONE IDRAULICA

WETTED PARTS/PARTI A CONTATTO CON IL LIQUIDO STANDARD MATERIALS/VERSIONE STANDARD UPON REQUEST/ A RICHIESTA

Pump head/ Corpo pompa PP PVC; AISI 316; PVDF ;PTFE


Diaphragm/ Diaframma PTFE PTFE; PVDF
Nipples/ Raccordi PP AISI 316; PVDF
LIP valves/ Valvola a labbro FPM (Viton ) EPDM (Dutral ); Silicone ; NBR
Sealings/O-rings/ Guarnizioni/O-ring FPM (Viton ) EPDM (Dutral ); Silicone ; NBR
Injection valve/ Corpo valvola iniezione PP AISI 316; PTFE
Foot filter / Filtro di fondo PP AISI 316; PTFE
Suction/Bleeding tubings/ Tubi aspirazione/spurgo PVC PTFE; PVDF
Delivery tubing/ Tubo mandata PE PTFE; PVDF
Injection valve sleeve/ Tenute Valvola iniezione/non ritorno FPM (Viton ) EPDM (Dutral )

A RICHIESTA/ UPON REQUEST:


Pump head with gravity ball/ Corpo pompa con valvole a sfera gravità Glass Pyrex/ Vetro Pyrex AISI 316; Ceramic/Ceramica
Pump head with hastelloy spring loaded ball valve/ Glass Pyrex/ Vetro Pyrex AISI 316; Ceramic/Ceramica
Corpo pompa con valvole a sfera e molla in Hastelloy

Viton : FPM / Dutral , Dupont trademarks/ Viton : FPM / Dutral , sono marchi registrati della Dupont Elastomeri

code DCY00024ML-A (04-2006)

ITALY (SEDE - HEAD OFFICE) ITALY (BRANCH OFFICE) ASIA


ETATRON D.S. S.p.A. ETATRON D.S. Inc ETATRON D.S. (Asia-Pacific) PTE Ltd
Via Catania, 4 Via Ghisalba, 13 No. 7, Kaki Bukit Road 2 - #03-01
00040 Pavona di Albano Laziale (RM) ITALY 20021 Ospiate di Bollate (MI) ITALY Great Pacific Warehouse, Singapore 417840
Phone +39 06 93 49 891 (r.a.) Phone +39 02 35 04 588 Phone +65 67437959
Fax +39 06 93 43 924 Fax +39 02 35 05 421 Fax +65 67430397
E-mail: info@etatronds.com E-mail: info@etatronds.com E-mail: info@etatron.ru
Web: www.etatronds.com Web: www.etatronds.com Web: www.etatron.com

UNITED KINGDOM IRELAND CANADA


ETATRON (U.K.) ETATRON (Ireland) Limited ETATRON D.S. Inc
Moor Farm House East Road The Pike #203-17665 - 66A Ave
Sleaford Lincolnshire, NG34 8SP Lisavaird Clonakilty Co.Cork Surrey BC V3S 2 A7 Canada
ENGLAND Republic of Ireland Phone +1 604 576 8539
Phone +44 1529 30 05 67 Phone: +353 1883 44 66 Phone+1 604 574 1401
Fax +44 1529 30 05 03 Fax: + 353 1883 44 68 Fax +1 604 576 0924
E-mail: sales@etatron.co.uk E-mail: sales@etatron.co.uk E-mail: info@etatronds.com
Web: www.etatron.co.uk Web: www.etatron.co.uk Web: www.etatronds.com

UKRAINE RUSSIA FEDERATION


OOO ETATRON-UKRAINE OOO ETATRON
Soborna Street, 446 3-rd Mytishchinskaja street, 16/2
Rivne, 33024 Rivne region, Ukraine 123626 Moscow, Russian Federation
Phone +380362610681 Phone +7 495 7871459
Fax +380362622033 Fax +7 495 7871459
E-mail: etatron@ukrwest.net E-mail: etatron@etatron.ru
www.etatron.com.ua www.etatron.ru
PAYMENT TERMS
• 50 % down payment against check
• Increase to 100% on site delivery against check

WARRANTY

• 1 year from date of installation with maximum of one month from


delivery

Service Charge OFFER VALIDITY

Included in our offer


Supervising
1 Month

all the treatment process

you are kindly requested to


cover accommodation and
transportation