Professional Documents
Culture Documents
No:5
Date:
FAULT ANALYSIS
AIM
To compute the fault level, post-fault voltages and currents for both
symmetrical and unsymmetrical faults.
Software Required
MIPOWER
Theory
The system must be protected against heavy flow of short circuit current
during the occurrence of the fault. This is done by disconnecting the faulty section
from the healthy section by means of circuit breaker. To estimate the magnitude of
fault current for the proper choice of circuit breaker and protective relays, short
circuit study is essential.
Fault types:
The most common type of fault on a three phase system by far is the line-to-
ground (L-G), followed by the line-to line faults (L-L), double line-to-ground (L-
L-G) faults, and balanced three phase faults. The probability of two or more
simultaneous faults on a power system is removed and is therefore ignored in
system design for abnormal conditions.
In power system, loads are specified and the load currents are unknown. The
effects of load currents in the fault analysis are to express the loads by constant
impedance evaluated at the prefault bus voltages.
Prefault fault bus voltages are obtained from the results of power flow
solution.
Loads are expressed by constant admittance using prefault bus voltages.
Replace reactances of synchronous machines by their sub-transient /
transient values.
Draw reactance diagram for the short circuit.
Draw Thevenin’s equivalent viewed from faulted bus (qth bus) and find the
fault current using the following formula
Vq0
If (5.1)
Z qq Z F
f 0
Vq Vq Z qq I f (5.2)
f
VN VN0 Z Nq I f
Determine post fault line flows using the following formula (5.3).
Vi f V j f
I
f
ij (5.3)
Z ijseries
Where
I ijf
= the post fault line current connecting the buses ‘i’ and ‘j’
series
Z ij
= the series impedance of the line connecting the buses ‘i’ and ‘j’.
Short circuit capacity (SCC) or fault level of a bus is defined as the product of
the prefault voltage and the post fault current and is given by
2
Vq0
SCC V . I f q
0
Z qq p.u.MVA (5.4)
If the prefault voltages are assumed to be 1.0 p.u then,
SCC 1 Z (5.5)
qq
Three phase (3L) fault being the most severe must be used to calculate the
rupturing capacity of circuit breakers, even though this type of fault has a low
frequency of occurrence, when compared to the unsymmetrical faults listed above.
There are, however, situations when LG fault can cause greater fault current than a
three phase fault.
Lightning
Wind damage, tree falling across lines, vehicles colliding with towers,
breaks due to excessive ice loading.
Salt spray.
Braking of one or more conductors.
Positive sequence:
The positive sequence sets have three phase currents/voltages with equal
magnitude, with phase ‘b’ lagging phase ‘a’ by 120°, and phase ‘c’ lagging phase
‘b’ by 120° as shown in figure (5.1).
Ic
Ib
Fig (5.1)
Ia
Negative Sequence:
Ic
Fig (5.2)
Ia
Zero sequence:
Zero sequence sets have three values with equal magnitude and angle. Zero
sequence sets have neutral current as shown in figure (5.3).
Ia
Ib
Ic
Fig (5.3)
The single line to ground fault, the most common type, is caused by
lightning or by conductors making contact with grounded structures.
Suppose a line to ground fault occurs on phase ‘a’ connected to ground through
impedance Zf as shown in figure (5.4).
F
a
Ia
b
Ib=0 Fig (5.4)
c
Ic=0
ZF
Fault current is calculated by
Vq0
I I I
0
(5.6)
Z KK Z KK 3Z F
a a a 0
Z KK
I a 1 1 1 I a0
I b 1 a
2
a 2 I a (5.9)
I c 1 a 2 a 2 I a
Va0 Z KK
0
I a (5.10)
Va Vq0 Z KK
I a (5.11)
Va Z KK
I a (5.12)
Post fault positive sequence bus voltages
f
V1 f V p . f Z 1K I K
f
Vk f
V p. f Z KK I K
f
VN V p. f Z NK
I Kf
(5.13)
V1 f 0 V p. f Z1K I K
0 f0
Vk V p. f Z KK I K
f0 0 f0
(5.15)
VN V p. f Z NK
f0 0
I Kf 0
Vi f V j f
Positive sequence line current I ijf (5.16)
Z ij
f
Vi f V j f
Negative sequence line current I (5.17)
Z ij
ij
Vi f 0 V j f 0
Zero sequence line current I f0
ij (5.18)
Z ij0
LINE –TO-LINE FAULT (L-L)
a
Ia=0
b Fig (5.5)
F
c
Ic
Ib
ZF
Fault current:
I a0 0 (5.19)
Vq0
I a I a
(5.20)
Z KK Z KK ZF
I f Ib
q
(5.23)
Z KK Z KK ZF
Symmetrical voltages:
Va 0 (5.24)
V V Z
a q
0
I
KK a (5.25)
Va Z KK
I a I a Z KK
(5.26)
Post fault positive sequence bus voltages
f
V1 f V p . f Z 1K I K
f
Vk f
V p. f Z KK I K (5.27)
f
VN V p. f Z NK
I Kf
Post fault negative sequence bus voltages
f
V1 f Z1K I K
Vk f
Z KK I Kf (5.28)
f
VN Z NK I Kf
Vk V p. f Z KK I K
f0 0 f0
(5.29)
VN V p. f Z NK
f0 0
I Kf 0
Vi f V j f
Positive sequence line current I ijf (5.30)
Z ij
f
Vi f V j f
Negative sequence line current I (5.31)
Z ij
ij
Vi f 0 V j f 0
Zero sequence line current I ijf 0 (5.32)
Z ij0
A three phase generator with a fault on phase ‘b’ to ‘c’ through impedance
Zf. Assuming the generator is initially on no-load, the condition at the fault K is
expressed by the following relations.
