Professional Documents
Culture Documents
216:4 ½M½L½T2
poundal lbwt
50 ½L 2
1 2
! 4:328 psi ½M½L ½T
FIG. 30.6 Pump suction pressure control eliminates discharge level control valve and level taps on pressure vessel.
As the required pump NPSH was 12 ft, I decided to set the pump suction pressure to
provide six extra feet of extra head. That is, 18 ft of head. One inch of Hg is equal to about
1.2 ft of warm water. Therefore:
180 1:2 ¼ 1500 Hg (30.5)
The vacuum degassing tower operated at 2500 Hg vacuum, my set-point pressure would be:
2500 Hg 1500 Hg ¼ 1000 Hg vacuum (30.6)
Actually, I lied about the above calculation. What I really did was to manually lower the
suction pressure until the pump cavitated a little. Then, I set the suction pressure about 500
Hg higher. All done without reference to the actual tower water level, which was below the
lower level tap, and hence not visible.
I checked the ambient temperature 102°F. Not a cloud in the sky. I recall thinking, “I’m
getting too old for this stuff. But, I do love it.”
Does this mean level control for pump’s suction is an engineering error? Yes! Use suc-
tion pressure control—at least for vacuum tower service (see Fig. 30.6).
In addition to the oppressive heat, I ran into another problem on this job. The pump’s
suction screen was located downstream of the sensing point for the pressure transmitter.
So, when the suction screen plugged during that night, the pump began to cavitate due to
loss of suction pressure.
The next morning, I revised the suction screen with larger openings. The lesson is that
when retrofitting a pump to suction pressure control, the suction pressure sensing point
must be located downstream of the suction screen and never upstream.
Chapter 30 • Centrifugal Pumps: Required Starting NPSH 239
The people I work with in refineries are most often honest, ethical, dedicated, and con-
fused. It is the complexity of the process equipment that is the origin of the confusion.
And, the most confusing sort of process equipment is compressors.
There are three sorts of compressors that I have worked with:
• Centrifugal
• Axial
• Reciprocating
To determine your own CI (i.e., Confusion Index), please take the following test:
• Question #1—A motor-driven centrifugal compressor which is running at a constant
speed, at a constant volume of gas flow and temperature at the suction, and at a
constant suction and discharge pressure. The molecular weight of the gas now
increases from 20 to 40. What happens to the motor’s amp load?
• Answer #1—There is no answer. Both the suction and discharge pressure (i.e., the
compression ratio) cannot be kept the same. Why? Because the machine is developing
a fixed amount of head or feet. The pressure ratio is a function of the molecular weight
of the gas. So, if the molecular weight goes up, so must the compression ratio. Either the
suction pressure is drawn down or the discharge pressure is pushed up, or both.
• Question #2—Same as above, except now I will permit the suction pressure to drop due
to the larger molecular weight. The discharge pressure is still kept constant. What now
happens to the motor amps?
• Answer #2—The amps go up. Not because the heavier, higher molecular weight gas is
harder to compress. Just the opposite is true. Fifty-eight molecular weight butane
requires 15% less amps to compress than 16 molecular weight methane, for a certain
volume of gas. The amps on the motor increases, because the compression ratio
(discharge pressure divided by the suction pressure) has increased, even though the
compressibility factor (Z) has dropped by 15% for butane, as compared to methane.
• Question #3—A reciprocating compressor, running at a fixed speed with a motor driver,
handling a fixed volume of gas, and with both the suction and discharge pressures
constant, is compressing methane (16 MW). It now switches to compressing propane
(44 MW). What happens to the motor amps?
• Answer #3—The amp load goes down by about 10%. Why? Because “Z” the
compressibility factor of the gas goes down by 10%.
• Question #4—For a variable speed centrifugal compressor, if I need to keep both the
suction and discharge pressure constant, and the suction volume and suction
temperature are constant, and the molecular weight of the gas is increasing, should I:
where:
• K ¼ a coefficient proportional to the air density that converts feet of polytropic head
to pressure
• Hp ¼ feet of polytropic head
The important thing to understand about both axial and centrifugal compressors is they
both develop the same feet of head, regardless of the density of the gas being compressed.
If the air gets hotter, because it’s summer time in Louisiana, then the discharge pressure
from the Axial Air Compressor drops off, but the feet of head developed remains constant.
Thus, if the air blower discharge pressure was too high in the winter, we could:
• Throttle on the suction.
• Slow the blower’s speed.
• Get the axial air compressor’s blades really dirty, as happened at the Marathon plant
in Garyville.
Centrifugal Compressors
Fig. 31.1 shows a picture of a centrifugal compressor’s rotating assembly. Instead, of blades
spinning around a shaft, there are wheels. The wheels impart kinetic energy to the gas
from the rotational energy of the wheels. As the gas escapes from each wheel, it flows into
a circular stationary chamber called the “Stator.” Inside the stator, the gas slows. And, the
kinetic energy imparted to the gas from the wheel is converted into feet of head. To convert