Professional Documents
Culture Documents
PART 1 - GENERAL
1.1 DESCRIPTION:
A. The Work shall consist of furnishing and installation of all electrical materials as
shown on the drawings and specified herein.
1.2 REFERENCES
SASO 138 Methods of test for tubular fluorescent lamps for general
lighting purposes
SASO 507 Methods of test for ballasts for tubular fluorescent lamps
SASO 1349 Circuit breakers for over current protection for house hold
and similar installations
SASO 1351 Methods of test for high pressure sodium vapor lamps.
IEC 298 AC Metal-Enclosed Switch gear and Control Gear for Rated
Voltages above 1 KV and up to 72.5 KV
ASTM D 1785 Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedule 40, 80
and 120
ASTM D 2564 Solvent Cement for Polyvinyl Chloride (PVC) Plastic Pipe
and Fittings
A. Complete list of materials and equipment proposed for incorporation in the work:
C. Samples shall be submitted for all items specified herein for Engineer’s approval
prior to placing order for procurement
E. Test Results: Provide test results for satisfactory performance of cables and other
equipment for Engineer’s review.
A. All materials and equipments specified under this section shall be provided in
manufacturer's original new and unopened packing bearing manufacturer's name
and label.
B. Store materials not in actual use in covered and well-ventilated area and protect
them from dirt, dust, moisture, direct sunlight and extreme temperatures.
1.5 WARRANTY:
A. Submit written guarantee signed by the contractor and manufacturer for the period
of 1 year from the date of substantial completion. The guarantee shall cover the
repair and replacement of defective materials and workmanship as directed by the
Engineer. If manufacturer warranties any equipment for more than one year as a
standard practice such warranties shall also be submitted.
1.6 QUALITY ASSURANCE:
C. All the components and installations shall comply with the requirements of
specified codes and standards. All equipments shall be suitable for altitude of the
site.
D. All the components and installations shall comply with the applicable seismic
requirements of project location as shown on structural drawings.
PART 2 - PRODUCTS
2.1 CONDUITS:
A. Interior Raceways: Raceways for wires inside the building, recessed in concrete
and CMU, shall be rigid UPVC conduit conforming to SASO 254/255 or Class IV
to SASO 14/15 or Schedule 40 to ASTM D 1785 with proper type of fittings such
as bell ends or terminal adapters. Rigid UPVC conduits for use in wet walls and
other wet areas locations as well as boxes & fittings shall be installed and
equipped to prevent water from entering the conduit and shall comply with the
requirements of NEC 352. Raceways for wires inside drywalls and above
suspended ceiling (except where cable trays are shown) shall be EMT conforming
to ANSI C80.3 or equivalent standards, with screw fittings. All supports for the
conduit system, bolts, straps, screws and so forth shall be of corrosion resistant
material.
B. Raceways for exterior underground installations, except where duct banks are
shown, use rigid UPVC conduit, Class IV conforming to SASO 14/15 or Schedule
40 conforming ASTM D 1785. Conduits under traffic areas shall be encased in
concrete.
D. PVC Duct Banks: Duct banks for underground utilities shall be of rigid UPVC
Class IV to SASO 14/15 or Schedule 40 conforming to ASTM D 1785 with proper
type of fittings. Duct banks to be encased in concrete under traffic areas. Size
shall be as shown on the drawings or as approved.
E. Concrete Duct Banks: Duct banks for underground utilities shall be of precast
reinforced concrete Class 30 complying with DIVISION 3 – CONCRETE. Size
shall be as shown on drawings.
F. Unless indicated otherwise on the drawings, minimum size of conduits for interior
installations shall be 20 mm diameter and for exterior installations shall be 25 mm
diameter.
G. Cable Tray and Cable Ladder: Cable tray and cable ladders shall be medium duty
with return flanges. Cable tray, cable ladders and accessories shall be
manufacturer's standard constructed of sheet steel, hot-dipped galvanized after
manufacture to ASTM A 123, Grade 35 or BS 729, Code G. Material thickness
and depth shall be manufacturer's standard suitable for the size of cable tray and
cable ladder. Cable tray shall be perforated type and supplied with galvanized
steel louvered covers (where required), support system and accessories, including
standard bends, tees, crossings, risers, connectors, reducers and bonding
jumpers. Cable ladders shall also be complete with supports and accessories.