a
Ia=0
b
F
c
Ic Fig (5.6)
Ib
ZF 3Ig0
Fault currents:
Vq0
I
ZF )
a 0
Z KK (Z KK
Z 0 (5.33)
Z KK Z KK 3Z F
KK
I a (Z KK
0
3Z F )
I
Z KK Z KK 3Z F
a 0
(5.34)
I a Z KK
0
I a0
Z KK Z KK0
3Z F (5.35)
Va0 Z KK
0
I a0 (5.39)
V V V Z
a a q
0
KK aI
(5.40)
Post fault positive sequence bus voltages
f
V1 f V p . f Z 1K I K
f
Vk f
V p. f Z KK I K
(5.41)
f
VN V p. f Z NK
I Kf
Post fault negative sequence bus voltages
f
V1 f Z 1K I K
Vk f
Z KK I Kf
(5.42)
f
VN Z NK I Kf
Vk V p. f Z KK I K
f0 0 f0
(5.43)
VN V p. f Z NK
f0 0
I Kf 0
Vi f V j f
Positive sequence line current I ijf
Z ij (5.44)
f f
Vi V j
Negative sequence line current I ijf
Z ij (5.45)
Vi f0
V j f0
Start
Read line data, bus data, fault bus sub-transient reactance of each machine
Assume prefault load currents, shunt elements in transformer, transformer taps, shunt
capacitances, series resistances
Draw the prefault per phase network (positive sequence network) and
then obtain Zbus matrix using bus building algorithm
Stop
Flow chart (Unsymmetrical Fault Analysis):
START
Read the bus data, line data, fault bus, reactance of each
machine, Assume prefault voltages.
Draw the positive, negative and zero sequence networks using the
sequence impedances of the power system. Compute positive,
negative, zero sequence using bus building algorithm
YES NO
IS LG FAULT?
IS LL FAULT?
YES
Symmetrical NO
components of Symmetrical
fault current at components of
bus ‘k’ for L-G fault current at bus Symmetrical
fault are k for L-L fault are components of fault
calculated calculated using current at bus k for
using the the equations LL-G fault are
equation (5.6) (5.19) and (5.20) calculated using the
equations (5.34),
(5.35) and (5.36).
E
F
G
F G
E
Post fault positive sequence bus voltages are calculated using the
formula (5.13)
Post fault negative sequence bus voltages are calculated using the
formula (5.14)
Post fault zero sequence bus voltages are calculated using the
formula (5.15)
Phase voltages
Vp T . Vs
Phase current
I p T
. Is
Stop
Algorithm:
1. Draw the prefault per phase network (positive sequence network). Determine the
matrix using step by step bus building algorithm.
5. Obtain the post fault bus voltages using the equation (5.2).
6. Calculate the post fault line current using the equation (5.3).
1. Draw the positive, negative and zero sequence networks using the sequence
impedance of the power system and compute the positive, negative, zero sequence
impedance matrices using bus building algorithm.
2. Check if the fault is L-G Fault. If YES then go to next step else jump to step 6.
3. For the L-G fault calculate the symmetrical components of the fault current at
bus ‘k’ using the formula (5.6)
4. Determine the fault phase current using the symmetrical components obtained in
the previous step using equations (5.7), (5.8) and (5.9).
5. Symmetrical voltages can be calculated from the equations (5.10), (5.11) and
(5.12) and then jump to step 13.
6. Check if the fault is L-L fault. If YES jump to step 10 else go to next step.
7. Calculate the symmetrical components for LLG fault using the equations (5.34),
(5.35) and (5.36).
8. Determine the fault phase currents for the LLLG fault from the symmetrical
component currents obtained in the previous step using the equations (5.37), (5.38)
and (5.39).
9. Compute the symmetrical voltage components for the LLLG fault using the
equations (5.40) and (5.41) and then jump to step 13.
10. Calculate the symmetrical components for L-L fault using the equations (5.19),
and (5.20).
11. Determine the fault phase currents for the L-L fault from the symmetrical
component currents obtained in the previous step using the equations (5.21), (5.22)
and (5.23).
12. Compute the symmetrical voltage components for the LLLG fault using the
equations (5.24), (5.25) and (5.26) and then jump to step 13.
13. Calculate the post fault positive, negative and zero sequence bus voltages using
the equations (5.13), (5.14) and (5.15) respectively.
14. Determine the positive, negative and zero sequence line currents using the
equations (5.16), (5.17) and (5.18) respectively.
Problem statement
For the above circuit with X= 15% generator, Transmission line X =30% and
Transformer X = 20%, obtain
a) Fault current at fault point and post fault voltage for a bolted fault at bus 4.
b) Symmetrical fault.
c) Line to ground fault
d) Line to line fault
1 2 3 4
G1 G2
F
RESULT
Thus the fault level, post-fault voltages and currents for both symmetrical and
unsymmetrical faults were computed using MIPOWER. The obtained outputs were
also verified using hand calculations.