CX501KB Series

TRAINING GAS TURBINES

START SEQUENCE

MLN BLOCK 405, ALGERIA


OPERATOR TRAINING

CX501KB Series
TRAINING GAS TURBINES

KB7 STARTING SEQUENCE

VENT FAN
AC LUBE OIL PUMP
STARTER MOTOR FUEL GAS OPEN

IGNITERS B.O.V. CLOSED


R.P.M. EXCITATION AND SYNCHRONISATION
LOAD RAMP ON LINE
BREAKER CLOSE
16,000
14571RPM GOVERNING
14,000 12200RPM BOVs CLOSE
13,000 RPM START RUN
12,000 TRANSITION OIL COOLER FAN ON
10,500RPM STARTER DROPOUT
10,000
PURGE
8,000 ( typically
3 minutes)
6,000 6000 RPM AC PUMP OFF

4,000
2,000 < 2000 RPM STARTER RE ENGAGE

0
5 15 25 35 45 55 165 175 185 195205 215 225 235 245 255 265 275 285 295 305 315 325 335 345 355 365 375 385 395

TIME (SECONDS)

START SECTION 7 PAGE 1-2


CX501KB Series
TRAINING GAS TURBINES

Turbine Start Sequence

This series of screens will briefly follow the main steps


undertaken when the turbine generator package is started.

CX501KB Series
TRAINING GAS TURBINES

At the HMI..Turbine "Ready to Start"

READY TO START

START SECTION 7 PAGE 3-4


CX501KB Series
TRAINING GAS TURBINES

Select "Start"

CX501KB Series
TRAINING GAS TURBINES

Confirm "Start"

START SECTION 7 PAGE 5-6


CX501KB Series
TRAINING GAS TURBINES

The enclosure ventilation fans starts...

FAULT CONDITION
ENCLOSURE VENTILATION FAULT:
No ventilation flow detected within
1 minute of start initiate. Check
enclosure doors; Vent fan failed;
Enclosure filters blocked ( high
delta P also indicated) or differential
pressure transmitter fault.

CX501KB Series
TRAINING GAS TURBINES

Control System now performs an automatic start sequence....

Main Programmable
Engine Control Unit Logic Controller
(ECU) (PLC)

START SECTION 7 PAGE 7-8


CX501KB Series
TRAINING GAS TURBINES

The PLC carries out the Block Valve tightness Check....

FAULT CONDITIONS

GAS BLOCK VALVE TIGHTNESS CHECK


FAILED- Pressure too low between block valves
in the first part of the check or too high in the
second part - leaking block or vent valve.

CX501KB Series
TRAINING GAS TURBINES

Lube oil priming pump starts and builds up oil pressure...

FAULT CONDITIONS
PRIMING OIL PUMP MOTOR NOT
RUNNING :Motor requested but not
running. No feed back signal from
contactor. Contactor failed to operate
either tripped, isolated or failed
FAILED TO PRIME : Lube oil pressure <
0.68 bar g with standby pump running
and start/ cranking initiated. Priming Oil
Pump failure check AC supply to pump;
Oil pressure regulator fault or system
leaks.

START SECTION 7 PAGE 9-10


CX501KB Series
TRAINING GAS TURBINES

Electric start motor starts...


Hydraulic pump solenoid engaged...
System on load.

FAULT CONDITIONS
ELECTRO-HYDRAULIC START MOTOR NOT
RUNNING: Motor requested but not running.
No feed back signal from contactor. Contactor
failed to operate either tripped, isolated or
failed
STARTER FAILED TO ENGAGE: Turbine failed
to reach 500rpm/ 20 secs after
hydraulic solenoid energised Check for
leaks in Hydraulic start system; insufficient
pump output or blocked hydraulic filter

CX501KB Series
TRAINING GAS TURBINES

Turbine is motored to PurgeSpeed of approx 3500 rpm.

R.P.M.

16,000
14,000
12,000
10,000
8,000
6,000
4,000
2,000
0

FAULT CONDITIONS
TURBINE FAILED TO CRANK: Turbine failed to reach 1800rpm/ 30 secs after
hydraulic solenoid energised. Check for leaks in Hydraulic start system; insufficient pump
output or blocked hydraulic filter

START SECTION 7 PAGE 11-12


CX501KB Series
TRAINING GAS TURBINES

Compressor BOVs closed at 3000rpm

CX501KB Series
TRAINING GAS TURBINES

A timed purge for turbine exhaust ducting.

R.P.M.

