Substation/Bay:
Substation: Substation address:
Bay: Bay address:
Device:
Name/description: Test Object Manufacturer:
Device type: Device address:
Serial/model number:
Additional info 1:
Additional info 2:
Hardware Configuration
Test Equipment
Type Serial Number
CMC256plus RJ869T
Hardware Check
Performed At Result Details
5/10/2022 2:40:42 PM Passed
Diff Configuration:
Test Module
Name: OMICRON Diff Configuration Version: 4.30
Test Start: 10-May-2022 14:45:33 Test End: 10-May-2022 14:45:43
User Name: Almiqdad Manager: Elgortbi
Company: SETCO
Test State:
Test passed
1 out of 1 points tested.
1 points passed.
0 points failed.
1/4
Test Object - Differential Parameters
Protected Object:
Protected Object: Busbar
Vector Group: n/a
Winding/Leg Name: Primary Secondary
Voltage: 33.00 kV 33.00 kV
Power: 114.32 MVA 114.32 MVA
Starpoint Grounding: No No
Delta-connected CT: No No
CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 400.00 A 400.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: 200.00 A 800.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a
Protection device:
Reference Winding: Primary
Ibias Calculation: ( |Ip| + |Is| ) / K1 (K1 = 1.00)
Zero Seq. Elimination: none
Reference Current: PO nominal current
Ground CT Used: No
Disable Comb. char.: No
Test Module
Name: OMICRON Diff Operating Version: 4.30
Characteristic
Test Start: 10-May-2022 14:43:45 Test End: 10-May-2022 14:45:13
User Name: Almiqdad Manager: Elgortbi
Company: SETCO
Test Settings
General Settings:
Testing: Primary / Secondary
Max. Test Time: 1.50 s Delay Time: 0.25 s
Prefault: Yes
Prefault current: 0.50 In Prefault time: 1.000 s
Vout enabled: No Vout winding: Primary
Time-triggered: No Winding/leg output: Primary
Binary Outputs
Bin. out 1: 0
Bin. out 2: 0
Bin. out 3: 0
Bin. out 4: 0
2/4
Test Results for Fault Location L1-E at Reference Side Primary
Idiff Check
Ibias Idiff Actual Dev (rel) Dev (abs) State Result
Nominal Test
2.70 In 1.620 In 1.708 In 5.41 % 0.0876 In Tested Passed
2.30 In 1.380 In 1.377 In -0.20 % -0.0028 In Tested Passed
1.50 In 1.200 In 1.187 In -1.09 % -0.0131 In Tested Passed
6.0
5.0
4.0
3.0
2.0
1.0
0.0
1 2 3 4 5 6 7 8 9 10
Ibias [In]
Test State:
Test passed
3 out of 3 points tested.
3 points passed.
0 points failed.
Test Module
Name: OMICRON Diff Trip Time Version: 4.30
Characteristic
Test Start: 10-May-2022 14:46:01 Test End: 10-May-2022 14:46:04
User Name: Almiqdad Manager: Elgortbi
Company: SETCO
3/4
State:
1 out of 1 points tested.
1 points passed.
0 points failed.
4/4