Professional Documents
Culture Documents
Level Indication
Liquid levels are not measured directly. They are indirectly measured by means of a
“Level-Trol” (see Fig. 41.2). The pressure difference (DP) between P1 and P2 (psi) is mea-
sured and then converted into inches of level (DH) by use of Eq. (41.1):
DH ¼ ðDPÞ ð28Þ ðSGÞ (41.1)
Flow Measurement
Flows are indirectly measured by use of a flow orifice plate. The DP across the orifice plate
is measured and then converted to flow using Eq. (41.2) (see Fig. 41.2).
Flare
Flare
CW
Level
trol
Level
output
Flow ¼ ðK 4P Þ½ (41.2)
In the 1960s, when flows were indicated on a strip chart recorder, we made this correc-
tion with a pencil, as the paper strip was already calibrated for the square root function.
With a digital display, this correction must be made with Eq. (41.3).
Chapter 41 • Plant Safety Fundamentals 325
Background
I worked as an operating supervisor in Texas City, and as a process engineer in Chicago for
Amoco Oil between 1965 and 1981. I designed 7% of the process equipment in Texas City
(Cokers, Sulfur Recovery, Light Ends Fractionation, Amine System, Fuel Gas Treating). For
the distillation towers I supervised (Debutanizer, Butane Splitter, Depropanizer, Butane-
Pentane Splitter), all relief valves were located at the top of the towers. All relieved directly
to the atmosphere. The reason I did not object to this design was because it was that way
when I had assumed supervision of the process. Also, the towers had been commissioned
in 1958 and nothing had happened “YET.” What would result if a tower flooded due to a
high liquid level was not a question that I considered.
50 psig
vapor line
Blowdown Raffinate
splitter
Loop FD
Relief
seal flow
valve
To
condenser
No
flow
3 psig
FIG. 41.3 Raffinate splitter—Texas City.
1. Design of the loop seal draining the Blowdown Tower to the 3# condensate collection
system.
2. Elevation of the splitter relief valves relative to the top of the tower.
3. Lack of technical support during start-up operations.
4. Operators not understanding the relationship between tower bottom temperature and
tower bottoms indicated level.
5. Operators not understanding the concept of a level-trol being “Tapped-Out.”
6. Failure to check liquid head pressure at the bottom of the tower.
During the Raffinate Splitter start-up, the liquid in the bottom of the tower was less dense
than normal. Thus, the indicated level observed on the control panel was lower than the
actual level. Unfortunately, when the liquid fills the space between the lower and upper
level taps, the differential pressure measured between the level taps remains constant,
regardless of how high the liquid level becomes (Fig. 41.2). This is called being
“Tapped-Out.” If the specific gravity of the liquid is 10% higher than normal, the indicated
level on the panel will read 110%. But, if the specific gravity of the liquid is 10% lower than
normal, the indicated level on the panel will read 90%. As the level rises by 10 ft, or 100 ft,
above the top level connection, the indicated level will remain at 90%. Which is exactly
what happened at Texas City.