Technical Data

rgs-td57e issue 11.2001

code table
Tap Position Interface inputs: outputs:
Type REG-S 'Y9 1 of n
(only one BCD - code
switch closed) 20 10 8 4 2 1
Operation contact 1 0 0 0 0 0 1
The tap position interface REG-S decodes the position of a contact 2 0 0 0 0 1 0
tap changer transformer to BCD code. . .
An external DC voltage (user part) supplies the moving side contact 10 0 1 0 0 0 0
of a dry contact row. REG-S gets the information from this contact 11 0 1 0 0 0 1
switch and the built-in diode matrix decodes the closed con- . .
contact 29 1 0 1 0 0 1
tact out of n to BCD (see code table). At one time only F2 F3 F4
contact 30 1 1 0 0 0 0
one contact should be closed. REG-S 'B2' contact 31 1 1 0 0 0 1
Outputs of REG-S will be wired to BCD inputs of REGSys.
A capacitor on each input enhances the noise surpression.
Function
 up to 35 dry contacts of a switch were decoded to BCD
 up to 100m cable length between switch and REG-S voltage drop across diode matrix < 2,5 V at I2 0,1A
 wide range of external DC voltage diode reverse voltage 400 V DC
capacitor on inputs 0,1 uF / 63V DC
Technical Characteristics Temperature operation 0 ... +65°C;
Mechanical Construction storage, transportation -25 ... +85°C
case wall mountable, aluminium, silver
205x106x130mm (Length x Wide x H.) connectors
protection class IP 00
conn. F2 conn. F3 conn. F4
connectors 3 pcs, 'F2,F3,F4': 16 pins each 16 pins 16 pins 16 pins
weight 3 connectors included  1,4 kg 11 cont. 33 31 cont. 1 51 cont. 2
mounting 130 cont. 34
12 32 cont. 3 52 cont. 4
13 cont. 35 33 cont. 5 53 cont. 6
... ... ... ...
120 20 GND cont.
/ BCD
21 BCD 20
Input or sign(-)
input voltage U1 22 BCD 10 42 cont. 23 62 cont. 24
dry contact closed 12 .. 60 V DC 23 BCD 8 43 cont. 25 63 cont. 26
open < 5 V DC 24 BCD 4 44 cont. 27 64 cont. 28
differential mode voltage < 2 V AC 25 BCD 2 45 cont. 29 65 cont. 30
26 BCD 1 46 cont. 31 66 cont. 32
input current < 5 x I2
Protective earth connection will be performed by use of a
Output current I2 into REGSys inputs 'Fast-On' connector (6,3mm) at REG-S case.
BCD 1,...BCD 10, BCD 20 or sign (-)
ON (1) < 0,1 A Order information
OFF (0) < 50 uA Tap position interface, wall mountable REG-S B2 E2 Y9

application REG-S ' B2 E2 Y9


tap changer transformer REG-S 'Y9 REG-D
1 out of n --> BCD decoder
with dry contact row
contact 1 F3/ 31 contact 1
1 out of n 2 F4/ 51 2

27 F3/44 27
28 F4/64 28
29 F3/45 29
30 F4/65 30
31 F3/46 31 tap position display
F4/66 32
U+ F2/ 11 33 BCD 1 F2/ 26 V 24b BCD1 inputs
F2/ 12 34 2 F2/ 25 V 26b 2
F2/ 13 35 4 F2/ 24 V 28b 4 binary -
8 F2/ 23 V 30b 8 low volt.
10 F2/ 22 V 24z 10 50V DC
cable length l BCD 20 or sign(-) F2/ 21 V 26z or 30z 20/,sgn (-)
GND F2/ 20 V 32b,32z GND
cable length l, AWG

< 100m 16AWG (1,5mm2)


< 40m 18AWG (1,0mm2)
U+ GND

a.eberle gmbh
Aalener Str. 30 D-90441 Nürnberg Germany phone +49 911 - 62 81 08 0 FAX - 66 66 64