This document provides specifications for a low voltage recirculation pump motor for a fuel farm complex and fuel hydrant at Bahrain International Airport. The motor is rated for 30 kW, operates at 400V AC, 3 phase, 50Hz, and has an IP55 degree of protection. It has a TEFC cooling type and Class F insulation with temperature rise limited to Class B.
This document provides specifications for a low voltage recirculation pump motor for a fuel farm complex and fuel hydrant at Bahrain International Airport. The motor is rated for 30 kW, operates at 400V AC, 3 phase, 50Hz, and has an IP55 degree of protection. It has a TEFC cooling type and Class F insulation with temperature rise limited to Class B.
This document provides specifications for a low voltage recirculation pump motor for a fuel farm complex and fuel hydrant at Bahrain International Airport. The motor is rated for 30 kW, operates at 400V AC, 3 phase, 50Hz, and has an IP55 degree of protection. It has a TEFC cooling type and Class F insulation with temperature rise limited to Class B.
Data Sheet - Low Voltage Motor (Recirculation Pump Motor)
Client Bahrain Airport Company Division Oil, Gas & Petrochemicals-Dubai
Project No. 352911 / DP1115 Document No. 352911/DA3112 Project Title. Fuel Farm Complex and Fuel Hydrant at Bahrain International Airport Page 1 of 1 Rev. 02
1 Equipment No. PM15 59 No load current * %FLC
2 Quantity (Running / Standby) One(1) 0 60 Locked Rotor Current * %FLC Main storage tank stripping and 3 Description 61 Insulation Class class recirculation * 4 Rating (kW) Note 4 30 62 Temperature rise * class 5 Supply Parameter 400Vac 3 ph 50Hz 63 Thermal rating constant * sec 5a System Fault Level & duration 65kA for 1 sec 64 Starting current with 100% V * %FLC 6 Space heater voltage / Cable Size 230 Volts, 50Hz, 1ph / 3C X 4mm² 65 Starting Current with 80% V * %FLC 7 Area Classification/Gas Group Note 9 66 Starting time with 100% V * sec 8 Type of explosion protection EEx (e) / EEx(n) 67 Starting torque with 100% V * %FLT Class F insulation with Temp rise 68 Starting Torque with 80% V SPECIFICATION
9 Class of winding insulation %FLT
limited to Class B * 10 Degree of protection IP 55 69 Starting time with 80% V * sec 11 Cooling TEFC 70 Locked Rotor Withstand time Refer cable schedule - 12 Power cable Type / Size 70a Hot sec 352911/DA3105 * 13 Duty S1 - Continuous. 70b Cold * sec 14 Winding Temperature Detectors Required (Thermistors/ RTDs) 71 Safe stalling time cold * sec 15 Bearing Temperature Detectors Not Required 72 No of starts Hot * nos 16 Vibration sensors Not Required 73 No of starts Cold * nos 17 Applicable standard IEC 60034 74 Locked Rotor Torque * %FLT 18 Direction of Rotation Bi-direction 75 Pull out Torque * %FLT 19 Stator Winding connection Star / Delta 76 Starting shaft torque * %FLT Refer Site Datasheet - 20 Design Ambient Temperature 77 Break down shaft torque %FLT 352911/DA0001 * Soft Starter with bypass provision 21 Starting Method 78 Pull-up shaft torque %FLT (Refer Note 11) * 22 Type of load * 79 Rated shaft torque * %FLT 23 Installed Rating * 80 Rated power factor * 24 Absorbed Power Max. * 81 Starting power factor * DATA TO BE FURNISHED BY EQPT.VENDOR
25 Motor speed (Synch.) * 82 Locked Rotor pf *
VENDOR CONFIRMATION
26 Type of mounting * 83 Efficiency @