Cable trays shall not connected to the equipment’s it serve. Size of cable tray and
cable ladders shall be as shown on the drawings. Install warning signs with black
letters on yellow ground, in English and Arabic, at visible locations on/or near
cable tray stating "WARNING! NOT TO BE USED AS WALKWAY, LADDER, OR
SUPPORT FOR LADDERS OR PERSONNEL".
1. For carpeted areas, provide open trunking system with modular lids flush
with the screed, body minimum 1.6 mm thick and lid minimum 3 mm thick.
2. For stone flooring areas, provide trunking suitable for burial in screed, body
minimum 1 mm thick and lid minimum 1.2 mm thick.
A. All boxes provided in the wiring or raceway system shall conform to SASO,
ANSI/UL 514, BS or equivalent standards and shall suit the devices installed.
B. Boxes for ordinary locations or flush installations shall be sheet steel, zinc or
cadmium plated, to meet code requirements. Boxes for flush exterior installations
shall be gasketed and hot-dipped galvanized.
C. Boxes for exposed locations subject to humid conditions shall be of cast metal
with threaded hubs. Finish shall be either cadmium/zinc electro-plate covered or
hot-dip galvanized. Boxes for exposed exterior locations shall be similar except
with gaskets.
A. General: Unless indicated otherwise, all wiring devices shall conform to SASO or
BS or CSA or NEMA Standards. Where applicable use multi-gang switches with
combinations as required to group dissimilar switches and dimmers together.
B. Device Plates: All the device plates shall be one-piece type white color,
manufactured of non-combustible mar-proof thermoset plastic with color-matching
screws; type and design shall be as selected by the Engineer. Plates for all outlets
to suit the boxes and devices installed. Device plates for telephone outlets shall be
able to accommodate a telephone jack.
C. Single or Duplex Receptacles: 60 Hz, two-phase, 3-wire, grounding type with
polarized parallel slots conforming to SASO, BS, UL 498 or NEMA 6-15R, or
equivalent Standards, voltage and rating as shown on drawings.
H. Push Buttons: Push buttons for lighting shall be general purpose, flush mounted,
conforming to SASO or BS or equivalent, standard duty, non-illuminated,
watertight, rating as shown on the drawings. Push button stations shall be for
normal ON/OFF operations.
A. The limit of the work of the Electrical Contractor shall be up to the supply terminals
of the equipment or device to be supplied by other trades. The Electrical
Contractor shall be responsible for providing the power supply and wiring/cabling
to the equipment or devices of other trades.
A. Items such as float switches, pressure switches and auxiliary relays shall have
current and voltage ratings in accordance with NEMA IC 1-18.20 for Class B
relays. All items shall be for 60 Hz and shall be UL listed.
2.6 MARKER TAPE:
A. Shall be detectable polyethylene plastic tape with metallic core, 150 mm width,
100 micron nominal thickness and obtained from approved supplier. It shall be
continuously printed in Arabic and English alternately with words CAUTION;
BURIED ELECTRIC/TELEPHONE LINE BELOW, as appropriate.
B. Manhole Covers: Manhole covers and frames shall be of gray cast iron casting,
heavy duty for traffic areas and medium duty for other areas, all complying with
ASTM A48 or BS 497, Appendix A. Type and size shall be as shown on the
drawings or selected by the Engineer. The words "ELECTRIC"/
"COMMUNICATION” as appropriate, in Arabic and English shall be cast in covers.
PART 3 - EXECUTION
B. The drawings indicate the extent and general location and arrangement of
equipment, conduits and wiring.
1. The Contractor shall study the drawings and details and in supplement to the
above mentioned drawings, all works to be done shall be in accordance with
approved shop drawings. All outlets and equipments shall be properly
located and readily accessible.
