You are on page 1of 5

 

Will be discharge 
to roadside drain 


 

DI PIPE 450mm Ø
DISCHARGE TO 
DRAINAGE SUMP 

UDRAIN 1.8 x 1.9m 


PROJECT : KAJANG ECO-VALLEY
EFFLUENT PUMPING DESIGN : 40700PE
1 DESIGN DATA

1.1 Design Process = Extended Aeration


1.2 Population Equivalent = 40700 PE
1.3 Wastewater flow per person = 0.225 m3/PE day ( or 225 lpcd )
1.4 Average wastewater flow = 9157.5 m3/day
= 381.56 m3/hr
= 6.359 m3/min
1.5 Peak flow factor = 4.7 x P-0.11
= 4.7 x ( 40700 / 1000 )^-0.11
= 3.13
Peak flow = 9157.5 x 3.13
= 28662.98 m3/day
= 1194.29 m3/hr
= 19.9 m3/min

2.0 DESIGN OF MANUAL PRIMARY SCREEN


2.3 LIQUID DEPTH
Let the screen width = 2m
a. The screen is clean, liquid depth (d) for = 0.4646m2 / 2m
one channel = 0.232 m
b. The screen is half plugged, liquid depth = 0.232m + 0.1m
(d+ H) = 0.332 m (required depth)
Provided depth = 0.5 m > 0.332 m, ok

3.0 DESIGN OF SEWAGE PUMP SUMP


3.1 EFFECTIVE VOLUME OF SUMP (WET WELL)
The effective volume of influent pump sump is calculated based on 6-10 minutes
and maximum 15 minutes for start/stop cycle per hour (time cycle)
V = TQ ÷ 4
where = 10*28662.98/(4*24*60)
V - volume = 49.76 m3
Q - Peak flow
T - Cycle duration = 10
Provide wet well/pit area of 5 mx 5m
Required effective depth = 49.76/(5*5) = 1.99m
Minimum effective operation height between duty pump start level and duty cut off
Provided effective depth, H = 2m
Provided effective volume = 5m x 5m x 2m
= 50 m3 > 49.76 m3

3.2 PIPE SIZING

Pump capacity at peak flow = 0.3317 m3/sec.


= 19.9 m3/min
= 331.67 l/s
Velocity in the discharge pipe at maximum pump discharge ≤ 2.5 m/s (MS 1228)

Adopt velocity in discharge pipe as 2 m/s


Diameter D = √(0.3317*4/(pi*2))
= 0.46 m
Provided pipe diameter ø = 450 mm (D.I. material or equivalent)
Actual mean velocity, V = (0.3317*4/(pi*0.45^2)
= 2.09 m/s LESS THAN 2.5m/s, ok

Page 1 of 3
* * HYDROLOGY * * * HYDRAULIC
AREA Intensity, Flow Rate, TOTAL DRAIN DETAILS, Velocity, Flow Rate,
LOCATION  C ƩA i Q ƩQ W H P A R S V Q
MARKING (ha) (mm/hr) (m³/s) (m³/s) (m) (m) (m) (m²) (m) (m/s) (m³/s)

0.95 3.000 322.3 2.551 2.5514140 1.80 1.90 5.60 3.42 0.61 0.023 7.3 25.0126889
STP DISCHARGE 19.900 19.9000000
25 YEARS 
DISCHARGE TO 
22.4514140
SUMP
*refer MSMA N = 0.015
TOTAL AREA :                                                  ‐  acre STOR JPS KAJANG
ƩA                                      30,000.00
  m2 ʎ K θ ɳ
                                               3.00
  ha 59.153 0.161 0.118 0.812

to = 107nL1/3 td = nL i = ʎTK


1/5 2/3 1/2
s 60R S (d+θ)ɳ

n = 0.015 Ld  = 107 m d = tc :  to + td 


s = 6.35 s = 0.005 = 7 min
n = 0.018 = 0.1167 hr
Lo  = 60 m w = 0.9
h = 0.9 T = 2 i2 = 214.603 mm/hr
to = 5 min A = 0.81 T = 5 i5 = 248.716 mm/hr
P = 2.7 T = 10 i10 = 278.080 mm/hr
R = 0.3 T = 25 i25 = 322.284 mm/hr
T = 50 i50 = 360.333 mm/hr
td = 2 min T = 100 i100 = 402.875 mm/hr
Channel Report
Hydraflow Express Extension for Autodesk® AutoCAD® Civil 3D® by Autodesk, Inc. Thursday, Jan 13 2022

<Name>

Rectangular Highlighted
Bottom Width (m) = 1.9000 Depth (m) = 1.6215
Total Depth (m) = 1.9000 Q (cms) = 22.2000
Area (sqm) = 3.0809
Invert Elev (m) = 69.9000 Velocity (m/s) = 7.2056
Slope (%) = 2.3200 Wetted Perim (m) = 5.1431
N-Value = 0.015 Crit Depth, Yc (m) = 1.9000
Top Width (m) = 1.9000
Calculations EGL (m) = 4.2699
Compute by: Known Q
Known Q (cms) = 22.2000

Elev (m) Depth (m)


Section
72.1000 2.2000

71.8000 1.9000

71.5000 1.6000

71.2000 1.3000

70.9000 1.0000

70.6000 0.7000

70.3000 0.4000

70.0000 0.1000

69.7000 -0.2000

69.4000 -0.5000
0 .3 .6 .9 1.2 1.5 1.8 2.1 2.4 2.7 3

Reach (m)