27 Transmission * 83a 100% FL * 28 Shaft Extension * 83b 50% FL * 29 2 * 83c At absorbed Power Inertia of load GD ( At motor speed) * 30 Starting Torque required * 84 Method of starting * Soft starter / DOL 31 Starting and running duties required * 85 Acceleration time * 32 Starting time limitation (if any) * 86 a) DOL start * sec 33 No. of starts/hour( start duty ) * 87 b) Assisted start n.a. 34 Motor starting against load * 88 i) Star /delta n.a. 35 unloaded * 89 ii) Auto transformer (tap %) n.a. 36 Type of Enclosure * 90 iii) Soft starter (Ist= %FLC) * sec 37 Dir. Of Rotation of motor (viewed from DE) * 91 stator connection star/delta * 38 Special Requirement * 92 te time (Exe motors) * Note: Equipment vendor to furnish speed / torque 39 93 GD2 of rotor(kg m2) curve for driven equipment * 40 Bearing Ref temperature DE * 94 Insulation Class * 41 Bearing Ref temperature NDE * 95 Temperature rise(by res) * MECH. DIM.& WT. DATA BY
42 Bearing type DE * 96 Duty *
MOTOR VENDOR
43 Bearing type NDE * 97 Type of enclosure *
44 Bearing Lubrication * 98 Degree of protection (enclosure) * 45 Net Weight * 99 Direction of rotation (viewed from DE) * 46 Shipping Weight * 100 Main Tb cable size & no.of entries * 47 Over All Dimension(mm) * 101 Neutral terminal box detail * 48 Out line drawing * 102 Noise(db at 1 meter) * 49 any other information * 103 Space heater Provision/wattage * 50 104 Wdg temperature protection n.a. 46 Manufacturer details * 105 Motor thermal time constant * min 47 Country of Origin * 106 Max. allowable -ve ph seq.current * %FLC 48 Nearest Service station details * 109 Acoustic noise at full load * dB VENDOR CONFIRMATION
50 Mounting Type * 111 Winding thermisters details * 51 Type of Rotor * 112 Insulated bearings n.a. 52 Duty * 113 Vibration sensor details n.a. 53 Efficiency class of motor * 114 Anti condensation heater details * 54 Voltage * Volt 115 location of cable terminal box * 55 Rating * Kw 107 Certification Standard * 56 No.of Poles * nos 108 Certification Authorities * 57 Rated Speed * Rpm 58 Full load Current * Amp. NOTES: 1. Motor vendor to furnish following characteristic curves for motor: a. Speed v/s Torque , Efficiency v/s Current , Power factor v/s Current. b. Motor starting curves (Current Time ) with 100% & 80% of rated voltage. c. Thermal withstand curves (hot as well as cold ) at 100% & 80% of rated voltage. 2. Testing of motors to be in accordance with IEC 60034. 3. Vendor to confirm selection and materials of construction and should return one completed (see * marks) or corrected copy to Engineer. 4. Motor rating is only indicative and to be confirmed based on the selected pump. Contractor to refer to Mechanical Datasheet for Pump 352911/DA1109 5. Motor shall be compatible with the load characteristics and operational duty of the driven equipment. The motor shall be suitable for intermittent operational requirement. 6. Motor shall be mounted on base frame & coupled to the pump at factory, the alignment between motor and pump shall be using laser or equivalent technique. 7. Interlock shall be provided with the LV switchgear for the operation of the space heaters. 8. This data sheet should be used in conjunction with the technical specification TS306. 9 Shall be Ex e Group II , Temperature Class T3. 10. External Painting-Corrosivity category C5M with Medium Durability as per BSEN ISO 12944-5 11. Motor shall be suitable for starting & running on Soft starter as well as DOL mode. 12. Motor bearing shall not take the axial loads 13. Motor terminal box shall be suitable to rotate in steps of 90 deg. 14. Factory and site acceptance test shall be ensured by contractor, In addition to third party inspection during FAT shall be arranged as minimum. 15. One year operating & commissioning spares shall be supplied. REV DATE DESCRIPTION ORIGNR CHKD APPD. 00 09/02/16 Preliminary SW VT ADS 01 15/06/16 For Approval SW VT ADS 02 02/08/16 Issued for Tender SW VT ADS PLEASE NOTE: THIS DATASHEET SHOULD NOT BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIALS UNTIL IT IS APPROVED.
P:\Dubai\ONG\DUO Sub Div\ProjDocs\2015\DP1115- BAC-Fuel Farm-BIA\ENGG\03_Electrical\Documents\Fuel Depot\Datasheets\02.08.2016\352911_DA3112-Recirculation pump motor (01)