D. Should the Contractor make equipment substitution or use equipment that may
result in increased loads and changes in feeder and raceway sizes, and result in
larger protective equipment, such changes shall not be considered an additive
change order. The contractor shall provide calculations for load flow, voltage and
short ciruit for Engineers review and approval and modify feeder and raceway
sizes accordingly without any extra cost and time.
E. Install pipe sleeve seals at all foundation and wall penetrations. Conduits, cables
and cable trays passing through exterior building walls shall be caulked weather
tight. Seal conduits, cables and cable tray penetrations through fire barriers (walls
and slab) using fire barrier penetration seals as specified in relevant Section of the
Specifications or as approved by the Engineer.
A. Conduits:
1. Conduit system shall be installed in accordance with Articles 346 and 348 of
ANSI/NFPA 70.
3. Raceways shall be concealed within walls, ceilings and floors where possible
and shall be kept 150 mm away from parallel runs of flues, steam or hot
water pipes.
4. Raceways shall be supported and secured at intervals of not more than 2440
mm.
6. Field made bends and offsets for steel conduits shall be made with approved
hickey or conduits bending machine.
11. Steel conduits shall be fastened to all sheet metal boxes and cabinets with
locknuts.
12. Bushing shall be installed on the ends of all steel conduits and shall be of the
insulating type where required by ANSI/NFPA 70. Bell ends or terminal
adapter and bushings shall be installed on the ends of all PVC conduits.
13. Raceways crossing expansion joints in concrete slabs shall be provided with
suitable expansion fittings or other suitable means shall be provided to
compensate for the building expansion or construction.
16. Nail-type nylon anchors or threaded studs, driven in by a powder charge and
provided with lock washers and nuts are acceptable in lieu of expansion
bolts or machine or wood screws. Conduits larger than 25 mm diameter shall
not be installed inside structural masonry slabs.
17. Conduits larger than 25 mm shall not be installed inside structural masonry
or slab.
B. Stubbed Conduits:
1. Flexible connections shall be provided for all motors and equipment subject
to vibration or movement.
2. Boxes for metallic raceways shall be of cast metal hub type when located in
normally wet locations, when surface mounted on exterior surfaces, in
hazardous areas and when installed exposed up to 2130 mm above exterior
floors and walkways. All metallic boxes shall be provided with grounding
screw.
4. Each box shall have the volume required by ANSI/NFPA 70 for the number
of conductors enclosed in the box.
5. Boxes for mounting lighting fixtures shall not be less than 100 mm except
the smaller boxes may be used if required by the fixture configuration.
6. Boxes installed for concealed wiring shall be provided with suitable extension
rings or plaster covers, as required.
7. Boxes for use in masonry walls shall be square cornered tile type or
standard boxes having square cornered tile type covers.
8. Cast metal boxes installed in wet locations and boxes installed flush with the
outside of exterior masonry surfaces shall be gasketed.
c. Where bar hangers are used, the bar shall be attached to raceways on
opposite sides of the box and shall be supported with an approved type
fastener not more than 356 mm from the box.
1. Boxes shall not be less than 38 mm deep except where shallower boxes
required by structural conditions are approved.
2. Boxes for other than lighting fixture outlets shall not be less than 100 mm
square except that 100 mm x 50 mm boxes may be used where only one
raceway enters the outlet.
G. Pull Boxes:
1. Pull boxes shall not be less than the minimum size required by ANSI/NFPA
70 and shall be constructed of galvanized steel or cast metal boxes.
3. Where several feeders pass through a common pull box, the feeders shall
be tagged to indicate clearly the electrical characteristics, circuit number and
panel designation.
A. Device plates shall be installed with all four edges in continuous contact with
finished wall surface without use of mats or similar devices.
3.4 TESTS:
A. After the interior wiring system installation is completed, the Contractor shall
conduct an operating test for approval.
E. Cable, GFCI receptacles test and circuit breaker testing, and testing in general
shall be as per the National Electric Code.
F. All phase balancing and loading tests shall be accomplished and data of such
tests shall be submitted to the Engineer.
END OF SECTION