16,000
14,000
12,000
10,000
8,000
6,000 PURGE

4,000
2,000
0

FAULT CONDITIONS
FAILED TO PURGE: Turbine failed to achieve 3000rpm/ 20 secs after hydraulic start system
energised or if speed drops below 3000rpm whilst purge timer is operating. Hydraulic Start
system failure; Start motor isolated or local stop switch operated.

START SECTION 7 PAGE 13-14


CX501KB Series
TRAINING GAS TURBINES

Hydraulic Start solenoid disengaged....Compressor BOVs


open...Turbine reduces speed again to below 2000 rpm.

R.P.M.

16,000
14,000
12,000
10,000
8,000
6,000
DECEL
4,000
2,000
0

CX501KB Series
TRAINING GAS TURBINES

At 2000rpm the hyraulic solenoid is re-engaged..


the gas block valves are opened...
and the igniters switched on...

START SECTION 7 PAGE 15-16


CX501KB Series
TRAINING GAS TURBINES

Acceleration Fault Conditions

FAULT CONDITIONS
IGNITER CHECK FAULT: Either main PLC or back Up PLC not requesting for
igniters to be turned on during the start sequence (both plcs must request igniters on
within 1 second of the other). Check for PLC fault; PLC sequencing fault; speed scaling
of either plc incorrect, fault seen by only one PLC. Plc programming fault.
GAS MANIFOLD/ P2 DP HIGH: Gas manifold pressure 0.6 bar > compressor delivery
pressure with Turbine Outlet Temperature < 180°C. Check gas regulator; or gas pressure
outside limits. Check setting of ECU gas ratio.
TURBINE FAILED TO LIGHT: CT temp. < 316°C or TOT <180°C 3seconds (10secs liquid
fuel) after fuel switched on and igniter energised. Check for igniter fault; - Insufficient
fuel :Fuel supply fault; gas-regulator or valve fault.; Compressor bleed valve position.
TURBINE OVER TEMP STARTING: CT temp. >871°C at turbine speed >13000 rpm ECU
fault (incorrect regulation by engine governor) FMV or fuel supply fault, check engine.
TURBINE STAGNATION: Turbine acceleration < 40rpm/sec speed<13000rpm.-
insufficient fuel. Check: Insufficient fuel :Gas regulator; Hydraulic start system;
Compressor bleed valve position

CX501KB Series
TRAINING GAS TURBINES

The turbine accelerates rapidly ....

R.P.M.

16,000
14,000
12,000
10,000 ACCEL
8,000
6,000
4,000
2,000
0

START SECTION 7 PAGE 17-18


CX501KB Series
TRAINING GAS TURBINES

Turbine fires and continues to accelerate...


Oil priming pump off 6,000rpm
Start motor off 10500rpm
BOVs close 13000rpm

CX501KB Series
TRAINING GAS TURBINES

Start/run transition 13,000RPM...


Oil Cooler Fan on...
Generator excitation on...

A V

EXCITATION EXCITATION
CURRENT VOLTAGE

FAULT CONDITIONS
OIL COOLER FAN NOT RUNNING (ALARM): Motor requested but not running. No feed back signal from contactor.
Contactor failed to operate either tripped, isolated or failed

START SECTION 7 PAGE 19-20


CX501KB Series
TRAINING GAS TURBINES

Turbine continues to accelerate to governed speed of 14571rpm.

CX501KB Series
TRAINING GAS TURBINES

Synchroniser raises generator voltage to match that of the


grid...

I I

Hz + - V
II
II

II I

I Grid Frequency SYNCHROSCOPE I Grid Voltage


II Generator Frequency II Generator Voltage

START SECTION 7 PAGE 21-22


CX501KB Series
TRAINING GAS TURBINES

and raises or lowers turbine speed to match frequencies...

I
I

V
Hz + -

II II

II I

I Grid Frequency SYNCHROSCOPE I Grid Voltage


II Generator Frequency II Generator Voltage

CX501KB Series
TRAINING GAS TURBINES

When voltage and frequency match the generator breaker


closes.

+ -

II I

FAULT CONDITIONS
SYNCHROSCOPE
G
FAILED TO AUTOSYNCHRONISE (ALARM): Switch the auto synch off and then on again. If it fails a
second time set to Manual and synchronise using the volts and frequency raise/lower switches and
breaker close. If still not working switchgear problem.

START SECTION 7 PAGE 23-24


CX501KB Series
TRAINING GAS TURBINES

Generator power is ramped up to power or temperature


setpoint at 100kW/sec.

7
6
5
POWER kW
4
3
2
1
0
TIME SEC

Control system maintains Generator at preset power output


and temperature

START SECTION 7 PAGE 25-26