Technical Data

rfan-d55e issue 06.2002

Tap Position Interface


Type REG-F 'D2 B3' F1

F2
Function
The tap position interface REG-F 'D2' passes the signal from
the dry contact row of a tap changer transformer on to the
voltage regulator system REGSys with BCD-Code.
At the same time the signal is readable on relais contacts.
The tap position is shown on the integrated display. REG-F 'D2 B3' 144 x 72

An external DC voltage (user part) supplies the moving side


of a dry contact row and is connected to 'E GND'.
Switching contacts feed the inputs 'EBCD1 ...EBCD20' of the
Code table input output
REG-F 'D2'. Binary outputs (current) pass the information on BCD code BCD code
to the voltage regulator system REGSys and to 6 relay con- 20 10 Dez
tacts (N/O) for further processing. 8 4 2 1 20 10 8 4 2 1
 6 BCD input range 1 ... 39 or –19 ... 0 ... +19 taps 0 0 0 0 00 0 0 0 0 0
 up to 100m cable length from tap changer to REG-F 0 0 0 U+ 10 0 0 0 0 1
0 0 U+ 0 20 0 0 0 1 0
'D2'. 0 0 U+ U+ 30 0 0 0 1 1
 noise immunity by opto isolation
 relais contacts with AC 250V 2A, DC 220V 150W U+ 0 0 0 80 0 1 0 0 0
 wide range of power supply voltage U+ 0 0 U+ 90 0 1 0 0 1
0 = EGND 0 = BCD GND
Technical Characteristics
Standards
IEC1010, IEC801-1 to 6 Electrical Safety
VDE0110, VDE0160 protection class / overvoltage category I / II
electrical noise immunity EN50082-2 pollution degree 2
electrical noise emission EN50081-2, EN55011 test voltage AC 2,3k V
BCD voltage input, current outp. against aux. voltage,
Mechanical Data against relay contacts
desingn panel case DIN43700 auxiliary voltage against relay contacts
144x72x210mm (WxHxD) Mat UV94V-1
connectors 2 pcs, 'F1' with 10 poles Power Supply
'F2' with 16poles isolated characteristics H1 AC 85..264 V / DC 100 ..280
protection class IP40 V
weight  1,2 kg ( 2 connectors included) characteristics H2 AC 20.. 60 V / DC 18 .. 72
mounting 138x69mm cutout in panel, 2 clips V
power consumption < 6 VA / 6W
Input
external voltage on EBCD1..20, E GND; input resistance Re Temperature operation / storage 0 ... +55°C/-25 ...
tap output BCDxx open < 3 V AC / < 5 V DC +75°C
tap output closed (char. E1,E2) DC 12 .. 50V,Re ~ 7kW
(characteristics E3) DC 50 ..250V,Re Contact assignment
~50kW
connector F2 connector F1
ripple voltage < 2 V, 50Hz 16 poles 10 poles
11 EBCD 1
Output 12 EBCD 2
current output BCD 1 ... BCD 20 for BCD-input (50V) of the 13 EBCD 4
REG-D, assigned to BCD GND; 14 EBCD 8
voltage on 10kW ON (1) > 10V DC 15 EBCD 10
OFF(0) < 5V DC 16 EBCD 20/Vz- 1 L (+)
17 E GND 2 N (-)
voltage output U+ 15V DC +10%; supply GND BCD;
18 U+ 3 PE pro-
internal resistance approx.1kOhm tect.earth
6 relays, one (N/O) contact each for BCD codes 1 20 GND BCD 4 relay supply
..20/sign- contact closed / open (1) / (0) 21 BCD20 or sign- 5 relay20 or sign-
isolation auxiliary voltage and relay contacts are 22 BCD 10 6 relay BCD 10
isolated against each other and from all 23 BCD 8 7 relay BCD 8
other circuits 24 BCD 4 8 relay BCD 4
contact load AC 250V 2A, DC 220V 150W 25 BCD 2 9 relay BCD 2
5 26 BCD 1 10 relay BCD 1
contact operations < 10
1
Technical Data REG-F D2

feature characteristics
tap position interface REG-F D2 panel case 144 x 72, with dis- REG-F D2 B3
play
galvanically isolated AC 85..264 V / DC 100 .. 280 H1
V H2
./. AC 20... 60 V / DC 18 .. 72 V
E2
external supply voltage on EBCD1 ... 20 DC 12 ... 50 V
E3
DC 50 .. 250 V

Application REG-F 'D2' with indication REG-F 'D2' Interface BCD --> 2x BCD REG-D

characteristics D2 input 6 x BCD F1/ 4


BCD 20
H1 auxiliary voltage AC 230V F1/ 5

E3 external voltage DC 50..250V


10
for the tap changer (user part) F1/ 6

8
F1/ 7

4
F1/ 8

2
F1/ 9
tap changer at transformator
Isol. 3mm creepage distances
BCD code "15" and clearances 1
F1/ 10
100 BCD 1 F2/ 11 EBCD 1

BCD 2 F2/ 12 EBCD 2

BCD 4 F2/ 13 EBCD 4


BCD
BCD 8 F2/ 14 EBCD 8

101 BCD 10 F2/ 15 EBCD 10

BCD 20 or sign- F2/ 16 EBCD 20 tap position indication


of transformer
GND F2/ 17 E GND
U+ BCD BCD 1 F2/ 26 V 24b BCD1 input LV
2 F2/ 25 V 26b 2 (50V)
4 F2/ 24 V 28b 4
8 F2/ 23 V 30b 8
10 F2/ 22 V 24z 10
cable length l 20 /sgn(-) F2/ 21 V 26or 30z 20 or sign-
cable length, AWG U external BCD GND F2/ 20 V 32b/32z GND
50.. 250V DC
GND

< 100m 16 AWG (1,5mm2)


U+
< 40m 18 AWG (1,0mm2)
1kOhm
U+ PE N (-) L (+)

F2/18 F1/3 F1/2 F1/ 1

19" mounting rack

For longer distances between the transducer and the REG-F 'D2', the maximum cable length will depend on the interference by
parallel cables rather than on the maximum output voltage of the transducer.

A permissible ripple voltage of up to 2V on the input of REG-F 'D2' is allowed. As there are different ground and voltage conditions
in every application, longer cables are in general possible, however, shielding and wider distances between the parallel cables must
be provided.